SS9901-SP040614Turner Collie ( Braden Inc.
To:
From:
Date:
Job No.:
Subject:
See Distribution
George Cisneros, P.E. - TCB
June 14, 2004
052 131124.0001 04000.A123 (2.1)
JOB#1 .
DATE T--R:9 SMITTAL
AHL
PJS
Deforest and Sandy Lake Wastewater Lift Stations and Force Main Improvements
Force Main Lines A&B
Shop Drawing Review Comments
Submittal No. 1
TCB has the following comments on this submittal:
Description Status Comment
Storm Water Pollution Received ~
Prevent Plan
Trench Safety Received N Oh:
Plan/Specifications ~-
Traffic Control Plan Received f
Type B-2 Embedment No Exceptions Taken
Type C Embedment No Exceptions Taken
HDPE Pipe & Fittings Make Corrections Noted; HDPE to be D.I.P.S; Per Specification
Submit Specified Items Section 02643, HDPE fittings cut sheets
shall be submitted;
HDPE Fusion Water No Exceptions Taken
Qualifications
HDPE Driller No Exceptions Taken
Experience Record
8 Mil Polyethylene Pipe No Exceptions Taken
Wrap
SDR 26 PVC No Exceptions Taken
Gate Valves No Exceptions Taken
D.I. Fittings Make Corrections Noted Clarify Meglug retainer glands are to be
used for this project, not Tyler retainer
glands;
Precast Manholes Make Corrections Noted There are no flat top manholes in this
project; use regular type manhole reducing
cone;
MH pipe to manhole Rejected Contractor to install Kor-n-seal boot
connector assembly;
MH Rubber Gasket for Rejected Manhole section joints to be sealed with
Section Joints Ramnek strips;
Lifting bodies with No Exceptions Taken
eyelinks or chains
Concrete Mix Design No Exceptions Taken
(mortar)
Line A&B
06/14/04
Page 2
Manhole Ring & Cover No Exceptions Taken
Casing Spacers No Exceptions Taken
Combination Sewage No Exceptions Taken Per the fax received by TCB on June 9,
Air Valve 2004 by Jim Cox Sales, Inc., it is
understood ARI D-020 combination air
valves will be used for this project;
Flange Bolt & Gasket No Exceptions Taken
Set
Megalug Retainer No Exceptions Taken
Gland
Detectable Tape Revise and resubmit Per General Notes, detector tape shall state
in a minimum of 1 ½" letters "Pressur/zed
Wastewater" continuously along the tape;
D.I. Pipe Submit Specified Item
When you re-submit the shop drawings, please address all comments and submit six (6) copies to this
office.
Distribution:
[X] 2 copies of submittal to the City
[X] 3 copies of submittal to C.J. Louis Construction of Texas
IX] 1 copy of submittal to TCB file
[ ] Other