Loading...
St Andrews Est-LR040922ALPHA TESTING, INC. 2209 Wisconsin St., Suite 100 Dallas, Texas 75229 972/620-8911 - 972/263-4937 (Metro) FAX: 972/406-8023 TESTED FOR: ST. ANDREWS LAND COMPANY CARROLLTON, TEXAS REPORT OF FIELD COMPACTION TESTS DATE: 09/22/04 PROJECT: ST. ANDREWS ESTATES COPPELL, TEXAS OUR REPORT NO.: 04219-36 TEST DATA: TEST ~ ELEV SOIL ID OPTIMUM t,&AXlMUM LAS IN PLACE IN PLACE PERCENT NO. DATEDE PTH""~...h NUMBER MOISTURE DRY DENSITY MOISTURE DRY DENSITY COMPACTION COMMENT* % PCF % PCF 602 09/22/04 FG-3.0 3 24.0 95.5 24,9 98 102 1-A 603 09/22/04 FG-2.5 3 24.0 95.5 24.1 98 103 1-A 604 09/22/04 FG-2.0 3 24.0 95.5 24.0 98 103 1-A 605 09/22/04 FG-1.5 3 24.0 95.5 25.5 97 102 1-A 606 09/22/04 FG-1.0 3 24.0 95.5 25.0 99 103 1-A 607 09/22/04 FG-0.5 3 24.0 95.5 24.2 98 102 I-A 608 09/22/04 FG 3 24.0 95.5 24.4 98 102 I-A TEST LOCATION: UTILITIES 602 WATER SERVICE TO BLOCK A, PAD 1 603 WATER SERVICE TO BLOCK A, PAD 1 604 WATER SERVICE TO BLOCK A, PAD 1 605 WATER SERVICE TO BLOCK A, PAD 1 606 WATER SERVICE TO BLOCK A, PAD 1 607 WATER SERVICE TO BLOCK A, PAD 1 608 WATER SERVICE TO BLOCK A, PAD 1 CC: HENNESSEY ENGINEERING; CITY OF COPPELL 1 FILL ' A IN PLACE PERCENT MOISTURE AND PERCENT COMPACTION COMPLY WITH SPECIFICATIONS 2 NATURAL SUBGRADE B PERCENT COMPACTION DOES NOT COMPLY WITH SPECIFICATIONS Respecffu~y ~bm~ed 3 LIME STABILIZED C. PERCENT IN PLACE MOISTURE DOES NOT COMPLY WITH SPECIFICATIONS 4 CEMENTTE~TED D RETEST ROY~ELEZ ALPHA TESTIN~NC Our test results and repo~s aCe for the excluswe use of the Client (and their designated recipients on file in our ~) and shall ~ot be reproduced and/or distributed except with express approval ALPHA The use of our name a~d test results must receive our written approval Test results and repods apply only to the samples Jested and/or obsewed and are ~ot indi~t~ve of the qualities of apparently ~denti~l or similar specimens Oeotechnical Engineering /, Construction Materials Testing /. Environmental Engineering /;~' Consulting ALPHA TESTING, INC. 2209 Wisconsin St., Suite 100 Dallas, Texas 75229 972/620-8911 - 972/263-4937 (Metro) FAX: 972/406-8023 TESTED FOR: ST. ANDREWS LAND COMPANY CARROLLTON, TEXAS REPORT OF FIELD COMPACTION TESTS DATE: 09~22~04 PROJECT: ST. ANDREWS ESTATES COPPELL, TEXAS OUR REPORT NO.: 04219-36A TEST DATA: TEST ~ ELEV. SOIL ID OPTIMUM MAXIMUM LAB IN PLACE IN PLACE PERCENT NO. DATEDEPTH~ NUMBER MOISTURE DRY DENSITY MOISTURE DRY DENStTY COMPACTION COMMENT* % PCF % PCF 609 09/22/04 FG-3.0 3 24.0 95.5 25.1 98 102 1-A 610 09~22~04 FG-2.5 3 24.0 95.5 25.4 97 101 I-A 611 09~22~04 FG-2.0 3 24.0 95.5 24.6 98 103 I-A 612 09~22~04 FG-1.5 3 24.0 95.5 24.0 99 103 I-A 613 09~22~04 FG-1.0 3 24.0 95.5 24.0 96 100 I-A 614 09/22/04 FG-0.5 3 24.0 95.5 24.5 96 101 I-A 615 09/22/04 FG 3 24.0 95.5 24.8 95 99 I-A TEST LOCATION: UTILITIES 609 WATER SERVICE TO BLOCK A, PAD 2 610 WATER SERVICE TO BLOCK A, PAD 2 611 WATER SERVICE TO BLOCK A, PAD 2 612 WATER SERVICE TO BLOCK A, PAD 2 613 WATER SERVICE TO BLOCK A, PAD 2 614 WATER SERVICE TO BLOCK A, PAD 2 615 WATER SERVICE TO BLOCK A, PAD 2 CC: HENNESSEY ENGINEERING; CITY OF COPPELL 1 FILL * A IN PLACE PERCENT MOISTURE AND PERCENT COMPACTION COMPLY WITH SPECIFICATIONS 2 NATURAL SUBGRADE B PERCENT COMPACTION DOES NOT COMPLY WITH SPECIFICATIONS Respect[ II Submitted 4 CEMENTTREATED D. RETEST Our test results and reports are for the exclusive use of the Client (and their designated reopients on file in our office) and shall no[ be reproduced and/or distributed except wilh express approval of ALPHA The use of our name and test results must receive our written approval Test results arid reports apply only to the samples tested and/or observed and are not indicative of the qualities of apparently identiCal or similar spec,mens