Solomon Dental-LR 990330CONCRETE COMPRESSIVE STRENGTH TEST
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
Date of Service: 02/25/1999
Client No.: 81986000
Report No.: 9906060
Project No.: 43-2560-98
Report Date
03/30/1999
Client: Structures & Interiors
Attn: Mike Lese
2855 Exchange Blvd., Suite 300
Southlake, TX 76092
Project: Dr. Glynn Solomon Dental Off.
188 W. Parkway Blvd.
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required field test and cast
compressive strength samples.
STRENGTH:
SLUMP:
AIR:
TEST METIIOD:
CONTRACTOR: Structures & Interiors
CONCRETE SUPPLIER: Mid-cities
PLANT: N/A
SPECIFICATION REQUIREMENTS
4000 psi @ 28 Days
6" Max
3-5%
ASTM C-143
ASTM C-172
ASTM C-39
PROJECT DATA
CONCRETE CLASS: 9355
PLACEMENT DATE: 02/25/1999 EATCt4 TIME: 3:35pm
TIME SAMPLED: 4:30pm E¥: Greg Dimock
WEATHER CONDITIONS: Partly cloudy
TEMPERATURE (F) - AIR 72 F CONCRETE: 76 F
TRUCK NO: 445 TICKET NO: 52704
AIRCONTENT(%): 4.75 UNITIVEIGHT(pcf): N/A
PLACEMENT LOCATION:
Paving, Approach from Parkway Road, 40' x 15% and a 6' x 15' piece of Parking Lot
SAMPLE LOCATION: See note below
REPORT OF TESTS
ACCUMULATIVE YARDS: 10
CYLINDER MEASURED MAXIMUM COMPRESSIVE
MARKED SLUMP DATE AGE LOAD STRENGTH FRACTURE
SET NO. (inches) TESTED (days) (lbs. force) (psi) TYPE
1 1 5.00 03/04/1999 7 112870 3990
1 2 5.00 03/04/1999 7 117260 4150
Average 4070
1 3 5.00 03/25/1999 28 125400 4430
1 4 5.00 03/25/1999 28 119010 4210
Average 4320
NOTE:
potential cold joint.
Sample taken from truck 8' south of north joint, and 10' east of
west curb in Approach. The 6' x 15' patch is against e×isting
paving, there is no roseboard or joint in between. This is a
See diagram.
Technician: Greg Dimock