SS9901-SP050222 (6)PROJECT:
MECHANICAL ENGINEER:
MECHANICAL CONTRACTOR:
INDEECO
ST. LOUIS, MISSOURI
ELECTRIC UNIT HEATERS
SUBMITTAL DATA
Sandy Lake Wastewater Lift Station
Coppell, Texas
Turner, Collie, & Braden, Inc.
Dallas, Texas
Professional Services
Desoto, Texas
Qty. 5-
EQUIPMENT SUMMARY
Indeeco company "Ultra-Safe" Explosion resistant unit heaters
complete with ceiling mounting bracket, and built in thermostat as
noted on Sheets SM-6 and SM-7
Tag: (3) 7.5 KW, (2) 5.0 KW
Notes:
1) Disconnect switches are not included.
urner Co tie' O'Bi ack
Revise & Resubmit
C. RcjecteC
SUBMITTED BY:
BARTOS INDUSTRIES, LTD.
10350 OLYMPIC DR.
DALLAS, TX 75220
PH. (214) 350-6871
FAX (2t4) 350-348t
RANDY WIECKER
FEBRUARY 9, 2005
xplosion-proof Untt Heater
FM and CSA Approved for:
Classes land Il
Divisions ,1,and 2
Groups C, D.E. Fand G
Safety and Versatility
IND£ECO's ULTRA-SAFETM Explosion-proof
Unit Heater product line is designed with
both safety and versatility in mind. Unique
ULTRA-SAFETM construction features include:
· Industry's Lowest Ignition Temperature
Code Rating: T3C, 320°F (160°C)
· Group C Rating
· Redundant Overtemperature Protection:
Dual automatic reset thermal cutouts for
additional safety.
· Nontoxic Propy[ene Glycol Heat Transfer
Fluid: Other heat exchanger designs use
toxic ethylene g~ycol as their standard heat
transfer fluid.
· Low 70 PSIG Relief Valve Setting: This
assures that in an emergency, the initial
escaping vapor temperature remains below
the 320°F (~.60°C) ignition temperature.
Other heat exchanger designs are rated
up to 200 psig that result in temperatures
of 380°F (193°C).
· More Options: INDEECO offers a wide
variety of options and special features tn
reduce the installed cost and meet your
unique application requirements.
Standard Construction
Heat Exchanger- is an efficient liquid-to-air
design utilizing a copper tube core with
integral a[uminum fins. Industria[ grade
IND£ECO heating elements are immersed in
a nontoxic, inhibited, propytene glycol heat
transfer fluid that provides freeze protection
down to -49°F (-45%). The heat exchanger
is hydrostatically tested at 350 psig. A
pressure relief valve provides excess
pressure protection and is set at 70 psig.
Standard Fan Motor Assembly- consists
of an explosion-proof motor fitted with an
aluminum fan blade. The motor has double*
shielded, permanently lubricated ball bearings
and automatic reset line breaking thermal
overload protection. Motors furnished on
standard units operate at line voltage and
are prewired to the control enclosure so
separate field wiring to the motor is not
required. The standard motor is rated for
Class I, Groups C and D, Class II, Groups F
and G. The minimum operating temperature
is -'14°F (-25°0 and the minimum storage
temperature is -49°F (-45°C). Optional motor
ratings are described on page 7.
Cabinet/Louvers - are an industrial grade,
corrosion resistant construction fabricated
from powder coated ~.4 gauge steel. The
adiustable louvers have minimum opening
safety stops.
Controls - are factory mounted on the unit
heater. Standard built-in controls include
dual (redundant) automatic reset overtemper-
ature cutouts, controlling magnetic contactor,
24 Volt control circuit transformer and
incoming power terminal blocks.
Explosion-proof Unit Heater
Assembly Stock Control Options
i~ ~Iop :: ~ / Oescr pttoh Code
Factory installed and prewired to the control enclosure.
Adjustable Thermostat T
Thermostat is adjustable from 50° to 90°F (~.0° to 30°C) range.
Factory installed on the unit heater beside the control enclosure.
Disconnect Switch This is an inexpensive and positive way to meet NEC/CEC requirements D
for a disconnecting means within sight of the heater.
A two-position switch wired to the control circuit for auto (automatic
Auto/Fan heat) and fan only control. This selector switch cannot be provided S
Selector Switch if option Code M is also specified.
Manual Reset This can be added to the built-in control package for triple N
Thermal Cutout overtemperature protection.
This provides both triple overtemperature protection and a
Manual Reset completely independent safety system since the backup contactor M
Thermal Cutout with is only controlled by the manual reset cutout. This option cannot
Backup Contactor be provided if option Code S is also specified.
"Heater On" Pilot Light Indicates when the electric heating elements are energized. L
Indicates when the thermal cutouts have tripped and the unit heater K
"Warning" Pilot Light needs servicing.
This can be provided when required for special external V
120 Volt Control Circuit thermostat circuit.
Custom Options
· Epoxy-coated them-duty motor, which has passed the
ASTM 8117 salt-spray test and is rated for outdoor use.
· Corrosion resistant iddite-coated heat exchanger.
Epoxy-coated fan blade, terminal box, and wiring conduit/fittings.
Dirty Duty Corrosion
Resistant Construction · Stainless steel hardware. C
· NEMA 4X, 7, 9 (outdoor/corrosion resistant) terminal box. Epoxy-
coated built-on thermostat, disconnect switch, and selector switch
options can also be supplied for corrosion resistant applications,
but these built-on controls are not rated for outdoor use.
50 Hz Motor Optional motors for international requirements. H
Available for locations classified as hazardous due to the
Group E (Metal Dust) presence of metal dust. The motor and heater wilt be rated for
E
Construction Classes I and II, Divisions 1 and 2, Groups D, E, F and G, ignition
temperature code T3C, 320 F (160 C).
Available for operating temperatures down to -40 F (-40 C). A
Arctic Duty Motor Consult factory.
.xPl i°P Pr°°f U nit Heater
Accessory Items
ULTRA-SAFETM Heater Mounting Kits
These are available for ceiling, wall and pole
mounting configurations as described below.
Specify type required and catalog number
5" (13 cm)
///.//////////////~
Ceiling Mounting Kit
(13 cm)
(5 cra)
Wall Mounting Kit
Pole Mounting Kit
ULTRA-SAFETM Mounting Kit Catalog Numbers
1 K100-001 K100-002 K100-005
2 KIO0-O01 K'I-O0-O03 K100-006
3 K100-001 K100-004 K100-007
Remote Room Thermostat - Catalog Number 1007002
· Used with all INDEECO explosion-proof
heater designs
· Shipped separately for field installation
· 50° to 90°F (1-O° to 30°C) range
· UL Listed and CSA Certified for
Class I, Groups C and D and
Class II, Groups E, Fand G
· Overall dimensions:
6~/8'' (16.2 em) W x 5%" (14.3 cm) H
x 4Y8" (11.1 cra) D
· Electrical Ratings:
22 amps at 125 - 277VAC
% HP at '125 VAC
1y~ HP at 250/277 VAC
· Available from stock
ExpLosion-proof Unit Heater
Dimensions, Airflows and Weights
KW,Range 3~V ~5,~I~OKW I$'KW I 20KW 25KW: ·
Overall "X" Inch (em) 21~ (55) 22~ (58) 22~ (58)
Heater "Y" Inch (cm) 25 (64) 29 (74) 36 (91)
Dimensions "Z" Inch (em) 21 (53) 24¼ (62) 29 (74)
Mounting "ML" Inch (cra) 2~'~ (6) 1~ (5) 1¥2 (4)
Hole "MD" Inch (cra) 7 (18) 7 (18) 7 (18)
Dimensions "MH" Inch (em) 13 (33) 17y2 (45) 22 (56)
Air Volume CFM 700 800 1230 1825 2735
(cubic meters/hr.) (1189) (1360) (2089) (3101) (4647)
Air\ow Air Throw Feet (m) 15 (5) 20 (6) 33 (10) 49 (15) 73 (22)
Characteristics
Outtet Velocity FPM 668 1019 1564 2324 3482
(meters/min.) (204) (311) (477) (708) (1061)
RPM 1725 1725 1140 1725 1140
HP 1/2 1/2 1/3 1/2 3/4
Motor/Fan
Fan Blade Dia.
Inch (cra) 12 (31) 16 (41) 20 (51)
Weight Net Lbs (kgs) 170 (77) 206 (93) 264 (120)
Shipping Lbs (kgs) 190 (86) 225 (102) 290 (132)
Side View
\
\
\
ML~
¥
Front View
How to Order
Specify:
'J.. Catalog Number- select from ULTRA-
SAFETM catalog heater listing on page !0.
2. KW, Voltage, Phase, Ignition Temperature
Code-select from catalog heater [isting
on page 10, or consult factory for non*
standard ratings.
3. Options- specify the option code letter-
see page 7.
4. Accessory Items:
· Must specify mounting kit type and
Catalog Number at time of order entry -
see page 8.
· Room thermostat (if required) -
see page 8.
9
Heater
ULTRA-SAFE'" Unit Heater Listing'
Temperature Code T3C, 320° (160°)
208 I 20 14 (8) 237-F24U-O036C S
240 1 17.4 14 (8) 237-F24U-OO36J AS
208 3 11.1 14 (8) 237-F24U-OO36D C
3 240 3 9.7 1/4 (8) 237-F24U-OO36K C
/480 3 4.8 14 (8) 237-F2/4U-OO36U S
600 3 3.9 1/4 (8) 237-F24U-OO36Z C
:2O8 I 29.9 23 (10) 237-F2/4U-O056C C
~.- 240 I 25.9 23 (10) 237-F24U-OO56J C
208 3 16.8 23 (10) 237-F24U-OO56D C
480 3 7.3 23 (10) 237-F24U-OO56U S
3 s.9 (10) 237- 2/4u-00 62c
~ 240 I 36.7 30 (17) 237-F24U-OO86J C
7.5
240 3 20.8 30 (17)
C
480 3 10.4 30 (17) 237-F24U-OO86U S
600 3 8.3 30 (17) 237-F24U-O086Z C
240 I 47./4 40 (22) 237-F24U-O106J C
208 3 31.1 40 (22) 237-F24U-OlO6D C
480 3 13.5 40 (22) 237-F24U-0106U S
600 3 10.8 40 (22) 237-F2/4U-OlO6Z C
208 3 44.7 40 (22) 237-F24V-O156D C
240 3 38.8 40 (22) 237-F24V-OiS6K C
i~i!i! 15
480 3 19.4 40 (22) 237-F24V-O156U S
20 600 3 20.7 35 (19) 237-F24V-0206Z C
480 3 32.6 30 (17) 237-F24W-O256U AS
25
600 3 26.1 30 (17) 237-F24W-O256Z C
480 3 38.8 35 (19) 237-F24W-O306U S
30
600 3 31 35 (19) 237-F24W-O306Z C
(1) Total Amps = Heating Element Amps and Motor Amps
(2) AYallability Code: S = Stock, AS = Assembly Stock, C = Custom
(3) Stock heaters o~dered with assembly stock or custom options subject to longer delivery.
Assembly Stock heater~ ordered with custom options subiect to longer delivery.
Explosion-proof Unit Heater
Sample Specification
A specification can be prepared by using the following information. A check box has been supplied
so that you may mark those selections which you require, Material which is part of the standard
ULTRA-SAFETM Explosion-proof Unit Heater specification has already been checked,
~' 1. Electric explosion-proof unit heaters shall be INDEECO ULTRA*SAFETM 5ERIES, of the KW
rating, voltage and phase specified in the schedule, They shall be forced fan type, Factory
Mutual and CSA Approved for:
[~* Class I, Divisions 1 and 2, Groups C and D; Class II, Divisions 1 and 2, Groups F and G
Ignition Temperature Code No. T3C, 320°F 0.60°C) (Standard construction)
0 Class I, Divisions `1 and 2, Group D; Class fi, Divisions 3. and 2, Groups E, F and G
Ignition Temperature Code No. T3C, 320°F (~-60°C) (Group E, Metal Dust Motor)
Q Class I, Divisions ~- and 2, Group D
Ignition Temperature Code No. T2B, 500°F (260°C) (Arctic Duty Motor)
~ 2. Unit heaters shall have dual automatic reset thermal cutouts for redundant overtemperature
protection, controlling magnetic contactor and 2,3 volt control circuit transformer housed in
a NEMA 7, 9 cast aluminum enclosure.
~" 3, The heat exchanger shall be liquid*to-air design, utilizing a copper tube core with integral
aluminum fins. Nontoxic, inhibited, propylene glycol heat transfer fluid shall be used that
provides freeze protection down to -49°F (-45°C). Pressure relief valve setting to be 70 psig,
The heat exchanger shall include industrial grade INDEECO electric heating elements,
I~ 4. Heat exchanger and aluminum fan blade to be enclosed in an industrial grade, corrosion
resistant cabinet fabricated from powder coated, 1.4 gauge steel, Adjustable outlet louvers
to have minimum opening safety stops.
· l' 5. Fan motor shall include permanently lubricated ball bearings and built-in thermal overload
protection. Motor to operate at line voltage and be prewired to the control enclosure to
eliminate the need for separate field wiring to the motor.
I~' 6. The heater shall be provided with an I NDEECO accessory mounting kit designed to bear
the weight of the heater assembly (check one):
~eillng mounting kit 0 Wall mounting kit ~1 Pole mounting kit
~ 7. Dirty Duty Corrosion Resistant Construction with epoxy-coated chem*duty motor;
iridite-coated heat exchanger; epoxy-coated fan blade; NEMA 4X, 7, 9 terminal box,
conduit and fittings; stainless steel hardware.
r~ 8. The following factory installed and prewired control options are to be supplied;
~l~'Adjustable built-in thermostat
rt Disconnect switch with external handle
r~ Manual reset thermal cutout for triple overtemperature protection
I~ Manual reset thermal cutout with backup contactor (cannot be provided if selector
switch is also specified)
0Two*position auto/fan selector switch for fan only control (cannot be provided
if manual reset cutout with backup contactor is also specified)
~3'120 volt control circuit for special external thermostat circuit
ri "Heater On" pilot light to indicate when heating elements are energized
I~ "Warning" pilot light to indicate when thermal cutouts have tripped and heater
needs to be serviced
~ 9. The following optional motors are to be installed and prewired to the control enclosure:
~1 50 Hertz for international requirements
r3 Class II Group E metal dust location (use section '1, second check block)
~1 Arctic duty for-40°F (-40°C) operation (use section '1, third check block)
(~ '10. Accessory room thermostat shall be furnished with each heater for remote field mounting.
Thermostat to be UL Listed and CSA Certified for Classes I, II, Groups C, D, E, F and G.