SS9901-CS041130Turner Collie _ Braden Inc.
To:
From:
Date:
Job No.:
Subject:
See Distribution
Enka K. Cooper, P.E. TCB
November 30, 2004
052 131124.0001 04000.A123 (2.1)
Deforest and Sandy Lake Wastewater Lift Stations and Force Main Improvements
DeForest & Sandy Lake Wastewater Lift Stations
Shop Drawing Review Comments
Submittal No. 08710-0 (Door Hardware Cut Sheets)
Submittal No. 04810-0 (Masonry)
TCB has the following comments on these submittals:
Description Status Comment
Door Hardware Cut Rejected · Heavy weight hinges are required per
Sheets Spec 08711, Paragraph 2.02.E. 1
· Stainless steel hinges are required per
Spec 08711, Paragraph 2.02.F.
· Proposed Iockset manufacturer is not an
approved manufacturer
· Panic threshold maximum height is
1/2", proposed shows 7/8".
Masonry Make Corrections Noted · Provide CAVITY MATE Ultra
insulation to meet the requirements of
Spec 04810, Paragraph 2.11.A.
· General Contractor shall verify the wall
tie type.
When you re-submit the shop drawings, please address all comments and submit eight (8) copies to
this office.
Distribution:
[X] 2 copies of submittal to the City
[X] 4 copies of submittal to Can-Fer Construction Company, Inc.
IX] 2 copies of submittal to TCB file
[ ] Other
12/8/04 1 / 1 P iCoppelliD F SILLS Corot/Con es\Shop Dwg Trans 2004 12 08 doc