ST9302-CS 970128January 28, 1997
City of Dallas
O?'31-979PO3925-Ni
Paul M. Hanes, P.E.
Project Manager
Kimley-Horn and Associates, Inc.
910 Collier Street
Fort Worth, Texas 76102
Sandy Lake Road from Denton Tap To MacArthur Blvd.
Review Comments for 30" RC Water Design
My staff has reviewed your preliminary plans showing proposed
alignments for the 30" water transmission-
Our comments are as follows:
1.) The profile for the 30" DWU Water main coincides with
Coppell's 36" water. Provide a separate profile for the 30"
main.
2.) Maintain a minimum cover of 6 Ft. for the proposed 30" main
throughout the paving limit.
3.) The proposed 30" main must clear all utility crossings a
minimum vertical clearance of 0.50 Ft.
4.) Use grade breaks or vertical curves in lieu of vertical
bends, in particular at sta. 6+50 to 7+75.
5.) Limit the extent of water main replacement within the
proposed pavement. Make connections to the existing main 5 Ft.
off paving limits.
We are returning your preliminary half-size plan marked with
comments. Please provide us with a cost estimate to construct
the 30" Water main to update our funding for this project.
Also, we are supplying you the enclosed copy of DWU plan
41iQ308D Sh. 1,3,4 r~ 14 of our Maple ~venue project~ showing in
particular the relocation of a 36" water main for your
reference.
Please call me or Jun Battad at tel. 918-4591 if you have any
questions.
Brian H. Cowan, P.E.
Project Manager
Relocations/Dart
Attachment
c:.~.~if~-:eoppell.~ J. Milstead, J. Battad, File 97028AB1
Water Utilities Department
Development Services ® 320 E. Jefferson, Room 218 · Dallas, Texas 75203 · 214 / 948-4590