Coppell Trade-LR050324 (2)FIELD DENSITY TESTING
Report Number: 94051081.0013
Service Date: March 14, 2005
'lrerracan
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client: Coppell Trade Center LP
Attn: Al Sorrels
5055 Keller Springs Rd Ste 300
Addison TX 75001
Report Date: March 24, 2005
Project: Coppell Trade Center
NWC Sandy Lake & State St
Coppell, TX
Project Number: 94051081
Material Information
Material Laboratory
No. Test Method
Description and Classification
Lab Test Data Project Requirements
Optimum Max. Lab Water
Water Dry Unit Content Minimum Dry
Content Weight Range Unit Weight
(%) (pcf) (%) (% compaction)
1. 510810002 ASTM D 698 Dark reddish browe sandy clay 15~2 106.2 >/= Opt. 95
2. 510810001 ASTM D 698 Light brown & brown clay w/sand &graveI 19.8 101.6 >/= Opt. 95
3. 510810005 ASTM D 698 Light brown silty clay w/gravel 15.4 109.8 >/= Opt. 95
Field Test Data Probe Water Dry Unit Dry Unit
Test Lift/ Mat. Depth Content Weight Weight
No. Test Location Elevation No. (inches) (%) (pct} (% compaction)
Building C, See Attached Sketch
1 75' SE from NW corner 13.5' BFG 2 6 20.5 96.2 95
2 100' E & 75' S from NW corner 13' BFG 1 6 15.9 101.4 95
3 100' E & 50' S from NW corner 12.5' BFG 3 6 15.8 106.4 97
4 50' E & 75' W from NW corner 13' BFG 1 6 19.7 102.8 97
5 100' E & 100' S from NW corner 12.5' BFG 3 6 15.7 106.5 97
6 75' SE from NW corner 13' BFG 3 6 16.2 106.3 97
Datum: BFG = Below final grade
Comments:
Test results on this report meet project specification.
Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture
condition.
Field Test Method:ASTM D2922, ASTM D3017
Gauge ID: 32769
Technician: Michael E. Odom
Field Results Repoded To: Charlie and Tyler w/Metroplex
(1) Coppell Trade Centel LP (1) Merriman Assoc Inc
(1) Pritchard Associates Inc Reviewed by:
(1) City of Coppell TX R rt D. Raj, S.E.Tf
(1) City of Coppell TX Senior Project Man r
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods This repod is exclusively for the us~hent
indicated above and shall not be reproduced except in full without the written consent of our company Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials
Page 1 of 1 , ,,,,
03/1 O/2OO5
F2+21' ~' ;'F4+75
C0+89
C2 ,~ 36 -
C2445
C0+49 F1+88
F1+75 F3+19 F4+63
F6+22;'-
FO+41
F0+14 C2+32'
.- F3+23 'z
:1+95 F1+31 ' C1+55
F2+93 F1 +47 C1 +09
C44 36
;C5+!
~C3 ~ 01 /
F3+15 F2+67 F1+72
F2+46 F1 +62
C0+28
334-88
100 Foot Grid
0 150 300
Cuts & Fills After Stripping to Proposed Subgrade Elevation
?q55'/0¢l, ¢0 l$