SS9402C-LR 980723Compaction Test Report Patton, Burke & Thompson 10555 Newkirk Street Suite 530 Dallas, Texas 75220 CLIENT CII~OF COPPELL 225 PARKWAY BLVD. P. O. BOX 478 COPPELL, TEXAS 75019 DATE 07/23/98 ;OB NO .1532 REPORENO 32 SHEET ! OF SUBJECT BETHEL ROAD SEWER LINE BACKFILL REPAIRS COPPELL, TEXAS CEMENT TREATED BASE PREPARATION SPECIFICATIONS: 95 % OF MAXIMUM ASTM D 698 MOISTURE WITHIN % OF OPTIMUM P/PE OF COMPACTION EQUIPMENT AND NO OF UNITS: VIBRATORY SHEEPSFQOT RO£LER (11,. PNUEMATIC ROLLER (1) MOISTURE ADDED BY THICKNE~OF LIFT 8 INCHES D/PE OF EARTH MOVING EQUIPMENT AND NO OF UNITS: THIS REPORT PRESENTS OPINIONS FORMED AS A RESULT OF OUR OBSERVATION OE EILL PLACEMEN~ AS WELL AS THE TESTS SHOWN ABOVE. WE HAVE RELIED UPON THE CONTRACTOR TO APPLY THE NECESSARy COMPACTIVE EFFORT AND MOISTURE TO ACHIEVE SPECIFIED COMPACTION DURING TIMES WHEN OUR OBSERVER IS NOT PRESENt AND AT LOCATIONS OTHER THAN THOSE TESTED. TEST DATA ARE NOT THE SOLE BASIS FOR OPINrONS ON WHETHER THE FILL MEETS SPECIFICATIONS PROGRESS REPORT AS REQUESTED, PBT MADE A SITE VISIT TO OBSERVE THE PLACEMENT OF CEMENT TREATED BASE MATERIAL IN THE AREAS WHICH WERE OVERCUT IN THE AREAS OF CTB WHICH WERE LEFT IN PLACE. THE CTB MATERIAL WAS A MIXTURE OF PREVIOUSLY RECLAIMED MATERIAL FROM BETHEL ROAD WITH 5.5% CEMENT ADDED. WE ADVISED GARRETH WITH THE CI;Y OF COPPELL THAT WE DID NOT HAVE A MAXIMUM DRY DENSITY ESTABLISHED FOR THIS MATERIAL YET. (CONTINUED ON SHEET 2 OF REPORT NO. L] IN OUR OPINION, FILL COMPACTION DOES NOT MEET SPECIFICATIONS AS INDICATED BY OUR OBSERVATIONS AN D TEST NOJSJ ~ ~ J HAMMERBERG.~ SCOPEOFOBSERVATION: ~ FULLTIME- F~ PERIODIC ONCALLBASIS. ~ CONTRACTOR'SORCUENT'SREPRESENTATIVEADVISEJ:J;,'~JK~.~o,,***,o**--***.* w.. ; Compaction Test Report Patton, Burke & Thompson 10555 Newkirk Street Suite 530 Dallas, Texas 75220 CLIENT: CIIY OF COPPELL 225 PARKWAY BLVD. P. O. BOX 478 COPPELL, TEXAS 75019 07/23/98 1532 DATE 32JOB NO 2 2 - REPORT NO BETHEL ROAD SEWER LI~H~E~CI~EL REPAIRS SUBJECT COPPELL, TEXAS CEMENT TREATED BASE PREPARATION LABORATORY FIELD TEST DEPTH TEST MAX OMC DRY MC COM- 95 ASTM D 698 SPBCIFICATIONS: % OF MAXIMUM MOISTURE WITHIN % OF OPTIMUM 1YPE OF COMPACTION EQUIPMENTAND NO OF UNIT~ E R ~FI. EEPSFOOT ROL~._ER (1), pNUEMAI~ED ROLL (11 MOISTURE ADDED BY THICKNES~ OF LIFT 8 INCHES T~'PE OF EARTH MOVING EQUIPMENT AND NO OF UNITS: THIS REPORT PRESENTS OPINIONS FORMED AS A RESULT OF OUR OBSERVATION OF FILL PLACEMEN[ AS WE LL AS THE TESTS SHOWN ABOVE WE HAVE I~ELIED UPON THE CONTRACTOR fO APPLY 1HE NECESSARY COMPACTIVE EFFORTAND MOISTURE lO ACHIEVE SPECIFIED COMPACTION DURING TIMES WHEN OUR OBSERVER IS NOT PRESE N[ AND AT LOCATIONS OTHER THAN THOSE TESTED f EST DATA ARE NOT THE SOLE B~SIS FOR OPINIONS ON WHETHER THE FILL MEETS SPECIFICATIONS PROGRESS REPORT [CONTINUED FROM SHEET 1 OF REPORT NO. 32). GARRETH ADVISED US TO CONTINUE TO OBSERVE PLACEMENT OF THE CTB AND THAT COMPACTION TESTS WOULD NOT BE REQUIRED ON THESE AREAS. BASED UPON VISUAL OBSERVATION OF THE CONTRACTOR'S METHODS AND INFORMATIONAL NUCLEAR WET DENSITY TESTS, WE BELIEVE THE CONTRACTOR PLACED AND COMPACTED THE CTB IN AN ACCEPTABLE FASHION.