Solomon Dental-LR 990330CONCRETE COMPRESSIVE STRENGTH TEST 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 Date of Service: 02/25/1999 Client No.: 81986000 Report No.: 9906060 Project No.: 43-2560-98 Report Date 03/30/1999 Client: Structures & Interiors Attn: Mike Lese 2855 Exchange Blvd., Suite 300 Southlake, TX 76092 Project: Dr. Glynn Solomon Dental Off. 188 W. Parkway Blvd. Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required field test and cast compressive strength samples. STRENGTH: SLUMP: AIR: TEST METIIOD: CONTRACTOR: Structures & Interiors CONCRETE SUPPLIER: Mid-cities PLANT: N/A SPECIFICATION REQUIREMENTS 4000 psi @ 28 Days 6" Max 3-5% ASTM C-143 ASTM C-172 ASTM C-39 PROJECT DATA CONCRETE CLASS: 9355 PLACEMENT DATE: 02/25/1999 EATCt4 TIME: 3:35pm TIME SAMPLED: 4:30pm E¥: Greg Dimock WEATHER CONDITIONS: Partly cloudy TEMPERATURE (F) - AIR 72 F CONCRETE: 76 F TRUCK NO: 445 TICKET NO: 52704 AIRCONTENT(%): 4.75 UNITIVEIGHT(pcf): N/A PLACEMENT LOCATION: Paving, Approach from Parkway Road, 40' x 15% and a 6' x 15' piece of Parking Lot SAMPLE LOCATION: See note below REPORT OF TESTS ACCUMULATIVE YARDS: 10 CYLINDER MEASURED MAXIMUM COMPRESSIVE MARKED SLUMP DATE AGE LOAD STRENGTH FRACTURE SET NO. (inches) TESTED (days) (lbs. force) (psi) TYPE 1 1 5.00 03/04/1999 7 112870 3990 1 2 5.00 03/04/1999 7 117260 4150 Average 4070 1 3 5.00 03/25/1999 28 125400 4430 1 4 5.00 03/25/1999 28 119010 4210 Average 4320 NOTE: potential cold joint. Sample taken from truck 8' south of north joint, and 10' east of west curb in Approach. The 6' x 15' patch is against e×isting paving, there is no roseboard or joint in between. This is a See diagram. Technician: Greg Dimock Report Distribution: (4) Structures & Interiors ( 1 ) City of Coppell (1) City of Coppell 5:30pm [-']'~ - . ~- - nc. Started: l:00pm Finished: '" ~"~ EngI~~e'l Eugene Harbour Vice President This reprnt is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of HBC Engineering, Inc. 01TM Page 1 of 1