CONCRETE COMPRESSIVE STRENGTH TEST
Client:
Project:
Services:
Report No.: 226373
Project No.: 049245
Date of Service: 01/19/2005
Report Date: 01/27/2005
Duke Realty Services, LP
Mr. Brian Stmley
5495 Belt Line Rd., Ste 360
Dallas TX 75254
Freeport XI & XII/
Coppell, Texas
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
STRENGTH:
SLUMP (in):
AIR (%):
TEST METHOD:
CONTRACTOR: Duke Construction
CONCRETE SUPPLIER: Southerll Star
PLANT: 27
SPECIFICATION REQUIREMENTS
3000 psi ~ 28 Days
5" maximum
3% - 6%
ASTM C- 172
ASTM C-31
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-1231
ASTM C-39
MIX DESIGN I.D.: 7750 MEASURED
SLUMP
PLACEM, ENT DATE: 01/19/2005 (fuch~s)
WEATHER CONDITIONS: Clear 5.0
TIME SAMPLED: 3:30am BATCHTIME: 3:10am
TEMPERATURE (F) - AIR 40 F CONCRETE: 51 F
TRUCK NO: 8 TICKET NO: 763692
Am com'~Nr (%12 4.4 UNIT WEIGHT (pc0: NA
OVERALL PLACEMENT LOCATION:
Paving, east parking lot and fire lanes, Building 12, east half of noRh parking lot and fire
lanes, Building 12
SAMPLE LOCATION:
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
60' south of northeaat comer, 20'
east of east wall
CYLINDER // MAXIMUM COMPRESSIVE
MARKED DATE AA ,// ~METER AREA LOAD STRENGTH ~ FRACTURE
SET NO. TESTED ~ (inches) (sq.in.) (lbs. force) ~(Ps~"/ / TYPE
1 1 01/26/2005 k,~_,~2._99 28.17 97140 ~/ Unbonded Cap
1 2 02/16/2005 28 0.00 0.00 ~ Unbonded Cap
1 3 02/16/2005 28 0.00 0.00 Unbonded Cap
1 4 Hold
Water added at site: 5 gallons
LIMITATIONS: The test results presented herein were prepa~ based upon the specific samples provided for testing. We a~sume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feat~e of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports am for the exclusive use of the clients to whom they a~ addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01SS Page 1 of 10
Client:
Ineers
Duke Realty Services, LP
Mr. Brian Straley
5495 Belt Line Rd., Ste 360
Dallas TX 75254
Project: Freeport XI & XII
Coppell, Texas
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporato Phone: (214)630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.: 226373
Project No.: 049245
Date of Service: 01/19/2005
Report Date: 01/27/2005
Services:
Obtain samples of bosh concrete at the placement locations, perform required field testing, east compressive s~'ength samples end bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
STRENGTH:
SLUMP 0u):
AIR (%):
TEST METHOD:
CONTRACTOR: Duke Construction
CONCRETE SUPPLIER: Southern Star
PLAto': 27
SPECIFICATION REQUIREMENTS
3000 psi ~ 28 Days
5" maximum
3% - 6%
ASTM C-172
ASTM C-31 ~
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-123 !
ASTM C-39
MIX DESIGN LD.: 7750 SLUMY
PLACEMENT DATE: 01/19/2005 (inches1
WEATHER CONDITIONS: Clear 4.5
TIME SAMPLED: 4:25am BATCHTIME: 4:00am
TEMPERATURE (F) ~ AIR 41 F CONCRETE: 52 F
TRUCKNO: NA TICKET NO: 763699
Am commNT (%1:4.5 tr~rr WEIGHT (pcf}: NA
OVERALL PLACEMENT LOCATION:
Paving, ¢~t parking lot and fire lanes, Building 12, east half of narth parking lot and fire
lanes, Building 12
SAMPLE LOCATION:
REPORT OF TESTS
90' south of northeast comer, 30'
east of oust wall
Concrete Compressive Cylinder 6" x 12"
CYLINDER MAXIMUM COMPRESSIVE
MARKED DATE AGE DIAMETER AREA LOAD STRE~.~
FRACTURE
SET NO. TESTED (days) (inchez) (sq.in.) (lbs. force) fpsi) TYPE
2 1 01/26/2005 7 5.99 28.17 97580 ~ 3460 Uubonded Cap
2 2 02/16/2005 28 0.00 0.00 ~ Unbonded Cap
2 3 02/16/2005 28 0.00 0.00 Unbonded Cap
2 4 Hold
Water added at site: 5 gallons
LIMrrATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Roue Engineers, Ltd.
01SS Page 2 of 10
ineers
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76115
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Client:
Duke Realty Services, LP
Mr. Brian Straley
5495 Belt Line Rd., Ste 360
Dallas TX 75254
Project: Freeport XI & XII
Coppell, Texas
Report No.: 226373
Project No.: 049245
Date of Service: 01/19/2005
Report Date: 01/27/2005
Services:
Obtain samples of fi'esh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for cming and testing in accordance with applicable standards.
PROJECT DATA
STRENGTH:
SLUMP (in):
AIR (%):
TEST METHOD:
CONTRACTOR: Duke Construction
CONCRETE SUPPLIER: Southern Star
PLANT: 27
SPECIFICATION REQUIREMENTS
3000 psi ~ 28 Days
5" maximum
3% - 6%
ASTM C-172
ASTM C-31
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-1231
ASTM C-39
MEASURED
MIX DESIGN LD.: 7750 SLUMP
PLACEMENT DATE: 01/19/2005 (inches)
WEATHER CONDITIONS: Clear 5.0
TIME SAMPLED: 5:30am BATCH TIME: 5:09am
TEMPERATURE (F) - AIR 42 F CONCRETE: 51 F
TRVCK NO: 1815 TlC~T NO: 763709
AIR CONTENT (%): 4.5 UNIT WEIGHT (pcD: NA
OVERALL PLACEMENT LOCATION:
Paving, cast parking lot and fire lanes, Building 12, east half of north parking lot and fire
lanes, Building 12
SAMPLE LOCATION:
REPORT OF TESTS
80' north of southeast comer, 25'
east of east wall
Concrete Compressive Cylinder 6" x 12"
CYLINDER
MARKED DATE AGE DIAMETER
SET NO. TESTED (days) (inches)
MAXIMUM COMPRESSIVE
AREA LOAD STRENGTH FRACTURE
(sq.in.) (lbs. force) (psi) TYPE
3 1 01/26/2005 7 5.99 28.17
3 2 02/16/2005 28 0.00 0.00
3 3 02/16/2005 28 0.00 0.00
3 4 Hold
Water added at si~e: 5 gallons
95340 3380
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letlers and
repons are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01SS Page 3 of 10
ineers
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Client:
Duke Realty Services, LP
Mr. Brian Straley
5495 Belt Line Rd., Ste 360
Dallas TX 75254
Project: Freeport XI & XII
Coppell, Texas
Report No.: 226373
Project No.: 049245
Date of Service: 01/19/2005
Report Date: 01/27/2005
Services:
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
STRENGTH:
SLU1V~ (in):
AIR (%):
TEST METHOD:
coNTRAcrom Duke Construction
CONCRETE SUPPLIER: Southerll Star
PLAWn 27
SPECIFICATION REQUIREMENTS
3000 psi ~ 28 Days
5" maximum
3% - 6%
ASTM C-172
ASTM C-31
ASTM C- 143
ASTM C-231
ASTM C- 1064
ASTM C- 1231
ASTM C-39
MEASURED
MIX DESIGN I.D.: 7750 SLU~4P
PLACEMENT DATE: 01/19/2005 (thch~)
WEATHER CONDITIONS: Cloar 5.0
TIME SAMPLED: 6:00am BATCHTIME: 5:30all1
TEMPERATURE (F) - AIR 60 F CONCRETE: 43 F
TROCK NO: 923 TICY, ET NO: 763722
AIR CONTENT (%): 4.5 UNIT WEIGHT (pc0: NA
OVERALL PLACEMENT LOCATION:
Paving, east parking lot and fire lanes, Building 12, east half of north parking lot and fire
lanes, Building 12
SAMPLE LOCATION: See below
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
CYLINDER
MARKED
SET NO.
MAXIMUM COMPRESSIVE
DATE AGE DIAMETER AREA LOAD STRENGTH FRACTURE
TESTED (days) (inches) (sq.in.) (lbs. force) (psi) TYPE
4 I 01/26/2005
4 2 02/16/2005
4 3 02/16/2005
4 4 Hold
7 5.99 28.17 97470 3460 Unbonded Cap
28 0.00 0.00 Unbonded Cap
28 0.00 0.00 Unbonded Cap
Sample location: 10' south of north curb, east half of north parking lot, and
10' east of expansion joint at center of parking lot running north and south
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We ~ssume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our Ic~ers and
reports are for the exclusive use of the clients to whom they ~e addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
O1SS Page 4 of 10
Report No.: 226373
Project No.: 049245 Client: Duke Realty Services, LP
Water added at site: 5 gallons
LIMITATIONS: The test results presented hereto were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, ixxformance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no conlxol. Our lette~ and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
0ISS Page 5 of 10
Client:
Duke Realty Services, LP
Mr. Brian Straley
5495 Belt Line Rd., Ste 360
Dallas TX 75254
Project: Freeport XI & XII
Coppell, Texas
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.: 226373
Project No.: 049245
Date of Service: 01/19/2005
Report Date: 01/27/2005
Obtain samples of fxesh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with appIicable standards.
PROJECT DATA
STRENGTH:
SLUMP (in):
AIR (%):
TEST METHOD:
CONT~.~CrOR: Duke Construction
CONCRETE SUPPLIER: Southern Star
PLANT: 27
SPECIFICATION REQUIREMENTS
3000 psi ~ 28 Days
5" maximum
3% - 6%
ASTM C-172
ASTM C-31
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-1231
ASTM C-39
MIX DESIGN LD.: 7750 MEASURED
SLUMP
PLACEMENT DATE: 01/19/2005 (inches)
WEATHER CONDITIONS: Clear 5.0
TIMESAM~LED: 9:00am BATCHTIME: NA
TEMPERATURE (FI - AIR 49 F CONCRETE: 53 F
TaUCKNO: 923 TICm~T NO: 763730
AIR CONTENT (%): 4.6 tn~IX WEIGHT (pc/): NA
OVERALL PLACEMENT LOCATION:
Paving, east parking lot and fire lanes, Building 12, east half of north parking lot and fire
lanes, Building 12
SAMPLE LOCATION:
REPORT OF TESTS
Concre~te Compressive Cylinder 6" x 12"
See below
CYLINDER MAXIMUM COMPRESSIVE
MARKED DATE AGE DIAMETER AREA LOAD STRENGTH FRACTURE
SET NO. TESTED (days) (inches) (sq.in.) Obs. force} (psi) TYPE
5 1 01/26/2005 7 5.99 28.17 93840 3330 Unbonded Cap
5 2 02/16/2005 28 0.00 0.00 Unbonded Cap
5 3 02/16/2005 28 0.00 0.00 Unbonded Cap
5 4 Hold
Sample location: North parking lot, 35' south of north curb, 20' east of
expansion joint at center of north parking lo~ running north and south.
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01SS Page 6 of 10
Report No.: 226373 RoneEngineers
Project No.: 049245 Client: Duke Realty Services, LP III
Water added at site: 7 gallons
LIMITATIONS: The test results presented herein wen: prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appoarm~ce, performance, etc.) or any other feature of similar subject mWaer provided by persons or conditio~ over which we have no contsol. Our letters and
r~ports are for the exclusive use of the clients to whom they are addressed and shall not b~ reproduced except in full without the written approval of Rone Engineers, Ltd.
01SS Page 7 of 10
Client:
ineers
Duke Realty Services, LP
Mr. Brian Straley
5495 Belt Line Rd., Ste 360
Dallas TX 75254
Project: Freeport XI & XII
Coppell, Texas
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.: 226373
Project No.: 049245
Date of Service: 01/19/2005
Report Date: 01/27/2005
Services:
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and l~sting in accordance with applicable standards.
PROJECT DATA
STRENGTH:
SLUMP (in):
AIR (%):
TEST METHOD:
CONTRACTOR: Duke Construction
CONCRETE SUPPLIER: Southerll Star
l,l~rl': 27
SPECIFICATION REQUIREMENTS
3000 psi @ 28 Days
5" maxhnum
3% - 6%
ASTM C-172
ASTM C-31
ASTM C-143
ASTM C-231
ASTM C- 1064
ASTM C- 1231
ASTM C-39
MIX DESIGN I.D.: 7750 MEASURED
SLUMP
PLACEMENT DATE: 01/19/2005
W~Th~R CONDITIONS: Clear 4.5
TIMESAM~LED: 10:05am BATCHTIME: 9:48am
TEMPERATURE (F)- AIR 55 F CONCRETE: 53 F
TaUCK NO: 1827 TICKET NO: 763741
AIR CONTENT (%): 4.6 UNITWEIGHT(pc0: NA
OVERALL PLACEMENT LOCATION:
Paving, east parking lot and fire lanes, Building 12, east half of north parking lot and fire
lanes, Building 12
SAMPLE LOCATION:
REPORT OF TESTS
Conc~te Compressive Cylinder 6" x 12"
See below
CYLINDER MAXIMUM COMPRESSIVE
MARKED DATE AGE DIAMETER AREA LOAD STRENGTH FRACTURE
SET NO. TESTED (days) (inches) (sq.in.) Obs. force) (psi) TYPE
6 1 01/26/2005 7 5.99 28.17 79920 2840 Unbonded Cap
6 2 02/16/2005 28 0.00 0.00 Unbonded Cap
6 3 02/16/2005 28 0.00 0.00 Unbonded Cap
6 4 Hold
Sample location: North parking lot, east half, 60' north of south curb, 10' east
of expansion joint at center of north parking lot running north and south.
LIMITATIONS: The test results presented herein were prepared b~sed upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition. appearance, performance, etc.) or any other feature of similar subject mailer provided by persons or conditions over which we have no control. Our lettem and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the wriaen approval of Rone Engineers, Ltd.
01SS Page 8 of 10
Report No.: 226373 RoneEngineers
Project No.: 049245 Client: Duke Realty Services, LP
Water added at site: 20 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no cona'o[. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the wri~en approval of Rone Engineers, Ltd.
01SS Page 9 of 10
ineers
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, gte. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Client:
Duke Realty Services, LP
Mr. Brian Straley
5495 Belt Line Rd., Ste 360
Dallas TX 75254
Project: Freeport XI & XII
Coppell, Texas
Report No.: 226373
Project No.: 049245
Date of Service: 01/19/2005
Report Date: 01/27/2005
Services: Obtain samples of flesh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR: Duke Conslruction
CONCRETE SUPPLIER: Southerll Star
PI. ANT: 27
SPECIFICATION REQUIREMENTS
sx~,g~G~m: 3000 psi ~ 28 Days
SLUMP (in): 5" maximum
Am (%): 3% - 6%
TF~T METHOD: ASTM C- 172
ASTM C-31 ,~
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-1231
ASTM C-39
PROJECT DATA
MEASURED
MIX DESIGN LD.: 7750 SLUM~
rLACEMra*r DATE: 01/19/2005 (inches)
WEATHER CONDITIONS: Clear 5.0
TIME SAMPLED: 12:10pm BATCHTIME: ll:41am
TEMPERATURE (F) - AIR 59 F CONCRETE: 54 F
tRUOCNO: 8003 TICKET NO: 384441
AIR CONTEWr (%): 4.6 ~rr WEIGHT (pc0: NA
OVERALL PLACEMENT LOCATION:
Paving, east parking lot and fire lanes, Building 12, east half of north parking lot and fire
lanes, Building 12
SAMPLE LOCATION:
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
See below
CYLINDER MAXIMUM COMPRESSIVE
MARKED DATE AGE DIAMETER AREA LOAD STRENGTH FRACTURE
SET NO. TESTED (days) (inches) (sq.in.) (lbs. force) (psi) TYPE
7 1 01/26/2005 7 5.99 28.17 83640 2970 Unbonded Cap
7 2 02/16/2005 28 0.00 0.00 Unbonded Cap
7 3 02/16/2005 28 0.00 0.00 ~ Unbonded Cap
7 4 Hold
Sample location: North parking lot, 75' north of south curb, 20'~f/~
expansion joint at center of parking lot running north and south
T*chnician: Pat P~ks Sta~ed: 2:30m Finished: l:30pm R~
(0 E~ K. Sco~ Watson, ~T
(1) Ci~ of Coppell C~ Operations M~er
(1) Ci~ of Ceppell
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject maaer provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they a~ addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01SS Page 10 of 10