SS9901-CS050103TurnerCollie Braden Inc. TRANSMITTAL
To:
From:
Date:
Job No.:
Subject:
See Distribution
Erika K. Cooper,"P.E. - TCB
January 3, 2005
052 131124.0001 04000.A123 (2.1)
Deforest and Sandy Lake Wastewater Lift Stations and Force Main Improvements
DeForest & Sandy Lake Wastewater Lift Stations
Shop Drawing Review Comments
Submittal No. 04-44-001A Rev 1 (Pump Clarification)
Submittal No. 04-44-0017A (Raven Coating)
Submittal No. 04-44-0018A (Parshall Flume)
Submittal No. 04-44-0019A (Access Hatches and Neenah)
TCB has the following comments on these submittals:
Description Status Comment
Pump Clarification No Exception Taken
Raven Coating Make Corrections Noted · Note that thicknesses shown in "Coating
Procedures for Raven 405" are average
thicknesses
· Perform any necessary repairs prior to
coating application in accordance with
Specification Section 09902
Parshall Flume Submit Specified Items · Submit flow data for 18" Parshall Flume
(data provided is for 18" Palmer-
Bowlus Flume)
· Provide precast concrete manhole grade
rings and manhole frame and cover (H-
20 rated) per precast manhole detail
(Sheet SD-21) in City of Coppell
Standard Construction Details
Access Hatches and Rejected · Hatch must be Bilco Type K Single
Neenah Leaf per Detail 4 on Sheet SS-1
· Verify openings for Neenah covers in
field
When you re-submit the shop drawings, please address all comments and submit eight (8) copies to
this office.
Distribution:
[X] 2 copies of submittal to the City
[X] 4 copies of submittal to Can-Fer Construction Company, Inc.
[X] 2 copies of submittal to TCB file
[ ] Other