SS9901-LR041123Client: Project: GEOTECHNICAL, ENVIRONMENTAL AND MATERIALS ENGINEERS DALLAS FORTWORTH HOUSTON AUSTIN LONGVIEW 1105CAbles Ln. Dallas, Texas 75229 phone: (972) 488-8800 fax(972) 488-8080 Concrete Compression Test Report City of Coppell Report Distribution: (1) City of Coppell DeForest Rd. Lift Station imp, Force Main Line "D" TMI Report No.: 74792-007 Report Date: 11/23/2004 Strength Slump Air Content Concrete Temperature Ambient Temperature Specifications 3600 psi @ 28 Days 3 in min 5in max 3%min6%max n/a n/a Test Data Placement Date 10/20/2004 Sampled By Jessie Nerios Weather Clear Supplier/Mix Beall/23011524 Air Content Method Ticket Number: Slump: Concrete Temperature: Placement Location: 13634528 Time Batched: 2:13 pm 4 in Air Content: n/a 90° F Ambient Temperature: 97° F East side at parking lot at 1101 Village Parkway Pump Station Sample Location: 70' South of Village Parkway & 50' East of building Set # Age Max Load Area Cyl#der Test Date (days) (lbs. force) (sq.in.) Time Sampled: 3:10 pm Unit Weight: n/a Yardage (c.y.): n/a Strencfth Fracture (psi~ Type I 10200401 10/27/2004 7 72550 28.27 1 10200402 11/17~004 28 106010 28.27 1 10200403 11/17/2004 28 109350 28.27 1 10200404 Hold 2570 unbonded cap 3750 unbonded cap 3870 unbonded cap 28 day average 3810 Normal cylinder size: 6" x 12" Field and laboratory tests by TMI are per applicable ASTM Standards: C31. C39, C138, C143, C172, C1064, and C617 or C1231. TERRA-MAR, INC. The results presented in this report pertain only to the specific items tested. This report was produced for the exclusive use of the client. Any reproduction of this report, or any part therein, is strictly prohibited without the express written consent of TML OmSD Page 1 of[