Freeport NIP(8.0)-LR041102Ro gineers 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630-9745 CONCRETE COMPRESSIVE STRENGTH TEST Client: Duke Realty Services, LP Mr. Brian S~'aley 5495 Belt Line Rd., Ste 360 Dallas TX 75254 Report No.: 219869 Project No.: 049245 Date of Service: 10/01/2004 Report Date: 11/02/2004 Project: Freeport XI & XII Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples end bring samples back to the laboratory for curing and testing in accordance with applicable standards. STRENGTH: SLUMP (in): AIR (%): TEST METHOD: 2ONTRACTOR: Duke Construction CONCRETE SUPPLIER: Southern Star PLANT: 27 SPECIFICATION REQUIREMENTS 4000 psi ~ 28 Days 6" maximum NA ASTM C-172 ASTM C~31 ASTM C-143 ASTM C-231 ASTM C- 1064 ASTM C-1231 ASTM C-39 PROJECT DATA MIX DESIGN I.D.: 9349 P~CEM~NT DATE: 10/01/2004 WEATHER CONDITIONS: Cloudy TIME SAMPLED: 6:30am BATCH TIME: 5:54am TEMPERATURE (F) - AIR 69 F CONCRETE: 8 ] F THUCK NO: 1827 TIClCET NO: 701123 Am coNTrwr (%): NA tn~rr WEIGHT (pc0: NA OVERALL pLACEMENT LOCATION: Slab on grade 1-8 and A-D MEASURED SLUMP (inches) 5.0 SAMI~LE LOCATION: REPORT OF TESTS ' ' " 12" Concrete Compressive Cylinder 6 x 7.8~A.2 CYLINDER MAXIMUM COMPRESSIVE MARIO~D DATE AGE DIAMETER AREA LOAD STRENGTH SET NO. TESTED (days) (inches) (sq.in.) (lbs. force} (psi) 1 1 10/08/2004 7 6.00 28.26 136530 4830 1 2 10/29/2004 28 6.00 28.26 177370 6270 1 3 10/29/2004 28 6.00 28.26 167920 5940 Average 6110 I 4 Hold Water added at site: 5 gallons FRACTURE TYPE Unbonded Cap Unbonded Cap Unbonded Cap LIM/TATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the wri~en approval of Rone Engineers, Ltd. 01SS Page 1 of 7 Client: ineers Duke Realty Services, LP Mr. Brian Sl~aley 5495 Belt Line Rd., Stp 360 Dallas TX 75254 Project: Freeport XI & XII Coppell, Texas 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, StP. 150, Houston, TX 77040 Corporate Phone: (214) 630-9745 CONCRETE COMPRESSIVE STRENGTH TEST Report No.: 219869 Project No.: 049245 Date of Service: 10/01/2004 Report Date: 11/02/2004 Obtain samples of fi'esh concrete at the placement locations, perform required field testing, cast compressive stxength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA STRENGTH: SLUMP (in): AIR (%): TEST METHOD: CONTRACTOR: Duke Construction CONCRETE SUPPLIER: Southern Star PLANT: 27 SPECIFICATION REQUIREMENTS 4000 psi ~ 28 Days 6" maximum NA ASTM C- 172 ASTM C-31 ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-1231 ASTM C-39 MIX DESIGN LD.: 9349 PLACEMENT DATE: 10/01/2004 WEATHER CONDITIONS: Cloudy TIME SAMPLED: 7:30am BATCHTIME: 6:50a~1 TEMPERATURE (F) - AIR 69 F CONCRETE: 83 F TRUCK NO: 8 TICKET No: 701136 Am CONTENT (%): NA u~rr WEIGHT (peO: NA OVERALL PLACEMENT LOCATION: Slab on grade 1-8 and A-D SAMPLE LOCATION: REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" 7.1 at C.6 MEASURED SLUMP 0aches) 6.0 CYLINDER MAXIMUM COMPRESSIVE MARKED DATE AGE DIAMETER AREA LOAD STRENGTH FRACTURE SET NO. TESTED (days) (inches) (sq.in.) Obs. force) (psi) TYPE 2 1 10/08/2004 7 6.00 28.26 121170 4290 Unbonded Cap 2 2 10/29/2004 28 6.00 28.26 143660 5080 Unbonded Cap 2 3 10/29/2004 28 6.00 28.26 150170 5310 Unbonded Cap Average 5200 2 4 Hold Water added at site: 5 gallons LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other fi~ature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in flail without the written approval of Rone Engineers, Ltd. 0ISS Page 2 of 7 Client: ineers Duke Realty Services, LP Mr. Brian SB'aley 5495 Belt Line Rd., Ste 360 Dallas TX 75254 Project: Freeport XI & XII Coppell, Texas 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630-9745 CONCRETE COMPRESSIVE STRENGTH TEST Services: Report No.: 219869 Project No.: 049245 Date of Service: 10/01/2004 Report Date: 11/02/2004 Obtain samples of fi'esh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA STRENGTH: SLUMP (in): AIR (%): TEST METHOD: CONTRACTOR: Duke Construction CONCRETE SUPPLIER: SouthelTl Star PLANT: 27 SPECIFICATION REQUIREMENTS 4000 psi ~ 28 Days 6" maximum NA ASTM C- 172 ASTM C-31 ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-1231 ASTM C-39 MIX DESIGN I.D.: 9349 PLACEMENT DATE: 10/01/2004 WEATHER CONDITIONS: Cloudy TIME SAMPLED: 8;15am BATCHTIME: 7:45am TEMPERATURE (F) - AIR 69 F CONCRETE: 86 F mvcK NO: 1827 TICr~T NO: 701146 AIR CONTENT (%): NA in, aT WEIGHT (pcf): NA OVERALL PLACEMENT LOCATION: Slab on grade I-8 a~d A-D SAMPLE LOCATION: REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" 6.7mB.3 MEASURED SLUMP (inches) 5.5 CYLINDER MAXIMUM COMPRESSIVE MARKED DATE AGE DIAMETER AREA LOAD STRENGTH FRACTURE SET NO. TESTED (days) (inches) (sq.in.) 0b~ force) (psi) TYPE 3 1 10/08/2004 7 6.00 28.26 139280 4930 Unbonded Cap 3 2 10/29/2004 28 6.00 28.26 169480 5990 Unbonded Cap 3 3 10/29/2004 28 6.00 28.26 179720 6360 Unbonded Cap Average 6180 3 4 Hold Water added at site: 15 gallons LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in qualit~ (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by pm'sons or conditions over w~tich we have no control. O~r letters and repoas are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written appwval of Rone Engineers, Ltd. 01SS Page 3 of 7 ineers 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630~9745 CONCRETE COMPRESSIVE STRENGTH TEST Client: Duke Realty Services, LP Mr. Brian Straley 5495 Belt Line Rd., Ste 360 Dallas TX 75254 Project: Freeport XI & XlI Coppell, Texas Report No.: 219869 Project No.: 049245 Date of Service: 10/01/2004 Report Date: 11/02/2004 Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA STRENGTH: SLUMP (in): AlP. (%): TEST METHOD: CONTRACTOR: Duke Construction CONCRETE SUPPLIER: SoutheFll Star PLA~r: 27 SPECIFICATION REQUIREMENTS 4000 psi @ 28 Days 6" maximum NA ASTM C-172 ASTM C-31 ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-1231 ASTM C-39 MIX DESIGN I.D.: 9349 PLACEMENT DATE: 10/01/2004 WEATHER CoN~mONS: Cloudy TIME SAMPLED: 9:00am BATCHTIME: 8:35am TEMPERATURE (F} - AIR 71 V CONCRETE: 85 V TRUCKNO: 0 TICKETNO: 701156 AIR CONTENT (%): NA vNrr WEIGHT (pc0: NA OVERALL PLACEMENT LOCATION: Slab on grade 1-8 and A-D SAMPLE LOCATION: REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" 5.9 at A.8 MEASURED SLUMP (inches) 6.0 CYLINDER MAXIMUM COMPRESSIVE MARKED DATE AGE DIAMETER AREA LOAD STRENGTH FRACTURE SET NO. TESTED (days) (inches) (sq.in.) (lbs. force) (psi) TYPE 4 1 10/08/2004 7 6.00 28.26 123270 4360 Unbonded Cap 4 2 10/29/2004 28 6.00 28.26 147510 5220 Unbonded Cap 4 3 10/29/2004 28 6.00 28.26 149900 5300 Unbonded Cap Average 5260 4 4 Hold Water added at site: 15 gallons LIMITATIONS: The test results presented herein were prepared bosed upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject mattar provided by persons or conditions over which we have no contxol. Our letters and reports are for the exclusive use of the clients to whom they are addressed ond shall not be reproduced except in full without the w~tten approval of Rone Engineers, Ltxl. 0ISS Page 4 of 7 ineers 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630-9745 CONCRETE COMPRESSIVE STRENGTH TEST Client: Duke Realty Services, LP Mr. Brian Straley 5495 Belt Line Rd., Ste 360 Dallas TX 75254 Project: Freeport XI & XII Coppell, Texas Report No.: 219869 Project No.: 049245 Date of Service: 10/01/2004 Report Date: 11/02/2004 Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA STRENGTH: SLUMP (in): AIR (%): TEST METHOD: CONTRACTOR: Duke Construction CONCRETE SUPPLIER: Southern Star PLANT: 27 SPECIFICATION REQWREMENTS 4000 psi ~ 28 Days 6" maximum NA ASTM C-172 ASTM C-31 ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C- ! 231 ASTM C-39 MIX DESIGN LO.: 9349 pLACEMENT DATE: 10/01/2004 WEA IHI~R CONDITIONS: Cloudy TIMESAMYLED: 10:30am BATCHTIME: 9:45am TEMPERATURE (F) - AIR 71 F CONCRETE: 85 F TRUCK NO: 0 TICKET NO: 701 170 AIR CONTENT (%): NA U~qT WEIGHT (pc0: NA OVERALL PLACEMENT LOCATION: Slab on grade 1-8 and A-D SAMPLE LOCATION: REPORT OF TESTS Concrete Compressivc Cylinder 6" x 12" 4.6atC.2 MEASURED SLUMP (inches) 6.0 CYLINDER MAXIMUM COMPRESSIVE MARKED DATE AGE DIAMETER AREA LOAD STRENGTH FRACTURE SET NO. TESTED (days) (inches) (sq.in.) (~bs. force) (psi) TYPE 5 1 10/08/2004 7 6.00 28.26 112340 3970 Unbonded Cap 5 2 10/29/2004 28 6.00 28.26 144070 5090 Unbonded Cap 5 3 10/29/2004 28 6.00 28.26 152400 5390 Unbonded Cap Average 5240 5 4 Hold Water added at site: 5 gallons LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in qaality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our let~rs and reporls are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd. 01SS Page $ of 7 Client: ineers Duke Realty Services, LP Mr. Brian Straley 5495 Belt Line Rd., Ste 360 Dallas TX 75254 Project: Freeport XI & XII Coppell, Texas 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630-9745 CONCRETE COMPRESSIVE STRENGTH TEST Report No.: 219869 Project No.: 049245 Date of Service: 10/01/2004 Report Date: 11/02/2004 Services: Obtain samples of ~'esh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA STRENGTH: SLUMP (in): AIR (%): TEST METHOD: CONTRACTOR: Duke Construction CONCRETE SUPPLIER: SouthelTl Star PLANT: 27 SPECIFICATION REQUIREMENTS 4000 psi ~ 28 Days 6" maximum NA ASTM C-172 ASTM C-31 ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-1231 ASTM C-39 MIX DESIGN I.D.: 9349 PLACEMENT DATE: 10/01/2004 WEATHER CONDITIONS: Cloudy TIME SAMPLED: ll:30am BATCHTIME: ll:07am TEMPERATURE (F) - AIR 70 F CONCRETE: 84 v TRUCKNO: 773 TICKET NO: 701181 AIR CONTENT (%): NA UNIT WEIGHT (pe0: NA OVERALL PlaCEMENT LOCATION: Slab on grade 1-8 and A-D SAMPLE LOCATION: REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" 3.9 at AA MEASURED SLUMP (inches) 6.0 CYLINDER MAXIMUM COMPRESSIVE MARKED DATE AGE DIAMETER AREA LOAD STRENGTH FRACTURE SET NO. TESTED (days) (inches) (sq.in.) (lbs. force) (psi) TYPE 6 1 10/08/2004 7 6.00 28.26 102050 3610 Unbonded Cap 6 2 10/29/2004 28 6.00 28.26 148300 5240 Unbonded Cap 6 3 10/29/2004 28 6.00 28.26 144020 5090 Unbonded Cap Average 5170 6 4 Hold Water added at site: 10 gallons LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports a~ for the exclusive use of~he clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd. 01SS Page 6 of 7 CLient: ineers Duke Realty Services, LP Mr. Brian Straley 5495 Belt Line Rd., Ste 360 Dallas TX 75254 Project: Freeport XI & XII Coppell, Texas 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630-9745 CONCRETE COMPRESSIVE STRENGTH TEST Services: Report No.: 219869 Project No.: 049245 Date of Service: 10/01/2004 Report Date: 11/02/2004 Obtain samples of fi'esh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA STRENGTH: SLUMP (in): AIR (%): TEST METHOD: CONTRACTOR: Duke Construction CONCRETE SUPPLIER: SoutherI1 Star PLANT: 27 SPECIFICATION REQUIREMENTS 4000 psi ~ 28 Days 6" maximum NA ASTM C-172 ASTM C-31 ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-1231 ASTIvl C-39 MIX DESIGN I.D.: 9349 rrACEMENT ANTE: 10/01/2004 WEATHER CoN~moNs: Cloudy TIME SAMPLED: 12:45pm BATCHTIME: 12:09pm TEMPERATURE (F)-AIR 71 F CONCRETE: 85 V TRUCK NO: 0 TICKET SO: 701 1 93 AIR CONTE~Vr (%): NA UNIT WEIGHT (pc0: NA OVERALL PLACEMENT LOCATION: Slab on grade 1-8 and A-D SAMPLE LOCATION: REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" l.SmB.7 MEASURED SLUMr (inches) 6.0 CYLINDER MARKED DATE AGE SET NO. TESTED (days) (inches) MAXIMUM COMPRESSIVE AREA LOAD STRENGTH FRACTURE (sq.in.) (lbs. force) (psi) TYPE 7 1 10/08/2004 7 6.00 28.26 105800 3740 Unbonded Cap 7 2 10/29/2004 28 7 3 10/29/2004 28 6.00 6.00 28.26 139330 4930 Unbonded Cap 28.26 141690 5010 Unbonded Cap Average 4970 7 4 Hold Water added at site: Technician: Scott Mitchell Report Distribution: (1) Duke Realty Services, LP ( 1 ) Extranet (1) City of Coppell (1) City of Coppell 10 gallons Started: 5:15am Finished: 2:00pm K. Scott Watson, AET CMT Operations Manager LIMITATIONS: The test results presented herein were prepared based upon the specific smnples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance ete,) or any other feature of similar subject matter provided by persons or conditions over which we have no control. O~r letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except m fuI w thout the written approval of Rone Engineers, Ltd. 01SS Page 7 of 7