Coppell Trade-LR050531CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94051081.0059 Service Date: April 28, 2005 Client: Coppell Trade Center LP Attn: At Sorrels 5055 Keller Springs Rd Ste 300 Addison TX 75001 ll'err can 8901 Carpenter F~,vy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Report Date: May 31, 2005 Project: Coppell Trade Center NWC Sandy Lake & State St Coppell, TX Project Number: 94051081 Material Information Specified Strength: 4000 psi ~ 28 Days Batch Time: 2:45 pm Plant: 6 Supplier: LMC Truck No: 5015 Ticket No: 6249566 Mix I.D. No.: 1701 Water Added Onsite Before Test: 0 Gallons Water Added Onsite After Test: 0 Gallons Sample Information sample Time: 4:00 pm Date Cast:April 28, 2005 Technician: Michael E. Odom Weather Conditions: Fair Accumulative Yards: 10 Placement Method: Direct Discharge Sample Locations: Line E inlet, Sta. 0+30 Placement Location: 10' Inlets, Line E, Sta. 0+30; Line D, Sta. 0+30; Line B, Sta. 0+25 Field Test Data Test Result Specification Test Method Slump, inches: 4.00 5.0 ASTM C143 Air Content, %: 4.9 3-7 ASTM C231 Concrete Temperature,° F: 87 ASTM C1064 Ambient Temperature, o F: 94 ASTM C1064 Plastic Unit Weight, pcf: 143.2 ASTM C138 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 1 1 6.00 28.27 05/05/2005 7 83,710 2,960 1 2 6.00 28.27 05/05/2005 7 78,350 2,770 Average 2,870 1 3 6.00 28.27 05126/2005 28 123,090 4,350 1 4 6.00 28.27 05/26/2005 28 120,800 ~4,27_0 Average Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Michael E. Odom Report Distribution: (1) Coppell Trade Center LP (1) Pritchard Associates Inc (1) City of Co ppell TX (1) City of Coppelt TX (1) McFadden & Miller Reviewed by: Robert D. Ray,~.T. Senior preje~vlanager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transroitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94051081.0062 Service Date: April 29, 2005 1E rracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Coppell Trade Center LP Attn: Al Sorrels 5055 Keller Springs Rd Ste 300 Addison TX 75001 Report Date: May 31,2005 Project: Coppeil Trade Center NWC Sandy Lake & State St Coppell, TX Project Number: 94051081 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: Supplier: LMC Truck No: 0 Mix I.D. No.: 1701 Water Added Onsite Before Test: Water Added Onsite After Test: Ticket No: 0 Gallons 0 Gallons Sample Information sample Time: 2:20 pm Date Cast: April 29, 2005 Technician: Michael E. Odom Weather Conditions: Fair Accumulative Yards: 3.5 Placement Method: Direct Discharge Sample Locations: See Placement Location Placement Location: Two Head Walls, Sta. 0+00, Line B 27"; Sta. 0+00, Line A 24" Field Test Data Test Result Specification Slump, inches: 3.75 Air Content, %: 4.7 Concrete Temperature, O F: 80 Ambient Temperature, o F: 75 Plastic Unit Weight, pcf: 146.0 Laboratory Test Data 4.0 3-7 Set Specimen Diameter Ama Date No. ID (inches) (sq. inches) Tested 1 1 6.00 28.27 05/06/2005 1 2 6.00 28.27 05/06/2005 1 3 6.00 28.27 05/27/2005 1 4 6.00 28.27 05/27/2005 Test Method ASTM C143 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Age at Maximum Compressive Test Load Strength (days) (lbs) (psi) 7 110,890 3,920 7 110,120 3,890 Average 3,910 28 164,580 f 5,820 28 163,530 ~ 5~780 Average "-S,800 Services - Obtain samples of fresh concrete at the placement locations, per[orm required field tests and cast compressive strength samples. Technician: Michael E. Odom (1) Cop.il Trade Center LP (1) Merriman Assoc ,nc (1) Pfitchard Associates Inc (1) McFadden & Miller Reviewed by: (1) City of Coppell TX ' Robert D. Ray, S.F~,/ (1) City of Coppeil TX ' Senior Proiect~fn~a~r The testa w~re bedorm~ in general accordance with applicable ^STM, ^ASHTO, or DO? t~t methode. This report is ex¢luaiYely for the ~Sf the client indioeted abeYe end ehall not be reproduoed e×oept in full without the written consent of our company. Test msuits transmitted herein are only epplicable to tl'~ actual samples tested at the location(s) mfemn¢~l and are not neces~adly indicative of the properti~ of other ~ppamn~ ~imHar or identical material*. REPORT OF REINFORCING STEEL OBSERVATION ' reffacon Date of Service: Client No.: Client: 05/31/05 93345 Coppell Trade Center LP 5055 Keller Springs Rd Ste 300 Addison, TX 75001 Report No.: Project No..' Project: 94051190.0017 94051190 Coppell Trade Center - Bldg C NWC Sandy Lake/Freeport Pkwy Coppell, TX Services: Drawings Utilized: Observe placement of reinforcing for compliance with furnished drawings. PROJECT DATA Civil Drawings Locations/Items Observed: Backwall, 2nd from west, @ SW comer of jobsite Test Method: Visual Observation REPORT OF OBSERVATION ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT Placing Dra'~ngs Approved X Bar Length and Shape X Colu~ Tie Spacing & Type Sar Size X Proper Bar Placement X Stirrup Spacing & Type Bar Grade X Prapedy Tied X Welded Splices Raper Clean X Dowel Sam in P~ace X Mechanical Splices Trash & Dapds Removed X Proper Bar SuppeRs X Lapped Splices X Nuttier ot Bars X Proper Cover/Clearance X Discrepancies/Comments: Any discrepancies found were corrected at the time of this observation unless otherwise noted. Field Results Report To: Technician: E. Jemigan Report Distribution: (1) Coppell Trade Center LP (1) TechniStructures (1) City of Coppell TX (1) City of Coppell TX 309ecs l rracon (1) McFadden & Milter (1) Macatee Engineering Inc This reporl is exclusively for the use of the client indicated above and shall not be reproduced witbo~t written appmvaJ of HBC. JTerraco~l.