Coppell Trade-LR050628FIELD DENSITY TESTING
Report Number: 94051190.0037
Service Date: June 14, 2005
Client: Coppell Trade Center LP
Attn: Al Sorrels
5055 Keller Springs Rd Ste 300
Addison TX 75001
ll'errecan
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: June 28, 2005
Project: Coppell Trade Center -Bldg C
NWC Sandy Lake/Freeport Pkwy
Coppell, TX
Project Number: 94051190
Material Information Lab Test Data Pmiect Renuirements
Optimum Max. Lab Water
Water Dry Unit Content Minimum Dry
Material Laboratory Content Weight Range Unit Weight
No. Test Method Description and Classification (%) (pcf) (%) (% compaction)
1. 510810002 ASTM D 698 Dark reddish brown sandy clay 15.2 106.2 -1/+3 95
Field Test Data Probe Water Dry Unit Dry Unit
Test Lift/ Mat. Depth Content Weight Weight
No. Test Location Elevation No. (inches) (%) (pcf) (%compaction)
Parking Lot
195 50' N & 100" E of NW comer FG 1 6 14.9 105.7 100
196 75' N & 200' E of NW comer FG 1 6 15.3 104.4 98
Datum: FG = final grade
Comments:
Test results on this report meet proJect specification.
Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture
condition.
Field Test Method~,STM D2922, ASTM D3017
Gauge ID: 2207
Technician: Laramie S. Chronister
Field Results Reported To: Ted/Chariie
Report Distribution:
(1) Coppell Trade Center LP
(1) Te~hniSffuctures
(1) City of Coppell TX
(1) City of Coppell TX
(1) Merriman Assoc Inc
(1) M<;Fadden & Miller
(1) Ma<alee Engineering
Reviewed by:
RobeA
Senior Project ~anager
The tests were parforrned in general accordance with applicebie ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicetod above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the preparties of other apparently similar or identical
materials.
,CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94051190.0012
Service Date: May 27, 2005
Client: Coppell Trade Center LP
Attn: Al Son'els
5055 Keller Springs Rd Ste 300
Addison TX 75001
'lrerracan
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: June 28, 2005
Project: Coppell Trade Center- Bldg C
NWC Sandy Lake/Freeport Pkwy
Coppell, TX
Project Number: 94051190
Material Information
Specified Strength: 4000 psi ~ 28 Days
Batch Time: 5:54am Plant: 141
Supplier: TXI
Truck No: 64
Mix I.D. No.: 8206
Water Added Onsite Before Test: 0 Gallons
Water Added Onsite After Test: 0 Gallons
Ticket No: 53370
Sample Information
Sample Time: 6:22am Date Cast: May 27, 2005
Technician: Bradley W. Hatch
Weather Conditions: Cloudy
Accumulative Yards: 40
Placement Method: Direct Discharge
Sample Locations: 20' S & 140' W of NW corner of building
Placement Location: Pavement, 0' - 250' S & 20' - 160' W of NW
comer of bldg
Field Test Data
Test Result Specification Test Method
Slump, inches: 6.00 ASTM C143
Air Content, %: 5.5 ASTM C231
Concrete Temperature,o F: 88 ASTM C1064
Ambient Temperature, o F: 71 ASTM C1064
Plastic Unit Weight, pcf: 142.8 ASTM C138
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
1 1 6.00 28.27 06~03/2005 7 102,170 3,610
1 2 6.00 28.27 06/0312005 7 102,960 3,640
Average 3,630
I 3 6.00 28.27 06/24/2005 28 127,410 4,510
1 4 6.00 28.27 06/24/2005 28 133,460 4,720
Average 4,620
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the usa of the client
indicated above and shall not be reproduced except in full without the written consant of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the prope~ies of other apparantfy similar or identical
materials.
Page 1 of 4
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94051190.0012
Service Date: May 27, 2005
Client: Coppell Trade Center LP
Attn: Al Sorrels
5055 Keller Spdngs Rd Ste 300
Addison TX 75001
lrerracan
8901 Carpenter Fnvy, Ste #100
Dalles, Texas 75247
(214) 630-1010
Report Date: June 28, 2005
Project: Coppell Trade Center - Sldg C
NWC Sandy Lake/Freeport Pkwy
Coppell, TX
Project Number: 94051190
Material Information
Specified Strength: 4000 psi (~ 28 Days
Batch Time: 6:43am
Supplier: TXI
Track No: 71
Mix I.D. No.: 8206
Water Added Onsite Before Test:
Water Added Onsite After Test:
Field Test Data
Test
Plant: 141
Ticket No: 53435
0 Gallons
0 Gallons
Result
Slump, inches: 5.00
Air Content, %: 5.7
Concrete Temperature, o F: 87
Ambient Temperature, o F: 73
Plastic Unit Weight, pcf: 142.8
Laboratory Test Data
Sample Information
Sample Time: 7:12am Date Cast: May 27, 2005
Technician: Bradley W. Hatch
Weather Conditions: Cloudy
Accumulative Yards: 110
Placement Method: Direct Dischaq3e
Sample Locations: 160' S & 30' W of NW corner of building
Placement Location: See page 1
Specification Test Method
ASTM C143
ASTM C231
ASTM C1064
ASTM C1064
ASTM C138
Age at
Set Specimen Diameter Area Date Test
No. ID (inches) (sq. inches) Tested (days)
2 1 6.00 28.27 06/0312005 7
2 2 6.00 28.27 06/0312005 7
Average
2 3 6.00 28.27 06~24~2005 28 135,540
2 4 6.00 28.27 06/24/2005 28 132,080
Average
Maximum Compr, es~ive
Load St/bngth
(lbs) ~
110,720 [ 3,920
107,010 ' 3,780
3,850
4,790
4,670
4,730
Services - Obtain samples of fresh concrete at the placement locations, perform required field te:
strength samples.
~ts and cast compressive
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except tn full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94051190.0012
Service Date: May 27, 2005
Client: Coppell Trade Center LP
Attn: Al Sorrels
5055 Keller Spdngs Rd Ste 300
Addison TX 75001
l rracan
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: June 28, 2005
Project: Coppell Trade Center- Bldg C
NWC Sandy Lake/Freeport Pkwy
Coppell, TX
Project Number: 94051190
Material Information
Specified Strength: 4000 psi ~ 28 Days
Batch Time: 7:54am
Supplier: TXI
Truck No: 802
Mix I.D. No.: 8206
Water Added Onsite Before Test:
Water Added Onsite After Test:
Field Test Data
Test
Plant: 141
Ticket No: 53534
0 Gallons
0 Gallons
Sample Information
Sample Time: 8:26am Date Cast: May 27, 2005
Technician: Bradley W. Hatch
Weather Conditions: Cloudy
Accumulative Yards: 210
Placement Method: Direct Discharge
Sample Locations: 195' S & 130' W of NW corner of building
Placement Location: See page 1
Result
Slump, inches: 5.25
Air Content, %: 4.9
Concrete Temperature, o F: 88
Ambient Temperature, o F: 75
Plastic Unit Weight, pcf: 144.4
Laboratory Test Data
Age at
Set Specimen Diameter Area Date Test
No. ID (inches) (sq. inches) Tested (days)
3 I 6.00 28.27 06~03~2005 7
3 2 6.00 28.27 06/0312005
Specification Test Method
3 3 6.00 28.27 06~24~2005
3 4 6.00 28.27 06~24~2005
ASTM C143
ASTM C231
ASTM C1064
ASTM C1064
ASTM C138
Maximum C~prassive
Load ! Strength
(lbs) ~ (ps0
119,680 4,230
7 116,930 4,140
Average 4,190
28 147,850 5,230
28 143,340 5,070
Average ~ 5,150
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests a~st compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT tesst methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only aplfllcable
to the actual samples tested at the location(s) referenced and ara not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 3 of 4 o,~,~m,.~,.
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94051190.0012
Service Date: May 27, 2005
Client: Coppell Trade Center LP
Attn: Al Sorrels
5055 Keller Spdngs Rd Ste 300
Addison TX 75001
l rracon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: June 28, 2005
Project: Coppell Trade Center - Bldg C
NWC Sandy Lake/Freeport Pkwy
Coppell, TX
Project Number: 94051190
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 9:25am
Supplier: TXI
Truck No: 62
Mix I.D. No.: 8206
Water Added Onsite Before Test:
Water Added Onsite After Test:
Field Test Data
Test
Plant: 141
Ticket No: 53661
0 Gallons
5 Gallons
Result
Slump, inches: 5.00
Air Content, %: 5.7
Concrete Temperature? F: 91
Ambient Temperature, o F: 78
Plastic Unit Weight, pcf: 143.6
Laboratory Test Data
Sample Information
Sample Time: 9:55am Date Cast: May 27, 2005
Technician: Bradley W. Hatch
Weather Conditions: Cloudy
Accumulative Yards: 320
Placement Method: Direct Discharge
Sample Locations: 230' S & 75' W of NW corner of building
Placement Location: See page 1
Specification Test Method
Set Specimen Diameter Area Date
No. ID (inches) (sq. inches) Tested
4 I 6.00 28.27 06/03/2005
4 2 6.00 28.27 06/03/2005
4 3 6.00 28.27 06/24/2005
4 4 6.00 28.27 06124/2005
ASTM C143
ASTM C231
ASTM C1064
ASTM C1064
ASTM C138
Age at Maximum Compressive
Test Load Strength
(days) (lbs) (psi)
7 114,150 4,040
7 115,420 4,080
Average 4,060
28 145,780 5,160
28 141,550 5,010
Average 5,090
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Bradley W. Hatch
Report Distribution:
(1) Coflpell Trade Center LP
(1) TechniStructures
(1) City of Coppell TX
(1) City of Coppell TX
(1) Merriman Assoc Inc
(1) McFadden & Miller
(1) Macatee Engineering Inc
Robert D. Ray,~//L/-I'.
Senior Proje~granager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
Indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the p~'opertisa of other apparently similar or identical
materials.
Page 4 of 4
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94051190.0048
Service Date: June 20, 2005
Client: ~--'G~nter LP
A'fin: Al Sorrels
5055 Keller Spdngs Rd Ste 300
Addison TX 75001
'll'erracon
8901 Carpenter Frwy, Ste #100
Daltas, Texas 75247
(214) 630-1010
Report Date: June 28, 2005
Project: Coppell Trade Center- Bldg C
NWC Sandy Lake/Freeport Pkwy
Coppell, TX
Project Number: 94051190
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time:
Supplier:
Track No:
Mix I.D. No.:
Ticket No:
Sample Information
Sample Time: Date Cast: June 17, 2005
Technician: Contractor Made
Weather Conditions:
Placement Method:
Sample Locations:
Placement Location: Spread Footings (~ B, C, D, E/12, 13
Field Test Data
Test
Result
Slump, inches:
Air Content, %:
Concrete Temperature, C F:
Ambient Temperature, o F:
Plastic Unit Weight, pcf:
Laboratory Test Data
Set Specimen Diameter Area
No. ID (inches) (sq. inches)
Specification
Test Method
ASTM C143
ASTM C231
ASTM C1064
ASTM C1064
ASTM C138
Age at Maximum Compressive
Date Test Load Strength
Tested (days) (lbs) (psi)
I 1 6.00 28.27 06/24/2005 7 99,990 3,540
1 2 07/15/2005 28
I 3 07/15/2005 28
Comments: Not tested for plastic unit weight.
. retul
Services Pick up test cylinders cast by others and atory for curing and testing.
Technician: Laramie S. Chmnister
Report Distribution:
(I) Coppell Trade Center LP
(1) TechniStructures
(1) City of Coppell TX
(1) City of Coppell TX
(1) Merriman Assoc
(1) McFadden & Miller
(1) Macatee Engineering
Robert D. Ray, S.E.~.
Senior Project IVl~ager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT teat methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein ara only applicable
to the actual samples tested at the location(s) referenced and ara not necessarily indicative of the properties of other apparently similar or identical
materials.
FIELD DENSITY TESTING
Report Number: 94051190.0033
Service Date: June 9, 2005
Client: Coppell Trade Center LP
Attn: Al Sorrels
5055 Keller Spdngs Rd Ste 300
Addison TX 75001
'll'err can
8901 Carpenter Fnvy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: June 28, 2005
Project: Coppell Trade Center - Bidg C
NWC Sandy Lake/Freeport Pkwy
Coppell, TX
Project Number: 94051190
Material Information Lab Test Data Project ReauJrements
Optimum Max. Lab Water
Water Dry Unit Content Minimum Dry
Matedal Laboratory Content Weight Range Unit Weight
No. Test Method Description and Classification (%) (pcf) (%) (% compaction)
1. 510810002 ASTM D 698 Dark reddish brown sandy clay 15.2 106.2 >/= +4 92-98
Field Test Data Probe Water Dry Unit Dry Unit
Test Lift/ Mat. Depth Content Weight Weight
No. Test Location Elevation No. (inches) (%) (pcf) (% compaction)
Utility Backfill in Building Pad
163 BI11 to 12 3' BFG 1 6 19.5 101.3 95
164 E/11 to 12 3' BFG 1 6 19.8 101.9 96
165 9/D to E 3' BFG 1 6 19.7 102.4 96
166 2/D to E 3' BFG 1 6 19.8 104.1 98
Datum: BFG = below final grade
Comments:
Test results on this report meet project specification.
Services - Perform in-place density and moisture content tests to determine degree of compaction and matedal moisture
condition.
Field Test Method~,STM D2922, ASTM D3017
Gauge ID: 2207
Technician: Laramie S. Chronister
Field Results Reported To: Henry
Report Distribution:
(1) Coppell Trade Center LP
(1) TechniStFuotures
('r) City of Coppell TX
(1) City of Coppell TX
(1) Merriman Assoc
(1) McFadden & Miller
(1) Macatee Engineering Inc
Reviewed by: ~~'~/
The tests were pafformed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the wfiffen consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the Icoation(s) referenced and are not neceesarify indicative of the properties of other apparently similar or identical
materials.
FIELD DENSITY TESTING
Report Number: 94051190.0032
Service Date: June 10, 2005
Client: Coppell Trade Center LP
Attn: Al Sorrels
5055 Keller Springs Rd Ste 300
Addison TX 75001
ll'erracan
8901 Carpenter F~vy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: June 28, 2005
Project: Coppell Trade Center - Bldg C
NWC Sandy Lake/Freeport Pkwy
Coppell, TX
Project Number: 94051190
Material Information Lab Test Data Pmiect Requirements
Optimum Max. Lab Water
Water Dry Unit Content Minimum Dry
Material Laboratory Content Weight Range Unit Weight
No. Test Method Description and Classification (%) (pcf) (%) (% compaction)
1. 510810002 ASTM D 698 Dark reddish brown sandy clay 15.2 106.2 >/-- Opt. 95
2. 510810002 ASTM D 698 Dark reddish brown sandy clay 15.2 106.2 >/= +4 92
Field Test Data Probe Water Dry Unit Dry Unit
Test LifiJ Mat. Depth Content Weight Weight
No. Test Location Elevation No, (inches) (%) (pcf) (% compaction)
Spread Footing Bearing
167 B/10 5.10' BFG 1 6 18.4 101.9 96
168 C/10 5.6' BFG 1 6 19.5 101.1 95
169 D/10 5.8' BFG 1 6 17.8 103.8 98
170 D/9 5.7' BFG 1 6 18.3 102.3 96
171 C/9 5.9' BFG 1 6 18.7 101.5 96
172 B/9 5.2' BFG 1 6 18.1 102.7 97
173 B/8 5.7' BFG 1 6 19.0 102.0 96
174 C/8 5.1' BFG 1 6 18.0 102.9 97
175 D/8 5.2' BFG I 6 18.6 103.2 97
Plumbing Ditch at Building Pad
176 Between Lines 11 and 12 at Line C 2' BFG 2 6 19.3 101.0 95
Datum: BFG -- below final grade
Comments:
Test results on this report meet project specification.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall nc~ be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 2 o~c~-~.,
· FIELD DENSITY TESTING
Client: Coppell Trade Center LP
ll'erracon
Project Number:94051190
Report Number. 94051190.0032
Services - Per[om] in-place density and moisture content tests to determine degree of compaction and material moisture
condition.
Field Test Method~,STM D2922, ASTM D3017
Gauge ID: 2207
Technician: Laramie S. Chronister
Field Results Reported To: Henry/Charlie
Report Distribution:
(1) Coppell Trade Center LP
(1) TechniStru~tures
(1) City of Ceppatl TX
(1) city of Coppel~ TX
(1) Merriman Assoc Inc
(1) McFadden & Miller
(1) Macatee Engineering Inc
Reviewed by: ~//~
Robert D. Ray,~T,
Senior Project~l~lanager
The tests were performed in general accordance with applicable ASTM, PASHTO, or DOT test methods. This mi)oR is excluslvely for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transtar(ted herein are only applicable
to the actual samples tested at the location(s) referenced and ara not necessarily indicative of the properties of other apparently similar or identical
materials.