Concrete Compression Test Report
Client: Prime Construction Company Report Distribution: (1) Houghton Capital
Project: Secur -Lock Self Storage (1) Prime Construction Company
Coppell, Texas (1) City of Coppell
( )City of Coppell
(1) AECC Inc.
TMI Report No.: FCO3- 63414 -049
Report Date: 09/07/2004
Specifications
66059
Test Data
Strength
3500 psi @ 28 Days �
Placement Date
08/09/2004
Slump
3 in min 5 in max
Sampled By
Ambient Temperature: 80° F
Air Content
3 % min 6 % max
Weather
Cloudy
Concrete Temperature
n/a
Supplier /Mix
So. Star /9339
Ambient Temperature
n/a
Air Content Method
ASTM C -231 -B
Field Data'Set #1
Ticket Number:
66059
Time Batched: 2:06
Time Sampled: 2:30
Slump:
4.5 in
Air Content: 4.5%
Unit Weight: n/a
Concrete Temperature:
89 F
Ambient Temperature: 80° F
Yardage (c.y.): 50
Placement Location:
Paving
1
SLCO8090402
Sample Location:
20'S. & 10'E.
From The N.E. Corner of Building C
28.27
Coil Compres's ori'Test Results
Set #
Cylinder
y #
Test Date
Age
(days)
Max Load
(lbs. force)
Area
(sq.in.)
Strength Fracture
(psi) Type
1
SLCO8090401
08/16/2004
7
83974
28.27
2970
1
SLCO8090402
08/23/2004
14
103837
28.27
3670
1
SLCO8090403
09/06/2004
28
111259
28.27
3930
1
SLC08090404
09/06/2004
28
115642
28.27
4090
28 day average
4010
Normal cylinder size: 6" x 12"
Field and laboratory tests by TMI are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
TMI was on site as requested to verify the placement of reinforcing steel for the paving of firelanes between building B - H.
Reinforcing steel was verified for conformance with ASTM A 605 for grade, size and quality. Configuration, minimum
clearance and spacing were per the approved construction documents with no discrepancies noted. The following
renresentativeriere notified. Tim /PCC
Terra - Mar /U.S. Labs Kevin T. Wells
Construction Division Manager
The results presented in this report pertain only to the specific Hems tested. This report was produced for the exclusive use of the client. Any reproduction of
this report, or any part therein, is strictly prohibited without the express written consent of TMI.
01
Page t of
"ES GEOTECHNICAL, ENVIRONMENTAL AND MATERIALS ENGINEERS
DALLAS FORTWORTH HOUSTON AUSTIN LONGVIEW
2400 Gravel Dr., Building 25 Fort Worth, Texas 76118 -6935 Voice: (817) 264 -9363 Fax:(817) 284 -9430
Concrete Compression Test Report
Client: Prime Construction Company Report Distribution: (1) Houghton Capital
(1) Prime Construction Company
Project: Secur -Lock Self Storage
Coppell, Texas (1) City of Coppell
(1) City of Coppell
(1) AECC Inc.
TMI Report No.: FCO3- 63414 -049
Report Date: 09/07/2004
specifications
Cylinder
#
Test D ata _
_
Strength
3500 psi @ 28 Days
Placement Date
08/09/2004
Slump
3 in min 5 in max
Sampled By
7
Air Content
3 % min 6 % max
Weather
Cloudy
Concrete Temperature
n/a
Supplier /Mix
So. Star /9339
Amb i e nt Te
n/a
Air Content Method
ASTM C -231 -B
Field Data Set #02'
Ticket Number: 660676 Time Batched: 3:51 Time Sampled: 4:45
Slump: 5 in Air Content: 4.5% Unit Weight: n/a
Concrete Temperature: 90° F Ambient Temperature: 76° F Yardage (c.y.): 200
Placement Location: Paving
Sample Location: 10' N. & 15'E. from The N.W. Corner of Building D
'Conerete Compression Test Results
Set #
Cylinder
#
Test Date
Age
(days)
Max Load
(lbs. force)
Area
(sq.in.)
Strength Fracture
(psi, Type
02
SLCO8090405
08/16/2004
7
88272
28.27
3120
02
SLC08090406
08/23/2004
14
86830
28.27
3070
02
SLC08090407
09/06/2004
28
101844
28.27
3600
02
SLC08090408
09/06/2004
28
104384
28.27
3690
28 day average
3650
Normal cylinder size: 6" x 12"
Field and laboratory tests by TMI are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
TMI was on site as requested to verify the placement of reinforcing steel for the paving of firelanes between building B - H.
Reinforcing steel was verified for conformance with ASTM A 605 for grade, size and quality. Configuration, minimum
clearance and spacing were per the approved construction documents with no discrepancies noted. The following
representatives were notified, Tim /PCC
fat
Terra - Mar /U.S. Labs Kevin T. Wells
Construction Division Manager
The results presented in this report pertain only to the specific Items tested. This report was produced for the exclusive use of the client. Any reproduction of
this report, or any part therein, is strictly prohibited without the express written consent of TMI.
Page 2 of 4
01
4 GEOTECHNICAL, ENVIRONMENTAL AND MATERIALS ENGINEERS
DALLAS FORTWORTH HOUSTON AUSTIN LONGVIEW
2400 Gravel Dr., Building 25 Fort Worth, Texas 76118 -6935 Voice: (817) 284 -9363 Fax:(817) 284 -9430
IV Concrete Compression Test Report
Client: Prime Construction Company Report Distribution: (1) Houghton Capital
(1) Prime Construction Company
Project: Secur -Lock Self Storage
Coppell, Texas (1) City of Coppell
(1) City of Coppell
(1) AECC Inc.
TMI Report No.: FCO3 -63414 -049
Report Date: 09/07/2004
Data
Strength
3500 psi @ 28 Days
Placement Date
08/09/2004
Slump
3 in min 5 in max
Sampled By
90° F Ambient Temperature: 73° F
Air Content
3 % min 6 % max
Weather
Cloudy
Concrete Temperature
n/a
Supplier /Mix
So. Star /9339
Ambient Temperature
n/a
Air Content Method
ASTM C -231 -B
Field Date Sit #03
Ticket Number:
660687 Time Batched: 5:00
Time Sampled: 6:20
Slump:
5 in Air Content: 5.0%
Unit Weight: n/a
Concrete Temperature:
90° F Ambient Temperature: 73° F
Yardage (c.y.): 330
Placement Location:
Paving
SLCO8090410
Sample Location:
25'N. & 5'W. From S.W. Corner of Building F
94535
" Concrete Cornpression Test Results
Set #
Cylinder
#
Test Date
Age
(days)
Max Load
(lbs. force)
03
SLCO8090409
08/1612004
7
95935
03
SLCO8090410
08123/2004
14
94535
03
SLCO8090411
09106/2004
28
118554
03
SLCO8090412
09/06/2004
28
117310
Area
Strenggth Fracture
(sq.in.)
(psl, Type
28.27
3390
28.27
3340
28.27
4190
28.27
4150
28 day average
4170
Normal cylinder size: 6" x 12"
Field and laboratory tests by TMI are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
TMI was on site as requested to verify the placement of reinforcing steel for the paving of firelanes between building B - H.
Reinforcing steel was verified for conformance with ASTM A 605 for grade, size and quality. Configuration, minimum
clearance and spacing were per the approved construction documents with no discrepancies noted. The following
representatives were notified, Tim /PCC
Terra - Mar /U.S. Labs Kevin T. Weiss
Construction Division Manager
The results presented in this report pertain only to the specific items tested. This report was produced for the exclusive use of the client. Any reproduction of
this report, or any part therein, is strictly prohibited without the express written consent of TMI.
Page 3 of
01
`* GEOTECHNICAL, ENVIRONMENTAL AND MATERIALS ENGINEERS
DALLAS FORT WORTH HOUSTON AUSTIN LONGVIEW
P ® 2400 Gravel Dr., Building 25 Fort Worth, Texas 76118 -6935 Voice: (817) 284 -9363 Fax:(817) 284 -9430
Concrete Compression Test Report
Client: Prime Construction Company Report Distribution: (1) Houghton Capital
Project: Secur -Lock Self Storage (1) Prime Construction Company
Coppell, Texas (1) City of Coppell
(1) City of Coppell
(1) AECC Inc.
TMI Report No.: FCO3- 63414 -049
Report Date: 09/07/2004
_ _ Specifications
_ _
_ Te st Data
Strength
3500 psi @ 28 Days
Placement Date
08/09/2004
Slump
3 in min 5 in max
Sampled By
Ambient Temperature: 73° F
Air Content
3 % min 6 % max
Weather
Cloudy
Concrete Temperature
n/a
Supplier /Mix
So. Star /9339
Ambient Temperature
n/a
Air Content Method
ASTM C -231 -B
'Field Data Set #4
Ticket Number:
705236
Time Batched: 8:12
Time Sampled: 8:50
Slump:
5 in
Air Content: 4.5%
Unit Weight: n/a
Concrete Temperature:
90° F
Ambient Temperature: 73° F
Yardage (c.y.): 490
Placement Location:
Paving
4
SLCO8090414
Sample Location:
20'N. & 10'E.
From The N.W. Corner of Building H
28.27
Concrete Compresslon Test Results`
Set #
Cylinder
#
Test Date
Age
(days)
Max Load
(lbs. force)
Area
(sq.in.)
Strength Fracture
(ps" Type
4
SLCO8090413
08/16/2004
7
75365
28.27
2660
4
SLCO8090414
08/23/2004
14
85940
28.27
3040
4
SLCO8090415
09/0612004
28
105247
28.27
3720
4
SLCO8090416
09/06/2004
28
102254
28.27
3620
28 day average
3670
Normal cylinder size: 6" x 12"
Field and laboratory tests by TMI are per applicable ASTM Standards: C31, C39, C138. C143, C172. C1064, and C617 or C1231.
TMI was on site as requested to verify the placement of reinforcing steel for the paving of firelanes between building B - H.
Reinforcing steel was verified for conformance with ASTM A 605 for grade, size and quality. Configuration, minimum
clearance and spacing were per the approved construction documents with no discrepancies noted. The following
representatives were notified, Tim /PCC
Terra - Mar /U.S. Labs Kevin T. Wells
Construction Division Manager
The results presented In this report pertain only to the specific Items tested. This report was produced for the exclusive use of the client. Any reproduction of
this report, or any part therein, is strictly prohibited without the express written consent of TMI.
01
Page 4 of 4
TERRA4NAR GEOTECHNICAL, ENVIRONMENTAL AND MATERIALS ENGINEERS
DALLAS FORTWORTH HOUSTON AUSTIN LONGVIEW
2400 Gravel Drive, Bldg. 25 Fort Worth, Texas 76118 phone: (817) 284 -9363 fax: (817) 284 -9430
B
=— Concrete Compression Test Report
Client: Prime Construction Company Report Distribution: (1) Houghton Capital
Project: Secur -Lock Self Storage (1) Prime Construction Company
Coppell, Texas (1) City of Coppell
(1) City of Coppell
(1) AECC Inc.
TMI Report No.: FCO3- 63414 -049
Report Date: 09/07/2004
Strength
3500 psi @ 28 Days
Slump
3 in min 5 in max
Air Content
3 % min 6 % max
Concrete Temperature n/a
Ambient Temperature n/a
Placement Date
08/09/2004
Sampled By
Keith Bowen
Weather
Cloudy
Supplier /Mix
So. Star /9339
Air Content Method
ASTM C -231 -B
Fie Id DatarSet #1 ..: 4r r a BE ,
Ticket Number:
66059 Time Batched: 2:06
Time Sampled: 2.30
Slump:
4.5 in Air Content: 4.5%
Unit Weight: n/a
Concrete Temperature:
89° F Ambient Temperature: 80° F
Yardage (c.y.): 50
Placement Location:
Paving
(lbs. force)
Sample Location: 20' S. & 10' E. From The N.E. Corner of Building C
Concrete Compression TesURes[tlfs`
Normal cylinder size: 6" x 12"
Field and laboratory tests by TMI are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or 1%
io it II
TERRA -MAR, INC. V Kevin T. Wells
Construction Division Manager
The results presented in this report pertain only to the specific items tested. This report was produced for the exclusive use of the client. Any reproduction of
this report, or any part therein, is strictly prohibited without the express written consent of TMI.
01 Page I of
Cylinder
Age
Max Load
Area
Stradgth Fracture
Set#
#
Test Date
( days)
(lbs. force)
(sq.in.)
(psi) Type
1
SLC08090401
08/16/2004
7
83974
28.27
2970
1
SLC08O90402
08/23/2004
14
103837
28.27
3670
1
SLCO8090403
09/06/2004
28
111259
28.27
3930
1
SLC08090404
09/06/2004
28
115642
28.27
4090
28 day average
4010
Normal cylinder size: 6" x 12"
Field and laboratory tests by TMI are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or 1%
io it II
TERRA -MAR, INC. V Kevin T. Wells
Construction Division Manager
The results presented in this report pertain only to the specific items tested. This report was produced for the exclusive use of the client. Any reproduction of
this report, or any part therein, is strictly prohibited without the express written consent of TMI.
01 Page I of
TERRA4YM GEOTECHNICAL, ENVIRONMENTAL AND MATERIALS ENGINEERS
DALLAS FORT WORTH HOUSTON AUSTIN LONGVIEW
2400 Gravel Drive, Bldg. 25 Fort Worth, Texas 76118 phone: (817) 284 -9363 fax:(817) 284 -9430
_ F=
Concrete Compression Test Report
Client: Prime Construction Company
Project: Secur -Lock Self Storage
Coppell, Texas
TMI Report No.
Report Date:
FCO3- 63414 -049
09/07/2004
Report Distribution: (1) Houghton Capital
(1) Prime Construction Company
(1) City of Coppell
(1) City of Coppell
(1) AECC Inc.
Strength
Slump
Air Content
Concrete Temperature
Ambient Temperature
3500 psi @ 28 Days
3 in min 5 in max
3 %min 6°/ max
n/a
n/a
Placement Date
Sampled By
Weather
Supplier /Mix
Air Content Method
08/09/2004
Keith Bowen
Cloudy
So. Star /9339
ASTM C -231 -B
Placement Location: Paving
Sample Location: 10' N. & 15' E. from The N.W. Corner of Building D
6K Concretei19 ��
bh5prgssSion TeWRtrlts : ,I'.Ry�
v.;,.. t.. ..4 OINt
Cylinder
(sq.in.)
Age
a
Field Data
ouqy
Test Date
(days)
(Ibs. force)
02
08/16/2004
7
88272
02
SLC08090406
08/23/2004
14
86830
02
SLC08090407
09/06/2004
28
101844
02
SLC08090408
09/06/2004
Ticket Number: 660676
Time Batched: 3:51
Time Sampled:
4:45
Slump: 5 in
Air Content: 4.5%
Unit Weight:
n/a
Concrete Temperature: 90° F
Ambient Temperature: 76° F
Yardage (c.y.):
200
Placement Location: Paving
Sample Location: 10' N. & 15' E. from The N.W. Corner of Building D
6K Concretei19 ��
bh5prgssSion TeWRtrlts : ,I'.Ry�
v.;,.. t.. ..4 OINt
Area
Cylinder
(sq.in.)
Age
Max Load
Set #
#
Test Date
(days)
(Ibs. force)
02
SLC08090405
08/16/2004
7
88272
02
SLC08090406
08/23/2004
14
86830
02
SLC08090407
09/06/2004
28
101844
02
SLC08090408
09/06/2004
28
104384
Area
Strength Fracture
(sq.in.)
(ps,) Type
28.27
3120
28.27
3070
28.27
3600
28.27
3690
28 day average
3650
Normal cylinder size: 6" x 12"
Field and laboratory tests by TMI are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
TERRA -MAR, INC. Kevin T. Wells
Construction Division Manager
The results presented in this report pertain only to the specific items tested. This report was produced for the exclusive use of the client. Any reproduction of
this report, or any part therein, is strictly prohibited without the express written consent of TMI.
01 Page 2 of 4
TERRAaNAR GEOTECHNICAL, ENVIRONMENTAL AND MATERIALS ENGINEERS
DALLAS FORT WORTH HOUSTON AUSTIN LONGVIEW
2400 Gravel Drive, Bldg. 25 Fort Worth, Texas 76118 phone: (817) 284 -9363 (ax. :(817) 284 -9430
_ 2>
Concrete Compression Test Report
Client: Prime Construction Company Report Distribution: (1) Houghton Capital
Project: Secur -Lock Self Storage (1) Prime Construction Company
Coppell, Texas (1) City of Coppell
(1) City of Coppell
(1) AECC Inc.
TMI Report No.: FCO3- 63414 -049
Report Date: 09/07/2004
Strength
3500 psi @ 28 Days
Placement Date
08/09/2004
Slump
3 in min 5 in max
Sampled By
Keith Bowen
Air Content
3 % min 6 % max
Weather
Cloudy
Concrete Temperature
n/a
Supplier /Mix
So. Star /9339
Ambient Temperature
n/a
Air Content Method
ASTM C -231 -B
Field Data Set #03
Ticket Number: 660687 Time Batched: 5:00 Time Sampled: 6:20
Slump: 5 in Air Content: 5.0% Unit Weight: ri
Concrete Temperature: 90 F Ambient Temperature: 73° F Yardage (c.y.): 330
Placement Location: Paving
Sample Location: 25'N. & 5'W. From S.W. Corner of Building F
Concrete Compression Test Results
Max Load
Cylinder
Strenggth Fracture
Age
Set#
#
Test Date
(days)
03
SLC08O90409
08/16/2004
7
03
SLC08O90410
08/23/2004
14
03
SLC08090411
09/06/2004
28
03
SLC08090412
09/06/2004
28
Max Load
Area
Strenggth Fracture
(lbs. force)
(sq.in.)
(psl' Type
95935
28.27
3390
94535
28.27
3340
118554
28.27
4190
117310
28.27
4150
28 day average
4170
Normal cylinder size: 6" x 12"
Field and laboratory tests by TMI are per applicable ASTM Standards: C31, C39, C138, C143, C172, C1064, and C617 or C1231.
TERRA -MAR, INC. Kevin T. Wells
Construction Division Manager
The results presented in this report pertain only to the specific items tested. This report was produced for the exclusive use of the client. Any reproduction of
this report, or any part therein, is strictly prohibited without the express written consent of TMI.
01 Page 3 of 4
TERRilli GEOTECHNICAL, ENVIRONMENTAL AND MATERIALS ENGINEERS
DALLAS FORT WORTH HOUSTON AUSTIN LONGVIEW
2400 Gravel Drive, Bldg. 25 Fort Worth, Texas 76118 phone: (817) 284 -9363 fax. :(817) 284 -9430
Concrete Compression Test Report
Client: Prime Construction Company
Project: Secur -Lock Self Storage
Coppell, Texas
TMI Report No.
Report Date:
FCO3- 63414 -049
09/07/2004
Report Distribution: (1) Houghton Capital
(1) Prime Construction Company
(1) City of Coppell
(1) City of Coppell
(1) AECC Inc.
Strength
Slump
Air Content
Concrete Temperature
3500 psi @ 28 Days
3 in min 5 in max
Placement Date
08/09/2004
Sampled By
Keith Bowen
Weather
Cloudy
Supplier /Mix
So. Star /9339
Air Content Method
ASTM C -231 -B
3 % min 6 % max
n/a
Ambient Temperature n/a
? _ Field Data'Set #4
Ticket Number:
705236 Time Batched: 8:12
Time Sampled: 8:50
Slump:
5 in Air Content: 4.5%
Unit Weight: n/a
Concrete Temperature:
90 F Ambient Temperature: 73° F
Yardage (c.y.): 490
Placement Location:
Paving
SLC08090413
Sample Location: 20'N. & 10' E. From The N.W. Corner of Building H
Concrete` aIn ressibn.Test Results
r
Area
Cylinder
(sq.in.)
Age
Max Load
Set #
#
Test Date
(days)
(lbs. force)
4
SLC08090413
08/16/2004
7
75365
4
SLC08090414
08/23/2004
14
85940
4
SLC08090415
09/06/2004
28
105247
4
SLC08090416
09/06/2004
28
102254
Area
Strength Fracture
(sq.in.)
(psi) Type
28.27
2660
28.27
3040
28.27
3720
28.27
3620
28 day average
3670
Normal cylinder size: 6" x 12"
Field and laboratory tests by TMI are per applicable ASTM Standards: C31, C39. C138, C143, C172, C1064, and C617 or C1231.
d�
TERRA -MAR, INC. Kevin T. Wells
Construction Division Manager
The results presented in this report pertain only to the specific items tested. This report was produced for the exclusive use of the client. Any reproduction of
this report, or any part therein, is strictly prohibited without the express written consent of TMI.
01 Page 4 of 4