Attached is a copy of the response to RFI No. 6 sent to S.J. Louis. Please feel free to
call me at 972-735-3056 if you have any questions.
Thanks,
Erika Cooper
An AECOM Company
2884 8?:22 FR TURNER COLLIE& BRADENg?2 ?35 3002 TO 997230435?0 P.02/05
DeForest and Sandy Lake Wastewater Lift Stations and Force Main Improvements
Force Main Line A&B RFI No. 6
Response Date:August t0, 2004
TCB Project no, 052.131124 0001.04000.A103
'I'CB has reviewed and has ~o exceptions to eliminating the 22.5 degree bends at the
following locations indicated in the RFI:
Sm2+58,09
o Sta2+69.91
Sta5+05.71
· Sta 5+30.52
Elimination of these bends will require that the Contractor deflect the pipe .joints in order to
hit the required elevations at the bores. Deflection of joints must not exceed the pipe
manufacturer's recommended maximum joint deflection.
In addition, TCB has reviewed and has no exccptions to installing two 22.5 degree l~ends in
lieu of a 45 degree bend at Station 6+37.12.
If you have any fft.rther questions, please feel free to contact Erika Cooper at 972-735-3056,
CC;
Rick O'Dell, prOject Inspector - City of Coppell
George Cisneros - TCB
G'reg Hooten - ?CB
AIIG 10 2084 8?:25 FR TURNER COLLIE~ BRADENg?2 73S 5082 TO 999250455?0 P.85/05
Request For Information (RFI)
Deforest Rd, Lift S~ation Improvemea~s - Force Main
E~ka Cooper,
17300 D~i~ ~., S~te 1010
D~I~, Tex~ 752~8
F~: (972~.735-~001.. (~ page ~ot~)
8/9/04
Adam Lunsford
Project Coordinator
This R.F.I. is regards to the 30" force man on the above referenced projeot. We have had an incorrect number
of 30" ductile iron bends delivered to the project. Per abe plans, we are shor~ one (1) 225 degree bend and one
(1) 45 degree bead. A total of seven (7) 22.5 degree beads were ordered. Due tn the availability of the bends,
we are proposing to defle~ the pipe joints from stations 1-20 thru 2*73 and stations 3+09.81 thru 5+36 in order
to hit thc required elevations at the bores. If this is acceptable, the 22.5 degree bends at Stations 2+58.09,
2~69.91, 5+05.71, & 5+30.$2 would be deleted, Given this, we would install four (4) of the bends at Stations
2+94, 3+09, 6+09, & 6+39 and would hastall two (2) at Station 6+37.12 in heu ora 45 degree b~ad. We have
ddscussed this alternative with the City in the field, and have received their approval if acceptable to the
Engineer. If this is acceptable, please let us know as soon a~ possible. Please call me at the offiec once you
have reviewed this.
Please con£u-m that our plan is acceptable by responding tn this R.,F.I. as soon as possible. Your help is ~reatly
appreciated.
Les V. Whitman, S.J. Louis Construction of Texas Ltd., LIP