Four Seasons 2R-LR050114 CONCRETE COMPRESSIVE STRENGTH TEST
. Report Number: 940413880056
Service Date: December 30, 2004
'lrei racan
8901 Carpenter Frwy Ste#100
Dallas fe,:as 75247
Client: Hill & Wilkinson LTD
Attn: Charles Hoagland
800 Klein Rd Ste 100
Piano TX 75074
Report D~JanuaFy 14 2005
Project: BCE Specialt_~s~~-~
~'~{'-~andy Lake Road
Coppell, TX
Project Number: 94041388
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 3:45 am
Supplier: Southern Star
Truck No: 2
Mix I.D. No.: 9349
Water Added Onsite Before Test:
Water Added Onsite After Test:
Field Test Data
Test Result
Slump, inches: 800
Air Content, %: 1.6
Concrete Temperature, o F; 62
Ambient Temperature, o F: 61
Plastic Unit Weight, pcf: 1472
Laboratory Test Data
Set Specimen Diameter Area
No. ID (inches) (sq. inches)
6.00 28,27
6.00 28.27
Plant: 29
Ticket No: 751255
5 Gallons
0 Gallons
3
4
Sample Information
Sample Time: 420 am Date Cast: December 30, 2004
Technician: Michael E Odom
Weather Conditions: Cloudy
Accumulative Yards: 860
Placement Method: Pump
Sample Locations: C5/2.5
Placement Location: Bldg. Slab-on-Grade
Specification Test Method
50 Max
ASTM C143
ASTM C231
ASTM C1064
ASTM C1064
ASTM C138
Age at Maximum Compressive
Date Test Load Strength
Tested (days) (lbs) (psi)
01/06/2005 7 102,050 / 3,610 '~
~,~.. 3,650~,~
01/06/2005 7 103,250
Average 3,630
01/27/2005 28
01/27/2005 28
Services
Obtain samples of fresh conc~.~at the placement locations, perform required field tests and cast compressive
strength samples. J '~ ~
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the chent
indicated above and shall not be reproduced except in full without the written consent of our company Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials
Page 1 of 9 i
cONCRETE COMPRESSIVE STRENGTH TEST
· Report Number: 94041388.0056
Service Date: December 30, 2004
'lrerracon
8901 CarpenterFrwy Ste#100
Dallas, Texas 75247
(214) 630-1010
Client: Hill & Wilkinson LTD
Attn: Charles Hoagland
800 Klein Rd Ste 100
Piano TX 75074
Report Date: January 14, 2005
Project: BCE Specialties
989 West Sandy Lake Road
Coppell, TX
Project Number: 94041388
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 5:00 am
Supplier: Southern Star
Truck No: 834
Mix I,D. No: 9349
Water Added Onsite Before Test:
Water Added Onsite After Test:
Field Test Data
Test
Plant: 29
Ticket No: 751265
0 Gallons
0 Gallons
Result
Slump, inches: 6.00
Air Content, %: 1.7
Concrete Temperature, o F: 62
Ambient Temperature, o F: 61
Plastic Unit Weight, pcf: 150.4
Laboratory Test Data
Sample Information
Sample Time: 5:20 am Date Cast: December 30, 2004
Technician: Michael E Odom
Weather Conditions: Cloudy
Accumulative Yards: 860
Placement Method: Pump
Sample Locations: B/4
Placement Location: See page 1
Specification Test Method
5.0 Max
ASTM C143
ASTM C231
ASTM C1064
ASTM C1064
ASTM C138
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq inches) Tested (days) (lbs) (psi)
2 1 6,00 2827 01/06/2005 7 103,550 3,660
2 2 6.00 28.27 01/06/2005 7 100,310 3,550
Average 3,610
2 3 01/27/2005 28
2 4 01/27/2005 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods This report is exclusively for the use of the client
indicated above and shall not be reproduced except m full without the written consent of our company Test results transmitted hereto are onlyapphcable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properhes of other apparently s~rnilar or identical
materials.
Page 2 of 9
cONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 940413880056
Service Date: December 30, 2004
'll'erracan
8901 Carpenter Frwy. Ste #100
Dallas Texas 75247
(214) 630-1010
Client: Hill & Wilkinson LTD
Attn: Charles Hoagland
800 Klein Rd Ste 100
Piano TX 75074
Report Date: January 14. 2005
Project: BCE Specialties
989 West Sandy Lake Road
Coppell, TX
Project Number: 94041388
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time:
Supplier: Southern Star
Truck No: 890
Mix I.D. No.: 9349
Water Added Onsite Before Test:
Water Added Onsite After Test:
Field Test Data
Test
Plant: 29
Ticket No: 751276
0 Gallons
0 Gallons
Result
Slump, inches: 5.75
Air Content, %: 1.4
Concrete Temperature, o F: 62
Ambient Temperature, o F: 62
Plastic Unit Weight, pcf: 150.0
Laboratory Test Data
Set Specimen Diameter Area
No. ID (inches) (sq inches)
3 1 600 28.27
3 2 6.00 28.27
3 3
3 4
Sample Information
Sample Time: 6:55 am Date Cast: December 30. 2004
Technician: Michael E Odom
Weather Conditions: Cloudy
Accumulative Yards: 860
Placement Method: Pump
Sample Locations: C1/5.2
Placement Location: See page 1
Specification Test Method
50 Max
ASTM C143
ASTM C231
ASTM C1064
ASTM C1064
ASTM C138
Age at Maximum Compressive
Date Test Load Strength
Tested (days) (lbs) (psi)
01/06/2005 7 105,790 3,740
01/06/2005 7 103,010 3.640
Average 3,690
01/27/2005 28
01/27/2005 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods This report is exclusively for the use of the client
indicated above and shall not be reproduced except in fu[I without the written consent of our company Test results transmitted herein are onlyapp[icable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently s~milar or identical
materials.
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 940413880056
Service Date: December 30, 2004
i r
erracan
8901 Carpenter Frwy Ste#100
Dallas, Texas 75247
(214) 630-1010
Client: Hill & Wilkinson LTD
Attn: Charles Hoagiand
800 Klein Rd Ste 100
Piano TX 75074
Report Date: January 14, 2005
Project: BCE Specialties
989 West Sandy Lake Road
Coppell, TX
Project Number: 94041388
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 7:00 am
Supplier: Southern Star
Truck No: 834
Mix I.D. No.: 9349
Water Added Onsite Before Test:
Water Added Onsite After Test:
Field Test Data
Test
Plant: 29
Ticket No: 751284
0 Gallons
0 Gallons
Result
Slump, inches: 6 00
Air Content, %: 1.4
Concrete Temperature, o F: 62
Ambient Temperature, o F: 63
Plastic Unit Weight, pcf: 149.2
Laboratory Test Data
Sample Information
Sample Time: 7:45 am Date Cast: December 30, 2004
Technician: Michael E Odom
Weather Conditions Cloudy
Accumulative Yards: 860
Placement Method: Pump
Sample Locations: A5/56-57
Placement Locabon See page 1
Specification Test Method
50 Max
ASTM C143
ASTM C231
ASTM C1064
ASTM C 1064
ASTM C138
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq inches) Tested (days) (lbs) (psi)
4 1 6.00 28.27 0110612005 7 104,210 3,690
4 2 6.00 28.27 01/06/2005 7 100,770 3,560
Average 3,630
4 3 01/27/2005 28
4 4 01/27/2005 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the propedies of other apparently similar or identical
materials
Page 4 of 9 ~" ~'~"~" ~ .........
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94041388.0056
Service Date: December 30, 2004
'lre racon
8901 CarpenterFrwy Ste#100
Dallas [exas75247
(214) 630 ;010
Client: Hill & Wilkinson LTD
Attn: Charles Hoagland
800 Klein Rd Ste 100
Piano TX 75074
Report Date: January 14, 2005
Project: BCE Specialties
989 West Sandy Lake Road
Coppell, TX
Project Number: 94041388
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 8:35 am Plant: 29
Supplier: Southern Star
Truck No: 1824 Ticket No: 751297
Mix I.D. No.: 9349
Water Added Onsite Before Test: 10 Gallons
Water Added Onsite After Test: 0 Gallons
Sample Information
Sample Time 1040am Date Cast December 30 2004
Technician Michael E Odom
Weather Conditions Cloudy
Accumulative Yards: 860
Placement Method: Pump
Sample Locations: CI7.5
Placement Location: See page 1
Field Test Data
Test Result Specification Test Method
Slump, inches: 6.25 5.0 Max ASTM C143
Air Content, %: 1.8 ASTM C231
Concrete Temperature, o F: 67 ASTM C1064
Ambient Temperature, o F: ASTM C1064
Plastic Unit Weight, pcf: N/A ASTM C138
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
5 1 6.00 28.27 01/06/2005 7 77,660 2,750
5 2 6.00 28.27 01/06/2005 7 80,590 2,850
Average 2,800
5 3 01/27/2005 28
5 4 01/27/2005 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicableASTM. AASHTO. or DOT test methods This report isexclus~vely for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company Test results transmitted hereto are only applicable
to the actual samples tested at the location(s/ referenced and are not necessarily indicahve of the properties of other apparently % tm'ar ~' :denhOal
materials.
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 940413880056
Service Date: December 30, 2004
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client: Hill & Wilkinson LTD
Attn: Charles Hoagland
800 Klein Rd Ste 100
Piano TX 75074
Report Date: January 14, 2005
Project: BCE Specialties
989 West Sandy Lake Road
CoppelL TX
Project Number: 94041388
Material Information
Specified Strength: 4000 psi @ 28 Days
BatchTime: 11:15am Plant: 29
Supplier: Southern Star
Truck No: 923 Ticket No: 763376
Mix I.D. No.: 9349
Water Added Onsite Before Test: 25 Gallons
Water Added Onsite After Test: 0 Gallons
Sample Information
Sample Time: 11:30 am Date Cast: December 30, 2004
Technician: Michaet E. Odom
Weather Conditions:
Accumulative Yards: 860
Placement Method: Pump
Sample Locations: B 5/78-7 9
Placement Location: See page 1
Field Test Data
Test Result Specification Test Method
Slump, inches: 6.25 50 Max ASTM C143
Air Content, %: N/A ASTM C231
Concrete Temperature, o F: 69 ASTM C1064
Ambient Temperature, o F: 70 ASTM C1064
Plastic Unit Weight, pcf: 1460 ASTM C 138
Laboratory Test Data Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. iD (inches) (sq inches) Tested (days) (lbs) (psi)
6 1 600 28.27 01/06/2005 7 100,170 3,540
6 2 6.00 28.27 01/06/2005 7 93,980 3,320
Average 3,430
6 3 01/27/2005 28
6 4 01/27/2005 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods This report is exclusively for the use of the client
indicated above and shall not be reproduced except m full without the written consent of our company Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or ~dentical
materials ,, ..,. .....
Page 6 of 9
cONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94041388.0056
Service Date: December 30, 2004
'lrerracan
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
CLient: Hill & Wilkinson LTD
Attn: Charles Hoagland
800 Klein Rd Ste 100
Piano TX 75074
Report Date: January 14, 2005
Project: BCE Specialties
989 West Sandy Lake Road
Coppell, TX
Project Number: 94041388
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 11:30. am
Supplier: Southern Star
Truck No: 2040
Mix I.D No: 9349
Water Added Onsite Before Test:
Water Added Onsite After Test:
Field Test Data
Test
Plant: 29
Ticket No: 751319
0 Gallons
0 Gallons
Result
Slump, inches: 5.50
Air Content, %: 1 2
Concrete Temperature, o F: 71
Ambient Temperature, o F: 73
Plastic Unit Weight, pcf: 151.2
Laboratory Test Data
Sample Information
Sample Time: 12:55pm Date Cast: December 30, 2004
technician Michael E Odom
Weather Conditions: Partly cloudy
Accumulative Yards: 860
Placement Method: Pump
Sample Locations: C.8/9.2-9.3
Placement Location: See page 1
Specification Test Method
50 Max
ASTM C143
ASTM C231
ASTM C1064
ASTM C1064
ASTM C138
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq inches) Tested (days) (tbs) (psi)
7 1 6.00 2827 01/06/2005 7 112,000 3.960
7 2 600 2827 01/06/2005 7 114,300 4 040
Average 4,000
7 3 01/27/2005 28
7 4 01/27/2005 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company Test results transmitted herein are oply apphcable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properhes of othel apparently $~rnilar or identical
materials
Page 7 of 9 i H~[ ..........
CONCRETE COMPRESSIVE STRENGTH TEST
· Report Number: 94041388.0056
Service Date: December 30, 2004
'irerracan
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client: Hill & Wilkinson LTD
Attn: Charles Hoagland
800 Klein Rd Ste 100
Piano TX 75074
Report Date: January 14, 2005
Project: BCE Specialties
989 West Sandy Lake Road
Coppell, TX
Project Number: 94041388
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 1:05 pm
Supplier: Southern Star
Truck No: 923
Mix I.D. No,: 9349
Water Added Onsite Before Test:
Water Added Onsite After Test:
Field Test Data
Test
Plant: 29
Ticket No: 763389
5 GaLlons
0 Gallons
Result
Slump, inches: 5.50
Air Content, %: 1.4
Concrete Temperature, o F: 91
Ambient Temperature, o F: 73
Plastic Unit Weight, pcf: 150.2
LaboratorF Test Data
Sample Information
Sample Time: 1:45 pm Date Cast: December 30, 2004
Technician: Michael E. Odom
Weather Conditions: Partly cloudy
Accumulative Yards: 860
Placement Method: Pump
Sample Locations: C9/105
Placement Location See page 1
Specification Test Method
50 Max
ASTM C143
ASTM C231
ASTM C1064
ASTM C1064
ASTM C138
Age at Maximum Compresswe
Set Specimen Diameter Area Date Test Load Strength
No. iD (inches) (sq. inches) Tested (days) (lbs) (psi)
8 1 6.00 28.27 01/06/2005 7 97,170 3,440
8 2 6.00 2827 01/06/2005 7 98,540 3,480
Average 3,460
8 3 01/27/2005 28
8 4 01/27/2005 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were per[ormed in general accordance with applicable ASTM, AASHTO, or DOT test methods This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials
CONCRETE COMPRESSIVE STRENGTH TEST
· Report Number: 940413880056
Service Date: December 30, 2004
'irE racon
8901 Calperlter Frwy, Ste #100
Dallas Texas 75247
(214) 630-1010
Client: Hill & Wilkinson LTD
Attn: Charles Hoagland
800 Klein Rd Ste 100
Piano TX 75074
Report Date: January 14, 2005
Project: BCE Specialties
989 West Sandy Lake Road
Coppell, TX
Project Number: 94041388
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 1:50 pm
Supplier: Southern Star
Truck No: 844
Mix I.D. No.: 9349
Water Added Onsite Before Test:
Water Added Onsite After Test:
Field Test Data
Test
Plant: 29
Ticket No: 708441
5 Gallons
0 Gallons
Result
Slump, inches: 475
Air Content, %: N/A
Concrete Temperature, o F: 72
Ambient Temperature, o F: 77
Plastic Unit Weight, pcf: N/A
Laboratory Test Data
Sample Information
Sample Time 300pm Date Cast L, ecemee~ 30 2004
Technician: Michael E Odom
Weather Conditions: Partly cloudy
Accumulative Yards: 900
Placement Method; Pump
Sample Locations: A.5/1t 7
Placement Location: See page 1
Specification Test Method
5.0 Max
ASTM C143
ASTM C231
ASTM C1064
ASTM C1064
ASTM C138
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq, inches) Tested (days) (lbs) (psi)
9 1 600 2827 01/06/2005 7 107,140 3,790
9 2 6.00 28.27 01/06/2005 7 108,500 3,840
Average 3,820
9 3 01/27/2005 28
9 4 01/27/2005 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Michael E. Odom
Repor~ Distribution: ~ E~../,,
(1) Hill & Wilkinson LTD (1) TMBP Consulbng Engineers
(1) City of Coppell TX (1) BCE Specialties Reviewed by:
(1) City of Coppell TX sReOn ~oerr tp rDo eRSt YlviSa r~er
(1) Hardy McCulIah/MLM Architects Inc
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods This report is exclusively for the L~se of the cliem
indicated above and shall not be reproduced except in full without the written consent of our company Tesl results transnqltted l~ele~l~ are un[y apphcable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of tde properties of other 3pparef;tl~
materials