Freeport NIP(8.0)-CS040610DEVELOPMENT REVIEW COMMITTEE
ENGINEERING COMMENTS
ITEM:
Duke-Freeport Addition~ Lots 6 and 7~ Block AT Replat, being a replat of
a portion of Lot 2, Block A, to allow the construction of a 140,000-square-
foot building on Lot 6 and a 70,000-square-£oot building on Lot 7, totaling
approximately 14.13 acres o£property located along the west side o£ Freeport
Parkway, south of Creekview Drive, at the request of Duke Realty
Corporation.
STAFF REP.: Matt Steer PROJECT ID# RP-04-0036
DRC DA TE: May 27, 2004 and June 3, 2004
CONTACT: Kenneth M. Gri~n, P.E., Dir. o~Engineerin~/Public Works 972/304-3686
COMMENT STATUS: ~ FINAL
Water & Sewer Plan -
I. The fire line on Sheet C4.0 shows tying into the existing system on Lot 5 Block A. That is a
privately owned and maintained system and as such needs to remain independent of this fire
line. Loop your fire line exclusive of this property.
2. The same is true of the fire line on Lot 6 versus Lot 7 those also need to be independent of
each other.
3. This is also true of the water and sewer service to these two buildings. You cannot combine
the services, they must be independent which will require the extension of the existing 8"
sanitary sewer onto Lot 7 and two service lines, one for Lot 7 and one for Lot 6.
4. Water service will need to be relocated from Lot 7 to Lot 6 to serve the Lot 6 building as
well.
Additional comments may be forthcoming during the full engineering review.