SS9901-CS041216Turner Collie(__ Braden Inc. TRANSMITTAL
To:
From:
Date:
Job No.:
Subject:
See Distribution
EnkaK. Cooper, P.E. TCB
December 16, 2004
052 131124.0001 04000.A123 (2.1)
Deforest and Sandy Lake Wastewater Lift Stations and Force Main Improvements
DeForest & Sandy Lake Wastewater Lift Stations
Shop Drawing Review Comments
Submittal No. 04-44-006A (Grating)
Submittal No. 04-44-007A (Misc. Metals)
Submittal No. 04-44-008A (Misc. Metal Drawings)
Submittal No. 04-44-01 lA (Tress Calculations)
Submittal No. 04-44-013A (Class Ksp Concrete)
TCB has the lbllowing comments on these submittals:
Description Status Comment
Grating No Exception Taken
Misc. Metals Make Corrections Noted * Provide clips to hold grating in place
per Sections A and B on Sheet SS-2, or
provide clamp clips as recommended by
the grating manufacturer.
· Field verify opening dimensions.
Misc. Metal Drawings No Exception Taken · Field verify size and location for
existing duct.
· Coordinate size and location for odor
control duct with odor control
equipment manufacturer.
Truss Calculations Not Required for Approval · File copy retained.
Class Ksp Concrete No Exception Taken ° HRWR admixture submittal to be
submitted separately.
When you re-submit thc shop drawings, please address all comments and submit eight (8) copies to
this office.