Transmittal
Date: 5 ADril 2000
To: SF?.'h=Ek, Jacobs & FiD3clea
Attn: liT. ,~ry C. Hendricks, PE
Project: CDp;_~ell 1.5 M. G.
~le,~t~l Tank
Gentlemen:
Henley-Johnston & Assoc., Inc. transmits herewith the
Paint I_nsiEtion Re.oort i~: 16939-0 (3/15/00-3/16/00)
following:
Comments:
cc; Larry Davis, City of Co?pall
Sincerely yours,
Herbert C. Cro~ler
telephone (214) 94Z.3808
fax (214) 943.7645
Henley-Johnston & Assoc.,
Project No. 7] 5]
235 Morgan Ave.. Dallas. Tcxas 75203
Inc.
· . 4305 Glenwood Ct.
Granbury, TX 76049
Client Henley Johnston & Associates
Attn: Herb Crowder
Contractor Advantage
ABRASIVE MATERIAL
Abrasive Type: Bulk blasting sand
Recycled: No Air Quality Good
Equipment
Project
Inspector
Sullair 1300 compressor; three (3) blast hoses
COATINL ,NSPECTION REPORT
Date 03-15-00 Report 16939-0
Page. 1 of I *03-16-00
Coppell 1.5 M.G. Elevated Tank
Coppell, Texas
Cindy Holmes, Certified Coating Inspector
SURFACE PREPARATION
Standard Specified SSPC-SP 10
Standard Achieved SSPC-SP 10
Profile Reading Average 4.03 mils
ENVIRONMENTAL CONDITIONS
COATING MATERIAL
Date 3/15/00 3/16/00 3/16/00 Material used Carboguard 561
Time 7:45 a.m. 11:30 a.m. 2:00 p.m. Batch No. Part A 9H0716M
Dry Bulb 68 69 81 Part B 9H0656M
Wet Bulb 49 6O 57 Part C N/A
Humidity · 20% 59% 20 Thinner #10 OA11455
Dew Point 26 54 34 Application method Airless spray (517 tip)
Surface Temp 64 70 73 Color - 1898 White
Wind Interior ENE 10 Interior
DRY FILM THICKNESS
Area Number of Low High Mean Comments
Readings
DFT gage used
Additional Information: 03-15-00 Contractor requested a preliminary inspection of the blast prior to
scheduled inspection on 03-16-00. Surfaces blasted so far include floor and up about four (4) feet on bowl. Some areas
in the ceiling are blasted also. Areas blasted up till now have some existing coatings still on the surface. These areas
need to be blasted again. A Munter's 4500 dehumidifier is on site and running. The interior temperatures reflect this.
Blasted areas do not appear to have any rust bloom present.
03-16-00 Areas presented for inspection today includes the ceiling and rafters on the south half of the tank. Areas
acceptable per SSPC-SP10 include ceiling from center rail out to about five (5) feet above wall painter's rail. Areas on
riser pipe and around roof hatch need additional blast cleaning and will not be coated today. Prior to the airless spray
application of Carboguard 561 blasted areas were blown clean with blast hose air. Airless spray application started at
3:00 p.m.