Loading...
Freeport NIP(8.0)-CS040812SPRINKLER August 12, 2004 Mr. Keith Martin City of Coppell Engineeking ~'/" Re: ~'~:~eepor't:_ XZI & X]! Via Fax: g72-304-3570 Keith, This memo is regarding the underground fire line at Freeport XI & XII. A 2000 gpm fire pump will be installed and is required by code t:o be fed with a 10" suction Fine, We are tapping the 8" fire loop with 10' lead in to the building. NFPA does not prohibit this arrangement and is subject only to limitations of verocities that are indicated in our calculations, We are submitting calculations to Tim Qates of the Coppell Fire Department for review, Should you have any further questionsl please do not hesitate to contact me, Alan .]ones ]P:aJ TEXAS SPRINKLER 803 STADIUM DRIVE, SUITE 106 · ARLINGTON, TEXAS 7601 (817) 461-0344 · FAX: (817) 461-0624 TFXA~ ,~TAT[: CFRTIFICATION REGIRTRATION NO