CONCRETE COMPRESSIVE STRENGTH TEST
Duke Realty Services, LP
Mr. Brian Straley
5495 Belt Line Rd., Ste 360
Dallas TX 75254
Freeport XI & XII
Coppell, Texas
Report No.: 221699
Project No.: 049245
Date of Service: 10/28/2004
Report Date: 11/09/2004
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
STRENGTH:
SLUMP(in):
AIR(%):
TEST METHOD:
CONTRACTOR: Duke Construction
CONCRETE SUPPLIER: 8outherll Star
PLANT: 27
SPECIFICATION REQUIREMENTS
5000 psi ~ 28 Days
5" maximum
NA
ASTM C- 172
ASTM C-31
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-1231
ASTM C-39
MIX DESIGN I.D.: 9385
PLACEMENT DATE: 10/28/2004
WEATHER CONDITIONS: Cloudy
TIME SAMPLED: 6:30am BATCHT1ME: 6:10am
TEMPERATURE (F)- AIR 73 F CONCRETE: 86 F
TaUCR NO: 823 TICKET NO: 656660
AIR CONTENT (%): NA UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
Panels Freeport Nd, 24 - 26, 31 - 33, 55, 57 - 62, screen wail 1 and 2
SAMPLE LOCATION: P-26
REPORT OF TESTS
MEASURED
SLUMP
(inches)
4.0
Concrete Compressive Cylinder 6" x 12"
C~%ENDER MAXIMUM COMPRESSIVE
STRE FRACTURE
MARKED DATE AGE DIAMETER AREA LOAD FRE~I~
SET NO. TESTED (days) (inches) (sq.in.) (lbs. force) ~si) TYPE
1 1 ! 1/04/2004 7 6.00 28.26 144920 : 5120 Unbonded Cap
! 2 11/25/2004 28 0.00 0.00 ~ Unbonded Cap
1 3 11/25/2004 28 0.00 0.~ Unbonded Cap
1 4 Hold
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our leiters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
~ISS Page 1 of 3
ineers
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: {214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Client:
Duke Realty Services, LP
Mr. Brian Straley
5495 Belt Line Rd., Ste 360
Dallas TX 75254
Project: Freeport XI & XII
Coppell, Texas
Services:
Report No.: 221699
Project No.: 049245
Date of Service: 10/28/2004
Report Date: 11/09/2004
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
MEASURED
STRENGTH:
SLUMP (in):
AIR (%):
TEST METHOD:
CONTRACTOR: Duke Construction
CONCRETE SUPPLIER: Southern Star
PLANT: 27
SPECIFICAI1ON REQUIREMENTS
5000 psi ~ 28 Days
5" maximum
NA
ASTM C-172
ASTM C-31
ASTM C- 143
ASTM C-231
ASTM C-1064
ASTM C-1231
ASTM C-39
M~X DESIGN I.O.: 9385
PLACEMENT DATE: 10/28/2004
WEATHER CONDITIONS: Partly cloudy
TIME SAMPLED: 8:15am BATCH TIME: 7:30am
TEMPERATURE (F) - AIR 73 F CONCRETE: 88 F
TRUC~: NO: 1827 TICKET NO: 656671
ALR CONTENT (%): NA UNITWEIGHT(pcf): NA
OVERALL PLACEMENT LOCATION:
Panels Freeport XI, 24 - 26, 31 - 33, 55, 57 - 62, screen wall 1 and 2
SAMPLE LOCATION: P-57
REPORT OF TESTS
SLUMP
(inches)
4.5
Concrete Compressive C> l nder 12"
CYLINDER MAXIMUM COMPRESSIVE
MARKED DATE AGE DIAMETER AREA LOAD STRENGTH
SET NO. TESTED (days) (inches) (sq.in.) (lbs. force) (psi)
FRACTURE
TYPE
2 1 11/01/2004 4 6.00 28.26 135150 4780
2 2 11/04/2004 7 6.00 28.26 14523O 5140
2 3 11/25/2004 28 0.00 0.00
2 4 11/25/2004 28 0.00 0.00
2 5 Hold
Water added at site: 5 gallons
Unbonded Cap
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMZTATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our leiters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the writien approval of Rone Engineers, Ltd
Pace 2 of 3
Ro gineers
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worlh, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Client:
Duke Realty Services, LP
Mr. Brian Straley
5495 Belt Line Rd., Ste 360
Dallas TX 75254
Project: Freeport XI & XII
Coppell, Texas
Report No.: 221699
Project No.: 049245
Date of Service: 10/28/2004
Report Date: 11/09/2004
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
MEASURED
S]~ENGTH:
SLUMP (in):
AIR (%):
TEST METHOD:
CONTRACTOR: Duke Construction
CONCRETE SUPPLIER: Southeri1 Star
PLANT: 27
SPECIFICATION REQUIREMENTS
5000 psi ~ 28 Days
5" maximum
NA
ASTM C-172
ASTM C-31
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-1231
ASTM C-39
MIX DESIGN I.D.: 9385
PLACEMENT DATE: 10/28/2004
WEATHER CONDITIONS: Partly cloudy
TIME SAMPLED: I0:30am BATCH TIME: NA
TEMPERATURE (F)-A1R 73 F CONCRETE: 88 F
TRUCK NO: 823 TICKET NO: 656682
A1R CONTENT (%): NA UNITWEIGHT(pcf): NA
OVERALL PLACEMENT LOCATION:
Panels Freeport Xl, 24 - 26, 31 - 33, 55, 57 - 62, screen wall 1 and 2
SAMPLE LOCATION: Screen wall 2
REPORT OF TESTS
SLUMP
(inches)
5.0
Concrete Compressive Cylinder 6" x 12"
CYLINDER
MARKED DATE AGE
SET NO. TESTED (days)
MAXIMUM COMPRESSIVE
DIAMETER AREA LOAD STRENGTH FRACTURE
(inches) (sq.in.) (lbs. force) (psi) I~rPE
3 1 11/01/2004 4
3 2 11/04/2004 7
3 3 11/25/2004 28
3 4 11/25/2004 28
3 5 Hold
Water added at site: 5 gallons
6.00 28.26 111870 3960 Unbonded Cap
6.00 28.26 132520 4690 Unbonded Cap
0.00 0.00 Unbonded Cap
0.00 0.00 Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc) or any other feature of similar subject maiter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01SS Page 3 of 3
ineers
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Client:
Duke Realty Services, LP
Mr. Brian Straley
5495 Belt Line Rd., Ste 360
Dallas TX 75254
Project: Freeport XI & XII
Coppell, Texas
Services:
Report No.: 221970
Project No.: 049245
Date of Service: 10/30/2004
Report Date: 11/09/2004
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
MEASURED
STRENGTH:
SLUMP (in):
AIR (%):
TEST METHOD:
CONTRACTOR: Duke Construction
CONCRETE SUPPLIER: Southern Star
PLANT: 27
SPECIFICATION REQUIREMENTS
4000 psi @ 28 Days
5" maximum
3% - 5%
ASTM C- 172
ASTM C-31
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-1231
ASTM C-39
except 9 I 2
MIX DESIGN I.D.: 7723
PLACEME~rr DATE: 10/30/2004
WEATHER CONDITIONS: S Illlrly
TINIESAMPLED: l:15pm BATCHTIME: 12:35pm
TEMPERATURE (F)- AIR 60 F CONCRETE: 86 F
TRUCK NO: 923 TICKET NO: 756282
AIRCONTENT(%): 6.1 UNITWEIGHT(pc~: NA
OVERALL PLACEMENT LOCATION:
Entry drive
SAMPLE LOCATION: Same as above
REPORT OF TESTS
SLUMP
(inches)
5.00
Concrete Compress ve Cyl nder 6 x !
CYLINDER
MARKED DATE AGE
SET NO. TESTED (days)
MAXIMUM COMPRESSIVE
DIAMETER AREA LOAD STRENGTH FRACTURE
(inches) (sq.in.) (lbs. force) (psi) TYPE
1 1 11/06/2004 7 6.00
1 2 11/27/2004 28 0.00
1 3 11/27/2004 28 0.00
1 4 Hold
See Report #221910 for technician time.
Technician: Scott Mitchell
Report Distribution:
(1) Duke Realty Services. LP
( 1 ) Extranet
(1) City of Coppell
(1) City of Coppell
28.26 107820 3810 Unbonded Cap
0.00 Unbonded Cap
0.00 Unbonded Cap
Started: Finished:
CMT Operations Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples pr°vialed f°r testing We assume no responsibility for variation in quality
(composition, appearance, performance, et¢ ) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to v~hom they are addressed and shall not be reproduced except in full without the wrirmn approval of Rone Engineers, Ltd.
O1SS Page 1 ofl
ineers
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Client:
Project:
Services:
Duke Realty Services, LP
Mr. Brian Straley
5495 Belt Line Rd., Ste 360
Dallas TX 75254
Freeport XI & XII ~
Coppell, Texas
Report No.: 221911
Project No.: 049245
Date of Service: 10/30/2004
Report Date: 11/09/2004
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to tbe laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
MEASURED
CONTRACTOR: Duke Construction
CONCRETE SL~'PLIER: Southern Star
PLANT: 27
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi ~ 28 Days
SLUMP (in): 5" maximum
Am(%): 3% - 5%
TEST METHOD: ASTM C-172
ASTM C-31 .... p~2
ASTM C-143
ASTM C-231
ASTM C- 1064
ASTM C-1231
ASTM C-39
MIX DESIGN I.D.: 7752 SLUMP
PLACEMENT DATE: 10/30/2004 (inches)
WEAmER CONmTIONS: Partly cloudy 4.25
TIME SAMPLED: 7:45am BATCHTIME: 7:10am
TEMPERATURE {F) - AIR 60 F CONCRETE: 78 F
TRUCK NO: 1815 TICKET NO: 756237
Am CONTENT (%): 4.2 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
Paving, west property line to Freeport Parkway, 65' x 680', reference point fire hydrant on
west property line. Paving 90' northeast of hydrant
SAMPLE LOCATION:
REPORT OF TESTS
· ' 6' x 12"
Concrete Compressive Cyl nder
75' south at 670' east
CYLINDER 1VLs~XIMUM COMPRESSIVE
MARKED DATE AGE DIAMETER AREA LOAD STRENGTH FRACTURE
SET NO. TESTED (days) (inches) (sq.in.) (lbs. force) (psi) TYPE
1 I 11/06/2004 7 6.00 28.26 103070 3640 Unbonded Cap
1 2 11/27/2004 28 0.00 0.00 Unbonded Cap
1 3 11/27/2004 28 0.00 0.00 Unbonded Cap
1 4 Hold
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc) or any other feature of similar subject mailer provided by persons or conditions over which we have no control. Our leaers and
repons are for the exclusive use of the clients to whom they are addressed mad shall not be reproduced except in full without the wriaen approval of Rone Engineers, Ltd
01SS Page 1 of 6
Client:
ineers
Duke Really Services, LP
Mr. Brian Straley
5495 Belt Line Rd., Ste 360
Dallas TX 75254
Project: Freeport XI & XII
Coppell, Texas
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.: 221911
Project No.: 049245
Date of Service: 10/30/2004
Report Date: 11/09/2004
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
MEASURED
STRENGTH:
SLUMP (in):
AIR (%):
TEST METHOD:
CONTRACTOR: Duke Construction
CONCRETE SUPPLIER: Southerll Star
PLANT: 27
SPECIFICATION REQUIREME~rs
4000 psi ~ 28 Days
5" maximum
3% - 5%
ASTM C- 172
ASTM C-31
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-1231
ASTM C-39
MIX DESIGN I.D.: 7752 SLUMP
PLACEMENT DATE: 10/30/2004 (inches)
WEATHER CONDITIONS: Partly cloudy 4.00
TIME SAMPLED: 8:30am BATCHTIME: 8:13am
TEMPERATURE ITl - AIR 61 F CONCRETE: 80 F
TRUCK NO: 93 1 TICKET NO: 756247
AIR CONTENT (%): 3.8 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
Paving, west property line to Freeport parkway, 65' x 680', reference point fire hydrant on
west property line. Paving 90' northeast of hydrant.
SAMPLE LOCATION: 45' south at 575' east
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
CYLINDER MAXIMUM COMPRESSIVE
MARKED DATE AGE DIAMETER AREA LOAD STRENGTH FRACTURE
SET NO. TESTED (days) (inches) (sq.in.) (lbs. force) (7 TYPE
2 1 11/06/2004 7 6.00 28.26 102910 ?3640 Unbonded Cap
2 2 11/27/2004 28 0.00 0.00 '-~-,-~ Unbonded Cap
2 3 11/27/2004 28 0.00 0.00 Unbonded Cap
2 4 Hold
LIMITATIONS; The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc) or any other feature of similax subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the wriaen approval of Rone Engineers, Ltd
01SS Page 2 of 6
Rone
ineers
8908 Ambassador Row, Dallas, TX '75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, ltouston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Client:
Duke Realty Services, LP
Mr. Brian Straley
5495 Belt Line Rd., Ste 360
Dallas TX 75254
Project: Freeport XI & XII
Coppell, Texas
Services:
Report No.: 221911
Project No.: 049245
Date of Service: 10/30/2004
Report Date: 11/09/2004
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
MEASURED
STRENGTH:
SLUMP (in):
AIR (%):
TEST METHOD:
CONTRACTOR: Duke Construction
CONCRETE SUPPLIER: Southern Star
PLANT: 27
SPECIFICATION REQUIREMENTS
4000 psi ~ 28 Days
5" maximum
3% - 5%
ASTM C-172
ASTM C-31
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-1231
ASTM C-39
REPORT
MIXDESIGN I.D.: 7752 SLUMP
PLACEMENT DATE: 10/30/2004 (inchesl
WEATHER CONDITIONS: Partly cloudy 3.75
TIME SAMPLED: 9:30ali1 BATCHTIME: 9202am
TEMPERATURE (F) - AIR 61 F CONCRETE: 80 F
TRUCKNO: 931 TICKETNO: 756257
AIR CONTENT (%): 4.7 UNIIWEIGHT(pcO: NA
OVERALL PLACEMENT LOCATION:
Paving, west property line to Freepori Parkway, 65' x 680', reference point fire hydrant on
west proper'o, line Paving 90' northeast of hydrant.
SAMPLE LOCATION: 30' south at 420' east
OF TESTS
Concrete Compressive Cylinder 6" x 12"
CYLINDER MAXIMUM COMPRESSIVE
MARKED DATE AGE DIAMETER AREA LOAD STRENGTH FRACTURE
SET NO. TESTED (days) (inches) (sq.in.) (lbs. force) (PT TYPE
3 1 11/06/2004 7 6.00 28.26 117740 ~4160 Unbonded Cap
3 2 11/27/2004 28 0.00 0.00 Unbonded Cap
3 3 11/27/2004 28 0.00 0.00 Unbonded Cap
3 4 Hold
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01SS Page 3 of 6
ineers
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Client:
Duke Realty Services, LP
Mr. Brian Straley
5495 Belt Line Rd., Ste 360
Dallas TX 75254
Project: Freeport XI & XII
Coppell, Texas
Services:
Report No.: 221911
Project No.: 049245
Date of Service: 10/30/2004
Report Date: 11/09/2004
Ob~in samples of fi-esh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
STRENGTH:
SLUMP (in):
AIR (%):
TEST METHOD:
CONTRACTOR: Duke Construction
CONCRETE SUPPLIER: SouthelTl Star
pLANT: 27
SPECIFICATION REQUIREMENTS
4000 psi ~ 28 Days
5" maximum
3% - 5%
ASTM C- 172
ASTM C-31
ASTM C-143
ASTM C-231
ASIM C-1064
ASTM C-1231
ASTM C-39
ex~ptgl2
REPORT
MEASURED
MIX DESIGN I.D.: 7752 SLUMe
PLACEMENT DATE: 10/30/2004 (inches)
WEATHER CONDITIONS: Mostly sunny 4.00
TIME SAMPLED: 10:45am BATCH TIME: NA
TEMPERATURE (F) - AIR 60 F CONCRETE: 81 F
TRUCK NO: 1097 TICKET NO: 756266
AIR CONTENT (%): 4.7 UNIT WE1GHT (pet): NA
OVERALL PLACEMENT LOCATION:
Paving, west properW line to Freeport Parkway, 65' x 680'. reference point fire hydrant on
west property line. Paving 90' northeast of hydrant.
SAMPLE LOCATION: 10' south at 360' east
OF TESTS
Concrete Compressive Cylinder 6" x 12"
C~i~L1NDER MA.XIMUM
MARKED DATE AGE DIAMETER AREA LOAD
SET NO. TESTED (days) (inches) (sq.in.) (lbs. force)
4 1 11/06/2004 7 6.00 28.26 101090
4 2 11/27/2004 28 0.00 0.00
4 3 11/27/2004 28 0.00 0.00
4 4 Hold
COMPRESSIVE
STRENGTH
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing We assume no responsibiliiy for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our le~ers and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in flail without the ,sTitten approval of Rone Engineers, Ltd.
01SS Page 4 of 6
RoneEngineers
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Client:
Duke Realty Services, LP
Mr. Brian Straley
5495 Belt Line Rd., Ste 360
Dallas TX 75254
Project: Freeport XI & XII
Coppell, Texas
Services:
Report No.: 221911
Project No.: 049245
Date of Service: 10/30/2004
Report Date: 11/09/2004
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
MEASURED
STRENGTH:
SLUMP (in):
AIR (%):
TEST METHOD:
CONTRACTOR: Duke Construction
CONCRETE SUPPLIER: Southern Star
PLANT: 27
SPECIFICATION REQUIREMENTS
4000 psi ~ 28 Days
5" maximum
3% - 5%
ASTM C-172
ASTM C-31
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-1231
ASTM C-39
except 9 12
MIX DESIGN I.D.: 7752 SLUMP
PLACEMENT DATE: 10/30/2004 (inches)
WEATHER CONDITIONS: Sunny 3.75
TIME SAMPLED: 1 l;30am BATCH TIME: 10:45ali1
TEMPERATURE (F) - AIR 60 F CONCRETE: 83 F
TRUCKNO: 923 T1CKETNO: 756273
AIR CONTENT (%): 4.4 UNITWEIGHT(pc0: NA
OVERALL PLACEMENT LOCATION:
Paving, west property line to Freeport Parkway, 65' x 680', reference point fire hydrant on
west property line. Paving 90' northeast of hydrant.
SAMPLE LOCATION:
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
25' south at 265' east
CYLINDER NLa~kIMUM COMPRESSIVE
MARKED DATE AGE DIAMETER AREA LOAD STRENGTH FRACTURE
SET NO. TESTED (days) (inches) (sq.in.) (lbs. force) ~i) TYPE
5 1 11/06/2004 7 6.00 28.26 99540 ~3520 Unbonded Cap
5 2 11/27/2004 28 0.00 0.00 Unbonded Cap
5 3 11/27/2004 28 0.00 0.00 Unbonded Cap
5 4 Hold
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our leRers and
reports are for the exclusive use of the client~ to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd
01SS Page 5 of 6
ineers
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, ltouston, TX 77040
Corporate Phone: (214} 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Client:
Duke Realty Services, LP
Mr. Brian Straley
5495 Belt Line Rd., Ste 360
Dallas TX 75254
Project: Freeport XI & XII
Coppell, Texas
Report No.: 221911
Project No.: 049245
Date of Service: 10/30/2004
Report Date: 11/09/2004
Obtain samples of flesh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
MEASURED
STRENGTH:
SLUMP (in):
AIR (%):
TEST METHOD:
CONTRACTOR: Duke Construction
CONCRETE SUPPLIER: Southern Star
PLANT: 27
SPECIFICATION REQUIREMENTS
4000 psi ~ 28 Days
5" maximum
3% - 5%
ASTM C-172
ASTM C-31
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-1231
ASTM C-39
MIX DESIGN I.D.: 7752 SLUMP
PLACEMENT DATE: 10/30/2004 (inches)
WEATHER CONDITIONS: Sunny 5.00
TIME SAMPLED: 12:00pm BATCHTINIE: NA
TEMPERATURE (F) - AIR 6 ] F CONCRETE: 86 F
TRUCKNO: 8 TICKETNO: 756279
AIR CONTENT (%): 4.4 UNIT WEIGHT (pcl): NA
OVERALL PLACEMENT LOCATION:
Paving, west properW line to Freeport Parkway, 65' x 680', reference point fire by,ant on
west property line Paving 90' northeast of hydrant.
SAMPLE LOCATION: 5' south at 110' east
REPORT OF TESTS
· ' ' x 12"
Concrete Compress ve C'yl rider 6
CYLINDER
MARK]ED DATE AGE DIAMETER
SET NO. TESTED (days) (inches)
6 1 11/06/2004 7 6.00
6 2 11/27/2004 28 0.00
6 3 11/27/2004 28 0.00
6 4 Hold
See Report #221910 for technician time.
Technician: Scott Mitchell
Report Distribution:
(1) Duke Realty Services, LP
(1) Extranet
(1) City of Coppell
(1) City of Coppall
MAXIMUM COMPRESSIVE
AREA LOAD STRENGTH FRACTURE
(sq.in.) (lbs. force) t (psi) TYPE
28.26 109130 k, 3860 Unbonded Cap
0.00 Unbonded Cap
0.00 Unbonded Cap
Started: Finished:
Scott Watson, AET
CMT Operations Manager
LIMATATIONS: The test results presented herein were prepared based upon the specific samples provided for testing We assume no responsibility for variation in quality
(composition, appearance, performance, etc ) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd
01SS Page 6 of 6
RoneEn gineers
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Client:
Duke Realty Services, LP
Mr. Brian Straley
5495 Belt Line Rd., Ste 360
Dallas TX 75254
Report No.: 221910
Project No.: 049245
Date of Service: 10/30/2004
Report Date: 11/09/2004
Project: Freeport XI & XII
Coppell, Texas
Services: Obtain samples of fi'esh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
STRENGTH:
SLUMP (in):
AIR (%):
TEST METHOD:
CONTRACTOR: Duke Construction
CONCRETE SUPPLIER: Southern Star
pLANT: 27
SPECIFICATION REQUIREMENTS
4000 psi @ 28 Days
5" maximum
NA
ASTM C-172
ASTM C-31
ASTM C-143
ASTM C-231
ASTM C- 1064
ASTM C-1231
ASTM C-39
ex.pt912
PROJECT DATA
MIX DESIGN I.D.: 9349
PLACEME~' DATE: 10/30/2004
WEATHER CONDITIONS: Partly cloudy
T1MESAMPLED: 4:30am BATCHTIME: 4:10am
TEMPERATURE (F) - AIR 61 F CONCRETE: 72
TRUCKNO: 923 TICKETNO: 756214
AIR CONTENT (%): NA UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
Panels #3 - #11
MEASURED
SLUMP
(inches)
4.50
SAMPLE LOCATION:
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Panel #5
MAXIMUM COMPRESSIVE
CYLINDER
.MARKED DATE AGE DIAMETER AREA LOAD STRENGTH
SET NO. TESTED (days) (inches) (sq.in.) (lbs. force) ~i)
1 1 11/06/2004 7 6.00 28.26 139050 ~9_20
FRACTURE
TYPE
Unbonded Cap
1 2 11/27/2004 28 0.00 0.00 Unbonded Cap
1 3 11/27/2004 28 0.00 0.00 Unbonded Cap
l 4 Hold
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibiliW for variation in quality
(composition, appearance, performance, etc) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reporis are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in f~ll without the written approval of Rone Engineers, Ltd.
01SS Page I of 2
RoneEn gineers
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Client:
Duke Realty Services, LP
Mr. Brian Straley
5495 Belt Line Rd., Ste 360
Dallas TX 75254
Report No.: 221910
Project No.: 049245
Date of Service: 10/30/2004
Report Date: 11/09/2004
Project: FreeportX1 &XII
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
STRENGTH:
SLUMP (in):
AIR (%):
TEST METHOD:
CONTRACTOR: Duke Construction
CONCRETE SUPPLIER: SouthelTl Star
PLANT: 27
SPECIFICATION REQUIREMENTS
4000 psi ~ 28 Days
5" maximum
NA
ASTM C-172
ASTM C-31
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-1231
ASTM C-39
MIX DESIGN I.D.: 9349
PLACEMENT DATE: 10/30/2004
WEATHER CONDITIONS: Partly cloudy
TIME SAMPLED: 5:45altl BATCH TIME: 5: ] 5 arfl
TEMPERAT~rRE (F) - AIR 61 F CONCRETE: 73 E
TRUCK NO: 923 TICKET NO: 756224
AIR CONTENT (%): NA UNITWEIGHT(pcO: NA
OVERALL PLACEMENT LOCATION:
Panels #3 - # 11
MEASURED
SLUMP
(inches)
4.75
SAMPLE LOCATION: Panel #9
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
CYLINDER
MARKED DATE AGE DIAMETER
SET NO. TESTED (days) (inches)
2 1 11/06/2004 7 6.00
2 2 11/27/2004 28 0.00
2 3 11/27/2004 28 0.00
2 4 Hold
Technician: Scott Mitchell
Report Distribution:
(1) Duke Realty Services, LP
( 1 ) Extranet
(1) City of Coppell
(1) City of Coppell
Started: 3:15am
MAO~IMUM COMPRESSIVE
AREA LOAD STRENGTH
(sq.in.) (lbs. force) i~psi)
28.26 132600
0.00
0.00
Finished: 3:00pm
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
K. Scott Watson, AET
CMT Operations Manager
LhV/ITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc ) or any other feature of similar subject mailer provided by persons or conditions over which we have no control Our lette/s and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd
Page 2 of 2