Four Seasons 2R-LR050509CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94041388.0102
Service Date: April 7, 2005
'll'erracan
8901 Carpenter F~,vy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client; Hill & Wilkinson LTD
Attn: Charles Hoagland
800 Klein Rd Ste 100
Piano TX 75074
Report Date: May 09, 2005
Project: BCE Specialties
989 West Sandy Lake Road
Coppell, TX
Material Information
Project Number: 94041388
Sample information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 3:00 am Plant: 27
Supplier: Southern Star
Truck No: 8
Mix I.D. No.: 7752
Water Added Onsite Before Test:
Water Added Onsite After Test:
Field Test Data
Test
Ticket No: 773742
0 Gallons
0 Gallons
Result
Slump, inches: 5,50
Air Content, %: 0,4
Concrete Temperature, o F: 70
Ambient Temperature, o F: 52
Plastic Unit Weight, pcf:
Laboratorv Test Data
Sample Time: 3:25 am Date Cast: April 7, 2005
Technician: Terry Smith Insp/Testing
Weather Conditions: Cloudy
Accumulative Yards: 30
Placement Method: Direct Discharge
Sample Locations: 20' E & 60' S of NW corner of bldg,
Placement Location: Paving around perimeter of bldg,
Specification Test Method
3-5 ASTM C143
3-7 ASTM C231
ASTM C1064
ASTM C1064
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. iD (inches) (sq. inches) Tested (days) (lbs) (psi)
1 1 6.00 28.27 04/14/2005 7 127,160 4,500
1 2 600 28,27 05/05/2005 28 156,610 5,540
1 3 6.00 28.27 05/05/2005 28 160,760 5,690
Average 5,620
1 4 Hold
Comments: Not tested for plastic unit weight. .~...-~ "'"~
Services - Obtain samples of fresh concrete at t..f.fl~lYc~em~t locations, perform required field tests and cast compressive
strength samples. .~' i . ~/,
The tests were performed in general accordance with applJcab e ASTM, AASHTO, or DOT test methods This report is exclusively for the use of the client
indicated above and shari not be reproduced except in full without the written consent of our company Test resutts transmitted herein are only applicable
to the actual samples tested at the location(s) reCerenced and are not necessarily indicative of the properties of other apparently similar or identical
materials
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94041388.0102
Service Date: April 7, 2005
'll'erracon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client: Hill & Wilkinson LTD
Attn: Charles Hoagland
800 Klein Rd Ste 100
Piano TX 75074
Report Date: May 09, 2005
Project: BCE Specialties
989 West Sandy Lake Road
Coppell, TX
Project Number: 94041368
Material information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 3:55 am Plant: 27
Supplier: Southern Star
Truck No: 648
Mix I.D. No.: 7752
Field Test Data
Test
Result
Slump, inches: 4.50
Air Content, %: 5.5
Concrete Temperature, o F: 72
Ambient Temperature, o F: 53
Plastic Unit Weight, pcf:
Laboratori/ Test Data
Ticket No: 773750
Sample Information
Sample Time: 4:30 am Date Cast: April 7, 2005
Technician: Terry Smith Insp/Testing
Weather Conditions: Cloudy
Accumulative Yards: 110
Placement Method: Direct Discharge
Sample Locations: 40' S & 8' E of NE corner of bldg.
Placement Location: See page I
Specification
Test Method
3-5 ASTM C143
3-7 ASTM C231
ASTM C1064
ASTM C1064
Set Specimen Diameter Area Date
No. ID (inches) (sq. inches) Tested
2 1 6.00 28.27 04/14/2005
2 2 6.00 28.27 05/05/2005
2 3 6.00 28.27 05/05/2005
2 4
Age at Maximum Compressive
Test Load Strength
(days) (lbs) (psi)
7 126,960 4,490
28 167,690 5,930
28 161,290 5,700
Average 5,820
Hold
Comments: Not tested for plastic unit weight.
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with app cab e ASTM AASHTO, or DOT test methods This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials
Page 2 of 3
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94041388.0087
Service Date: March 10, 2005
Client: Hill & Wilkinson LTD
Attn: Charles HoagLand
800 Klein Rd Ste 100
Piano TX 75074
'lrerracan
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report l~: May 09, 2005
p r oj e c.~.~C E S p eci a It~e~
98"g'~c~5~ndy Lake Road
Coppell, TX
Project Number: 94041388
Material Information Sample Information
Specified Strength: 4000 psi @ 28 Days Sample Time: 8:30 am Date Cast: March 10, 2005
Technician: Charles A. Patterson
Batch Time: 7:50 am Plant: 27 Weather Conditions: Sunny, windy
Supplier: Southern Star Accumulative Yards: 20
Truck No: 0031 Ticket No: 764502 Placement Method: Pump
Mix hD No.: 7752 Sample Locations: See attached sketch
Water Added Onsite Before Test: 0 Gallons Placement Location: Paving
Water Added Onsite After Test: 0 Gallons
Field Test Data
Test Result Specification Test Method
SLump, inches: 450 5.0 Max ASTM C143
Air Content, %: 3.7 3-7 ASTM C231
Concrete Temperature,° F: 64 ASTM C1064
Ambient Temperature, o F: 53 ASTM C1064
Plastic Unit Weight, pcf:
Laboratory Test Data Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (Lbs) (psi)
1 1 6.00 28.27 0311712005 7 137,910 4,880
1 2 6.00 28.27 0410712005 28 152,170 5,380
1 3 6.00 28.27 0410712005 28 166,890 5,900
Average 5,640
1 4 6.00 2827 0510512005 56 188,130 6,650
Comments: Not tested for plastic unit weight,
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples' i~
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods This report is exclusively for the use of the client
indicated abo*e and shall not be reproduced except in full without the written consent of our company Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials Page 1 of 4
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94041388.0087
Service Date: March 10, 2005
'lrerracan
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client: Hill & Wilkinson LTD
Attn: Charles Hoagland
800 Klein Rd Ste 100
Piano TX 75074
Report Date: May 09, 2005
Project: BCE Specialties
989 West Sandy Lake Road
Coppell, TX
Project Number: 94041388
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 9:08 am Plant: 27
Supplier: Southern Star
Truck No: 0031 Ticket No: 764511
Mix I.D. No.: 7752
Water Added Onsite Before Test: 10 Gallons
Water Added Onsite After Test: 0 Gallons
Field Test Data
Test Result
Slump, inches: 5.00
Air Content, %: 3.1
Concrete Temperature, o F: 64
Ambient Temperature, o F: 58
Plastic Unit Weight, pcf:
Sample Information
Sample Time: 10:00 am Date Cast: March 10, 2005
Technician: Charles A. Patterson
Weather Conditions: Sunny, windy
Accumulative Yards: 110
Placement Method: Pump
Sample Locations: See attached sketch
Placement Location: See page 1
Specification
Test Method
5.0 Max ASTM C143
3-7 ASTM C231
ASTM C1064
ASTM C1064
Laboratory Test Data Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
2 1 6.00 28.27 03/17/2005 7 110,670 3,910
2 2 6.00 28.27 04/07/2005 28 140,950 4,980
2 3 6.00 28.27 04/07/2005 28 143,430 5,070
Average 5,030
2 4 6.00 28.27 05/05/2005 56 162,700 5,750
Comments: Not tested for plastic unit weight.
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, °r DOT test meth°ds This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily ir~dicative of the properties of other apparently similar or identical
Page 2 of 4
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94041388.0087
Service Date: March 10, 2005
'll'erracan
8901 Carpenter Frwy, Ste #~00
Dallas, Texas 75247
(214) 630-1010
Client: Hill & Wilkinson LTD
Attn: Charles Hoagland
800 Klein Rd Ste 100
Piano TX 75074
Report Date: May 09, 2005
Project: BCE Specialties
989 West Sandy Lake Road
Coppell, TX
Project Number: 94041 388
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 10:30 am Plant: 27
Supplier: Southern Star
Truck No: 1883
Mix I.D. No.: 7752
Water Added Onsite Before Test:
Water Added Onsite After Test: 0 Gallons
Field Test Data
Test Result
Slump, inches: 500
Air Content, %: 4.0
Concrete Temperature, o F: 70
Ambient Temperature, o F: 71
Plastic Unit Weight, pcf:
Ticket No: 764523
0 Gallons
Sample Information
Sample Time: 11:45 am Date Cast: March 10, 2005
Technician: Chades A. Patterson
Weather Conditions: Sunny, windy
Accumulative Yards: 220
Placement Method: Pump
Sample Locations: See attached sketch
Placement Location: See page 1
Specification Test Method
5.0 Max ASTM C143
3-7 ASTM C231
ASTM C1064
ASTM C1064
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
3 1 6.00 28.27 03/17~2005 7 107,240 3,790
3 2 6.00 28.27 04/07/2005 28 135,640 4,800
3 3 6.00 28.27 04/07/2005 28 141,840 5,020
Average 4,910
3 4 6.00 28.27 05/05/2005 56 155,410 5,500
Comments: Not tested for plastic unit weight.
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM AASHTO. or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94041388.0087
Service Date: March 10, 2005
1rerracan
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client: Hill & Wilkinson LTD
Attn: Charles Hoagland
800 Klein Rd Ste 100
Piano TX 75074
Report Date: May 09, 2005
Project: BCE Specialties
989 West Sandy Lake Road
Coppell, TX
Project Number: 94041388
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 11:25 am Plant: 27
Supplier: Southern Star
Truck No: 1883
Mix I.D. No.: 7752
Field Test Data
Test
Result
Slump, inches: 5.00
Air Content, %: 3.7
Concrete Temperature, o F: 71
Ambient Temperature, o F: 73
Plastic Unit Weight, pcf:
Ticket No: 764532
Sample Information
Sample Time: 1:00 pm Date Cast:March 10,2005
Technician: Charles A. Patterson
Weather Conditions: Sunny, windy
Accumulative Yards: 310
Placement Method: Chute
Sample Locations: See attached sketch
Placement Location: See page 1
Specification
Test Method
5.0 Max ASTM C143
3-7 ASTM C231
ASTM C1064
ASTM C1064
LaboratorF Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
4 1 6.00 28.27 03/17/2005 7 99,160 3,510
4 2 6.00 28.27 04/07/2005 28 123,650 4,370
4 3 6.00 28.27 04/07/2005 28 123,940 4,380
Average 4,380
4 4 6.00 28 27 05/05/2005 56 135,090 4,780
Comments: Not tested for plastic unit weight.
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Charles A. Patterson
Repod Distribution:
(1) Hill & Wilkinson LTD
(1) Hardy McCullah/MLM Archilects Inc
(1) TMBP Consulling Engineers
(1) City of Copper] TX
(1) BCE Specialties Reviewed by:
Senior Proj//~an-i~;r
The tests were performed in general accordance with applicable ASTM, AASHTO or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently sinai[ar or identical
materials