Four Seasons 2R-LR050314CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94041388.0073
Service Date: February 11,2005
Client: Hill & Wilkinson LTD
Attn: Chades Hoagland
800 Klein Rd Ste 100
Piano TX 75074
'il'erracan
8901 Carpenter Fr~Ny, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: March 14, 2005
Project: BCE Specialties
989 West Sandy Lake Road
Coppell, TX
Project Number: 94041388
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 4:10 am Plant: 27
Supplier: Southern Star
Truck No: 923 Ticket No: 782586
Mix i.D. No.: 7752
Water Added Onsite Before Test: 0 Gallons
Water Added Onsite After Test: 0 Gallons
Sample Information
Sample Time: 5:05 am Date Cast: Februar~ 11, 2005
Technician: Michael E. Odom
Weather Conditions: Cloudy
Accumulative Yards: 100
Placement Method: Pump
Sample Locations: Adjacent to Grid 8
Placement Location: Rear Fire Lane Slab-on-Grade from Grid 7
to 12
Field Test Data
Test
Result
Slump, inches: 6.00
Air Content, %: 6.8
Concrete Temperature,O F: 62
Ambient Temperature, o F: 46
Plastic Unit Weight, pcf: 142.4
Laboratory Test Data
Set specimen Diameter Area
No. ID (inches) (sq. inches)
1 1 6.00 28.27
1 2 6.00 28.27
1 3 6.00 28.27
1 4 6.00 28.27
Specification Test Method
5.0 Max ASTM C143
3-6 ASTM C231
- 95 ASTM C1064
ASTM C1064
ASTM Cl 38
Age at Maximum Compressive
Date Test Load Strength
Tested (days) (lbs) (psi)
02/18/2005 7 109,020 3,880
02/18/2005 7 105,090 ~...,.,.~720
Average 3,790
03/11/2005 28 135,960 4,810
03/11/2005 28 133,560 ~ 4,727~.~
Average ~'4~,770
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the ciient
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
rnaterials.
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94041388.0073
Service Date: February 11~ 2005
Client: Hill & Wilkinson LTD
Attn: Charles Hoagland
800 Klein Rd Ste 100
Piano TX 75074
lrerracan
8901 Carpenter Frw¥, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: March 14, 2005
Project: BCE Specialties
989 West Sandy Lake Road
Coppell, TX
ProJect Number: 94041388
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 5:30 am Plant: 27
Supplier: Southern Star
Truck No: 923 Ticket No: 782595
Mix I.D. No.: 7752
Water Added Onsite Before Test: 10 Gallons
Water Added Onsite After Test: 0 Gallons
Field Test Data
Test Result
Slump, inches: 6.25
Air Content, %: 4.7
Concrete Temperature,O F: 58
Ambient Temperature, o F: 45
Plastic Unit Weight, pcf: 145.6
Laboratorl/ Test Data
Sample Information
sample Time: 6:45 am Date Cast: February 11,2005
Technician: Michael E. Odom
Weather Conditions: Cloudy
Accumulative Yards: 130
Placement Method: Pump
Sample Locations: Adjacent to Grid 11.5
Placement Location: See page 1
Specification
Test Method
5.0 Max ASTM C143
3-6 ASTM C231
- 95 ASTM C1064
ASTM C1064
ASTM Cl 38
Set Specimen Diameter Area Date
No. ID (inches) (sq. inches) Tested
2 1 6.00 28.27 02/18/2005
2 2 6.00 28.27 02/18/2005
2 3 6.00 28.27 03/11/2005
2 4 6.00 28.27 03/11/2005
Age at Maximum Compressive
Test Load Strength
(days) (lbs) (psi)
7 112,400 3,970
7 114,520 4,050
Average 4,010
28 136,860 ~ 4,840
28 130,990 ~
Average 4,740
Services- Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Michael E. Odom
Report Distribution:
(1) Hill & Wilkinson LTD (1) City of Coppetl TX
(1) Hardy McCullah~MLM Architects Inc (1) BCE Specialties Reviewed by:
(1) TMBP Consulting Engineers
(1) City of Coppell TX Senior Project M ager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in ful~ without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the lesation(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.