Freeport NIP(8.0)-LR041201Roi ineers 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630-9745 IN-PLACE DENSITY TESTING Client: Project: Duke Realty Services, LP Mr. Brian Straley 5495 Belt Line Rd., Ste 360 Dallas TX 75254 Freeport XI & XII Coppell, Texas Perform In-Place Density Test in accordance with ASTM Standards. Report No.: 223248 Project No.: 049245 Date of Service: 11/20/2004 Report Date: 12/01/2004 PROJECT DATA CONTRACTOR: Test Methods: I~UD No. Duke Construction ASTM D-2922 ASTM D-3017 Gauge: Troxler 3430 Gauge Serial No: 35518 Test Mode: BS Moisture Current: 644 Previous: 640 Standard Counts Density Current: 2716 Previous: 2708 Description MOISTURE DENSITY RELATIONS Maximum Moisture % Density pcf Recycled Concrete w/Clayey Sand Project Requirements Moisture Density 12.5 117.0 NA 95 min FIELD DENSITY TESTS TEST NO TEST LOCATION PROBE DEPTH MfD MOISTURE WET DENSITY DRY DENSITY DENSITY No. (%) (pc0 (pcf) (% max) Flex base 1 Northbound mm lane, 25' south of north end Flex base 2 Northbound turn lane, 25' north of south end Technician: Joe Jemigan Report Distribution: (1) Duke Really Services, LP (1) Exttanet (1) City of Coppell (1) City of Coppell 0" I 19.7 132.5 110.7 95 0" 1 19.9 132.9 110.8 95 Started: 8:30am Finished: ll:00a K. Scott Watson, AET CMT Operations Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing We assume no responsibilily for variation in qualily (composition, appearance, performance, etc) or any other fealure of similar subject mailer provided by persons or conditions over which we have no control. Our leilers and repons are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd 07TM Page I of I Roi Client: ;ers Duke Realty Services, LP Mr. Brian Straley 5495 Belt Line Rd., Ste 360 Dallas TX 75254 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630-9745 IN-PLACE DENSITY TESTING Report No.: 222944 Project No.: 049245 Date of Service: 11/15/2004 Report Date: 12/01/2004 Project: Freeport XI & XII Coppell, Texas Services: Perform In-Place Density Test in accordance with A§TM Standards. CONTRACTOR: Duke Construction Test Methods: ASTM D-2922 ASTM D-3017 PROJECT DATA Gauge: Troxler 3430 Moisture Gauge Serial No: 35518 Current: 648 Test Mode: DT Previous: 633 Standard Counts Density Current: 2684 Previous: 2669 M/D No. Description MOISTURE DENSITY RELATIONS Maximum Moisture % Density pcf Recycled Concrete w/Clayey Sand 12.5 117.0 Project Requirements Moisture Density NA 95 min TEST NO TEST LOCATION PROBE DEPTH M/D MOISTURE WET DENSITY DRY DENSITY DENSITY No. (%) (pc0 (pcfl (% max) Paving subgrade 0" 108.0 92.1 1 Northbound turnlane, 25' from north end 1 17.3 Paving subgrade 0" 89.1 2 Northbound tumlane, 25' from south end 1 19.4 106.4 An asterisk (*) appears next to test results which do NOT meet the project specifications. Technician: Joe Jemigan Report Distribution: (1) Duke Realty Sen'ices, LP (1) Extranet (1) CiD' of Coppell (1) City of Coppell Started: l:00pm 79* 76* Finished: 2:45pm CMT Operations Manager LEMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We ~ssume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject manet provided by persons or conditions over which we have no control. Our lei~ers and reports are for the exclusive use of the clients to whom they are addressed and Sphaalglell~ toi~e ir e p r o d u c e d except ill f/Ill without the written approval of Rorle Engineers, Ltd. Re ineers 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630-9745 IN-PLACE DENSITY TESTING Client: Project: Services: Duke Realty Servic~r,~LP Mr. Brian Slrale~ '~ 5495 B~., St~360 Report No.: 223192 Project No.: 049245 11/19/2004 12/01/2004 Date of Service: Perform In-Place Density Test in accordance with ASTM Standards. PROJECT DATA CONTRACTOR: Duke Construction Test Methods: ASTM D-2922 ASTM D-3017 Gauge: Troxler 3430 Gauge Serial No: 35518 Test Mode: DT Moisture Current: 640 Previous: 638 Standard Counts Density Current: 2708 Previous: 27 l 2 MfD No. Description Brown Silty Sandy Clay MOISTURE DENSITY RELATIONS Maximum Moisture % Density pcf Project Requirements Moisture Density 20.0 103.0 Optimum +4 95 min FIELD DENSITY TESTS TEST NO Technician: Joe Jernigan Report Distribution: PROBE TEST LOCATION DEPTH M/D MOISTURE WET DENSITY DRY DENSITY No. (%) (per) (pc0 Fill Inside leaveouts, F/10, 1' below grade 6" I 24.3* 127.4 102.5 Fill Inside leaveouts, F/03, 2' below grade 6" 1 23.2 126.7 102.8 Fill Inside leaveouts, C/01, 2' below grade 6" 1 25.1 * 126.2 100.9 An asterisk (*) appears next to test results which do NOT meet the project specifications. ~8t~d~ l:15pm 3:00pm / K. Scottt'~atson, AET DENSITY (% max) 100 98 (1) Duke Realw Services, LP A [ ,: (1) Extranet (1) City of Coppell CMT Operations Manager (1) City of Coppell / LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc) or any other feature of similar subiect matler provided by persons or conditions over which we have no control Our letters and reports are for the exclusive use of the clients to whom they are addressed and'shall not be reproduced except in fall without the written approval of Roue Engineers, Ltd. 07TM Page 1 of 1 ineers 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630-9745 REPORT OF CYLINDER COLLECTION Client: Duke Realty Services, LP Mr. Brian Straley 5495 Belt Line Rd., Ste 360 Dallas TX 75254 Project: Freeport X! & XII Coppell, Texas Report No.: 223217 Project No.: 049245 Date of Service: 11/20/2004 Report Date: 12/01/2004 Services: Cylinder Collection Report of Collection On this date, a Rone Engineers, Ltd. representative arrived on site as scheduled to pick up compressive strength test specimen cast prior to this date. Technician Time: 6:45am - 8:00am Page 1 of 1 Technician: Jeremy WaRs Report Distribution: (I) Duke Realty Services, LP (1) Extranet (1) City of Coppell (1) City of Coppell Rone Engineers, Ltd. LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject mailer provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd Paffe I of I RoneEn gineers 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 761! 8 6300 Rothway, St¢. 150, Houston, TX 77040 Corporate Phone: (214} 630-9745 REPORT OF REINFORCING STEEL INSPECTION Client: Duke Realty Services, LP Mr. Brian Straley 5495 Belt Line Rd., Ste 360 Dallas TX 75254 Project: Freeport XI & XII Coppell, Texas Report No.: 223317 Project No.: 049245 Date of Service: 11/24/2004 Report Date: 12/01/2004 Services: Reinforcing Steel Inspection Report of Inspection On this date, a Rone Engineers, Ltd. representative(s) arrived on site as scheduled to perform a Reinforcing Steel Inspection. The results are attached. Technician Time: 7:00am - 8:15am Page 1 of 2 Technician: Bobby Robinson Report Distribution: (1) Duke Realty Services, LP (1) Extranet (1) City of Coppell (l) City of Coppell erations Manager LLMITATIONS: The test results presented herein were prepared ba~ed upon the specific samples provided for testing, We assume no responsibility for variation in quality (composition, appearance, performance, etc) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our lertem and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd. 99TM Page 1 of I 8908 Ambassador Row Dallas, Texas 75247 (214) 630-9745 121 North Rayner Fort Worth, Texas 76111 (817) 831-6211 Report of Reinforcing Steel Inspection Client: ~c,,J(~c ¢6c~'~/ ~v,ced'~lL~ ReportNo.: Project No.: Project: Ft~*~¢ ~[ ~ ~ Date of Se~ice: (~a~ ~ ~O~) Page Locations and Items Inspected: Items Inspected: Conforming Non Items lnsl~cted: Conforming Non Items Inspacted: Conforming Non Conforming Conforming Conforming Placing Drawings t// Bar Length p/ Column Ties Properly Approved and Shape Tied and Spaced ~ Bar Size ~/' Proper Bar Placemem t/' Stirrup Spacing and Type ~ r Bar Grade I/ F Properly Tied ~ Lapped Splices ~ Bars Clean ~ Dowel B~rs in Place / Welded Splices Form Clean 6/r Proper Bar Supports ~ Mechanical Splices qumber Bars l,/ Proper Cover 1/ Discrepancies / Comments: Inspector's Signature: Client/Contractor Signature: Client/Contractor Copied with Results: Yes / No ineers 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 62500 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630-9745 REPORT OF STRUCTURAL STEEL INSPECTION Client: Duke Realty Services, LP Mr. Brian Straley 5495 Belt Line Rd., Ste 360 Dallas TX 75254 Project: Freeport XI & XII Coppell, Texas Report No.: 603125 Project No.: 049245 Date of Service: 11/23/2004 Report Date: 12/01/2004 Services: Structural Steel Inspection Report of Inspection On this date, a Rone Engineers, Ltd. representative(s) arrived on site as scheduled to perform a Structural Steel Inspection. The results are attached. Technician Time: ll:15am - l:30pm Page 1 of 2 Technician: D, Wilcher CAWI-02040654 Report Distribution: (1) Duke Realty Services, LP (1) Extranet (1) City of Coppell (I) CiD' of Coppell LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd. Rone neers 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6.300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630-9745 Report of Structural Steel Inspection Client: Duke Realty Services, Inc. Report No.: 603125 Project No.: 049245 Project: Freeport II Date of Service: 11/23/2004 Coppell, Texas Page 2 of 2 Column Base Plates Location: Gridline A to F and 1 to 11 (partial random inspection performed). ~ Non Code Compliant Compliant AWS D1,1 ~ Other Anchor Bolt Tension Verification X X Spec Grouted Base Plates X Spec Comments: Location: Structural Framing Non Code __ Compliant Compliant AWS D-~.I '---~ISC Other Bolt Tension Verification: Column to Column Bolt Tension Verification: Beam to Column Column Plumbness Weld Profile Nelson Stud Verification WQT's Structural Comments: LIMITATIONS The test results presented herein were prepared based upon the specific samples pmvirSed for testing We assume no responsibility for variation in quality (composition, · · Our letters and reports are fo- the exclusive appearance, performance, otc ) or any other feature of slm~tar sg~bJeCt matter provided by persons or conditions over which we have no con o[ use of tb~ clients to whom they are addressed and shall not be reproduced except in full without the vcrfft en approval of Rone Engineers, Ltd Rom ineers 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630-9745 REPORT OF STRUCTURAL STEEL INSPECTION Client: Duke Realty Services, LP Mr. Brian Straley 5495 Belt Line Rd., Ste 360 Dallas TX 75254 Project: Freeport XI & XII Coppell, Texas Report No.: 603104 Project No.: 049245 Date of Service: 11/16/2004 Report Date: 12/01/2004 Services: Structural Steel Inspection Report of Inspection On this date, a Rone Engineers, Ltd. representative(s) arrived on site as scheduled to perform a Structural Steel Inspection. The results are attached. Technician Time: 6:30am - 10:15am Page 1 of 2 Technician: Jeb Gray CWI#02041061 Report Distribution: (1) Duke RealW Services, LP (l) Extranet (1) CiD' of Coppell (1) City of Coppell LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing We assume no responsibility for variation in quality (composition, appearance, performance, etc ) or any other feature of similar subject mat~er provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shah not be reproduced except in fall without the written approval of Rone Engineers, Ltd. OOT]k~ RONE ENGINEERS Client: Duke Realty Services, LP Report No.: 603104 Date of Service: 11/16/2004 Project No.: 049245 Page 2 of 2 Location: Bar Joists Freeport Buildings #11 and #12, Section 12-15, Gridlines A-E. Non Code Compliant Compliant AWS D1.1 S JI Other Joist Seat Bearing X x Spec Visual Weld Verification X x Spec Horizontal Bridging X X Spec Diagonal Bddging X X Spec Bottom Chord StabiLization Joist Spacing Per meter Edge Angle Weld Verification X Spec WQT's Structural Comments: Location: Sheet Deck Attachment to Structural Framing Freeport Buildings #11 and #12, Section 12~15, Gridlines A-E. Non Code Compliant Compliant AWS D1.3 SJI Other Visual Verification Puddle Welds X X Spec Visual Verification Powder Actuated Visual Verification Pneumatic Visual Verification Tek Screws X X Spec Side Laps Mechanically Fastened Side Laps Mechanically Crimped Sheet Deck Intedor Attachment Pattern X X Spec Sheet Deck Perimeter Attachment Pattern X X Spec WQT's Sheet Steel Comments: Intersection of Section 14 and Gridline E. This area ~s currentl being used for the cons entrance. Will inspect at a later date. 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630-9745 REPORT OF STRUCTURAL STEEL INSPECTION Client: Duke Realty Services, LP Mr. Brian Straley 5495 Belt Line Rd., Ste 360 Dallas TX 75254 Project: Freeport XI & XII Coppell, Texas Report No.: 603100 Project No.: 049245 Date of Service: 11/15/2004 Report Date: 12/01/2004 Services: Structural SteelInspection Report of Inspection On this date, a Rone Engineers, Ltd. representative(s) arrived on site as scheduled to perform a Structural Steel Inspection. The results are attached. Technician Time: 7:00am - l:30pm Page 1 of 2 Technician: Jeb Gray CWI#02041061 Report Distribution: (I) Duke Realty Services, LP (l) Extranet (i) City of Coppell (1) City of Coppell LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for v~iation in quality (composition, appearance, performance, etc) or any other feature of similar subject mailer provided by persons or conditions over which we have no control. Our le~ers and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd 99TM RONEENGINEERS Client: Duke Realty Services Repor[ No.: 603100 Date of Service: 11/15/2004 Project No.: 049245 Page 2 of 2 Location: Bar Joists Freepod Buildings #11 and #12. Section 9-12, Gridline A-F. I Non Code Compliant Compliant AWS D1.1 SJI Other Joist Seat Bearing X x Spec Visual Weld Verification X X Spec Horizontal Bridging X X Spec Diagonal Bridging X X Spec Bottom Chord Stabilization Joist Spacing Perimeter Edge Angle Weld Verification X X Spec WQT's Structural Comments: Location: Sheet Deck Attachment to Structural Framing Section 01-8, Gridline A-F. Non Code Compliant Comp ant l AWS D1.3 SJI Other Visual Verification Puddle Welds X X Spec Visual Verification Powder Actuated Visual Verification Pneumatic iVisuai Verification Tek Screws x X Spec Side Laps Mechanically Fastened Side Laps Mechanically Crimped Sheet Deck Intedor Attachment Pattern X X Spec ;heet Deck Perimeter Attachment Pattern X X Spec WQ'F's Sheet Steel Comments: LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing We assume no responsibility for vadabon in quality (composition · neers 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6500 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630-9745 REPORT OF STRUCTURAL STEEL INSPECTION Client: Duke Realty Services, LP Mr. Brian Straley 5495 Belt Line Rd., Ste 360 Dallas TX 75254 Project: Freeport X! & XII Coppell, Texas Report No.: 603088 Project No.: 049245 Date of Service: 11/11/2004 Report Date: 12/01/2004 Services: Structural Steel Inspection Report of Inspection On this date, a Rone Engineers, Ltd. representative(s) arrived on site as scheduled to perform a Structural Steel Inspection. The results are attached. Technician Time: 2:45pm - 6:00pm Page 1 of 2 Technician: Jeb Gray CWI#02041061 Report Distribution: (1) Duke Realty Services, LP (1) Extranet (I) City of Coppell (1) Ci'ff of Coppell cken CMT Division Manager LLMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc) or any other feature of similar subject magter provided by persons or conditions over which we have no control Our letlets and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd RONE ENGINEERS Client: Duke Realty Services, LP Report No.: 603088 Date of Service: 11/11/2004 Project No.: 049245 Page 2 of 2 Location: Bar Joists Freeport Buildings #11 and #12. Section 6-9, Gridline A-F. Non Code Compliant Compliant AWS D1.1 SJI Other Joist Seat Bearing X Visual Weld Verification X Horizontal Bridging X Diagonal Bridging X Bottom Chord Stabilization x Joist Spacing Perimeter Edge AngJe Weld Verification WQT's Structural Comments: Location: Sheet Deck Attachment to Structural Framing Non Code Compliant Compliant AWS D1.3 SJI Other Visual Verification Puddle Welds Visual Verification Powder Actuated Visual Verification Pneumatic Visual Verification Tek Screws Side Laps Mechanically Fastened Side Laps Mechanically Crimped Sheet Deck Interior Attachment Pattern Sheet Deck Perimeter Attachment Pattern ~/VQT's Sheet Steel Comments: UM~TATIONS: The test results presented herein were prepared based upon the specific samples provided for testing We assume ne responsibil~ for vanagon in quality (composition, appearance, p~rformance etc ) or any other feature of similar subject metier provided by persons or cond~ions over which we have no cor~ral OUr h~13ers and reports are for the exciu siva use of the clients to whom they are addressed an~ shall not be repro0uced except in full w~thout the wntle n approval of Ro~le Engineers Ltd