SS9901-CS050222Turner Collie Braden lnc TRANSMITTAL
To:
From:
Date:
Job No.:
Subject:
See Distribution
Erika K. Cooper, P.E. - TCB
February 22, 2005
052 131124.0001 04000.A123 (2.1)
Deforest and Sandy Lake Wastewater Lift Stations and Force Main Improvements
DeForest & Sandy Lake Wastewater Lift Stations
Shop Drawing Review Comments
Submittal No. 04-44-037A (DeForest Exhaust Fan)
Submittal No. 04-44-038A (DeForest Wall Louver)
Submittal No. 04-44-039A (Electric Unit Heaters)
Submittal No. 04-44-040A (Vibration Isolators)
Submittal No. 04-44-041A (Sandy Lake Exhaust & Supply Fans)
Submittal No. 04-44-042A (Drum Scrubber Sandy Lake)
Submittal No. 04-44-043A (Passive Dram Scrubber Sandy Lake)
Submittal No. 04-44-044A (Drum Scrubber DeForest)
Submittal No. 04-44-045A (Passive Drum Scrubber DeForest)
Submittal No. 04-44-046A (Dampproofing)
TCB has the following comments on these submittals:
~ Description Status Comment
DeForest Exhaust Fan No Exception Taken
DeForest Wall Louver No Exception Taken
Electric Unit Heaters No Exception Taken
Vibration Isolators Make Corrections Noted * Confirm isolation rails are sized to
match the weights of the fans
Sandy Lake Exhaust & Make Corrections Noted · Gravity intake needs to provide 300 cfm
Supply Fans
Drum Scrubber Sandy Make Corrections Noted · Spec 11312 requires 450 lb Odorcarb II
Lake in the passive scrubber and 400 lb
Odormix in the powered scrubber
· Submittal shows 450 lb Odorcarb II and
450 lb Odorufix in each scrubber unit
Passive Drum Scrubber Make Corrections Noted · Spec 11312 requires 450 lb Odorcarb II
Sandy Lake in the passive scrubber and 400 lb
Odormix in the powered scrubber
· Submittal shows 450 lb Odorcarb II and
450 lb Odormix in each scrubber unit
Drum Scrubber Make Corrections Noted · Spec 11312 requires 450 lb Odorcarb II
DeForest in the passive scrubber and 400 lb
Odormix in the powered scrubber
· Submittal shows 450 lb Odorcarb II and
450 lb Odormix in each scrubber unit
2/22/05 1/2 p/CoppelI/DF.SL/LS Const/Cor'es~Shop Dwg Trans 2005 02 22 doc
DeForest and Sandy Lake Waste~vater Lifl Stations
02/22,/05
Page 2
Description Status Comment
Passive Drum Scrubb~ Make Corrections Noted · Spec 11312 requires 450 lb Odorcarb II
DeForest in the passive scrubber and 400 lb
Odormix in the powered scrubber
· Submittal shows 450 lb Odorcarb II and
450 lb Odormix in each scrubber unit
Dampproofing No Exception Taken
When you re-submit the shop drawings, please address all comments and submit eight (8) copies to
this office.
Distribution:
IX] 2 copies of submittal to the City
[X] 4 copies of submittal to Can-Fer Construction Company, Inc.
[X] 2 copies of submittal to TCB file
[ ] Other
p \Coppell\DF S[/LS Coast\Cortes/Shop Dwg Tran$ 2005 02 22doc