SS9901-CS040701 (3)~UL 0~ ~004 10:~
Turner Collie . Braden Inc.
9?2 ?35 5002
FR TURNER COLLIE& BRADEN9?2 735 5002 TO 99725045570 P.01/02
17300 D~II~
Suite 10t0
Dallas, Texas
Fax: (972) 73~-8001
Engineers · Planners ' Project Managers
DATE: ~ 01, 2004
TO: Rick O' Dell
FROM: George Cisneros
# OF PAGES inc, lud n!
FAX NUMBER: (972) 304-3570
PHONE NUMBER: (972) 735-3074
(If transmil~al is incomplete or unclear, please
call sender directly at this number.)
An AECOM Company
JUL 01 2004 10:42 FR TURNER COLLIE& BRADENg?2 ?55 5002 TO 99?250455?0 P.02/02
Turner Collie __ Braden lnc
TRANSMITTAL
To:
From:
Date:
Job No.:
Subject:
See Distribution
George Cisneros, P.E. - TCB
July 01, 2004
052 131124.0001 0~000.A123 (2.1)
Deforest and Sandy Lake Wastewater Lift Stations and Force Main Improvements
Force Main Lines A&B
Shop Drawing Review Comments
Submittal No. 2
TCB has the following comments on this submittal:
Description Status Comment
Concrete Mix Design No Exceptions Taken
for CIP MH Structures
MH pipe to manhole Rejected Contractor to install Kef-n-seal boot
connector* assembly;
MH Rubber Gasket for Rejected Manhole sechon joints to be sealed with
Section Joints* Ramnek strips;
Detectable Tape Revise and resubmit Per G~neral Notes, detector tape shall state
in a minimum of 1%" letters "Pressurized
Wastewater' continuously along the tape;
D.I. Pip~* ..... Submit Specified Item
When you re-submit the shop drawings, please address all comments and submit six (6) copies to this
office. Comments noted with an asterisk (*) above were noted in our previous review but not
addressed in this submittal.
Distribution:
IX] 2 copies of submittal to the City
[X] 3 copies of submittal to C.J. Louis Construction of Texas
[X] 1 copy of submittal to TCB file
[ ] Other
1/1
TOTAL PAGE.02 **