Loading...
SS9901-CS041130Turner Collie _ Braden Inc. To: From: Date: Job No.: Subject: See Distribution Enka K. Cooper, P.E. TCB November 30, 2004 052 131124.0001 04000.A123 (2.1) Deforest and Sandy Lake Wastewater Lift Stations and Force Main Improvements DeForest & Sandy Lake Wastewater Lift Stations Shop Drawing Review Comments Submittal No. 08710-0 (Door Hardware Cut Sheets) Submittal No. 04810-0 (Masonry) TCB has the following comments on these submittals: Description Status Comment Door Hardware Cut Rejected · Heavy weight hinges are required per Sheets Spec 08711, Paragraph 2.02.E. 1 · Stainless steel hinges are required per Spec 08711, Paragraph 2.02.F. · Proposed Iockset manufacturer is not an approved manufacturer · Panic threshold maximum height is 1/2", proposed shows 7/8". Masonry Make Corrections Noted · Provide CAVITY MATE Ultra insulation to meet the requirements of Spec 04810, Paragraph 2.11.A. · General Contractor shall verify the wall tie type. When you re-submit the shop drawings, please address all comments and submit eight (8) copies to this office. Distribution: [X] 2 copies of submittal to the City [X] 4 copies of submittal to Can-Fer Construction Company, Inc. IX] 2 copies of submittal to TCB file [ ] Other 12/8/04 1 / 1 P iCoppelliD F SILLS Corot/Con es\Shop Dwg Trans 2004 12 08 doc