Loading...
Coppell Trade-LR050627 (2)CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94051190.0041 Service Date: June 16, 2005 Client: Coppell Trade Center LP Attn: Al Sorrels 5055 Keller Springs Rd Ste 300 Addison TX 75001 'll'erracon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Report Date: June 27, 2005 Project: Coppell Trade Center - Bldg C NWC Sandy Lake/Freeport Pkwy Coppell, TX Project Number: 94051190 Material Information Specified Strength: 4000 psi (~ 28 Days Batch Time: 6:55am Plant: 141 Supplier: TXI Truck No: 834 Mix I.D. No.: 8206 WaterAdded Onsite Before Test: 10 Gallons Water Added Onsite After Test: 0 Gallons Field Test Data Test Result Slump, inches: 6.00 Air Content, %: 6.1 Concrete Temperature, o F: 92 Ambient Temperature, o F: 81 Plastic Unit Weight, pcf: N/A Laboratory Test Data Ticket No: 64214 Sample Information Sample Time: 7:45am Date Cast: June 16, 2005 Technician: Eric G. Jernigan Weather Conditions: Clear, hot & humid Accumulative Yards: 70 Placement Method: Direct Discharge Sample Locations: 150' S of N end of Bldg C Placement Location: E Parking Area & Fire Lane Specification 3-5 3-7 Test Method ASTM C143 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 1 1 6.00 28.27 06/23/2005 7 96,030 3,400 I 2 6.00 28.27 06/23/2005 7 95,510 3,380 Average 3,390 1 3 07/14/2005 28 1 4 07/14/2005 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in tull without the written consent of our ccmpeny. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. ,CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94051190.0041 Service Date: June 16, 2005 Client: Coppell Trade Center LP Attn: Al Sorrels 5055 Keller Springs Rd Ste 300 Addison TX 75001 lrerracan 8901 Carpenter Fro,y, Ste #100 Dallas, Texas 75247 (214) 630-1010 Report Date: June 27, 2005 Project: Coppell Trade Center - Bldg C NWC Sandy Lake/Freeport Pkwy Coppell, TX Project Number: 94051190 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 8:55am Supplier:. TXI Truck No: 109 Mix I.D. No.: 8206 Water Added Onsite Before Test: Water Added Onsite After Test: Field Test Data Test Plant: 141 Ticket No: 64437 0 Gallons 0 Gallons Result Slump, inches: 5.00 Air Content, %: 7.8 Concrete Temperature, o F: 97 Ambient Temperature, o F: 92 Plastic Unit Weight, pcf: N/A Laboratory Test Data Set Specimen Diameter Area No. ID (inches) (sq. inches) 2 1 6.00 28.27 2 2 6.00 28.27 2 3 2 4 Sample Information Sample Time: 9:30am Date Cast:June 16, 2005 Technician: EricG. Jernigan Weather Conditions: Sunny & warm Accumulative Yards: 170 Placement Method: Direct Discharge Sample Locations: 270' S of N end of Bldg C Placement Location: See page 1 Specification 3-5 3-7 Test Method ASTM C143 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Age at Maximum Compressive Date Test Load Strength Tested (days) (lbs) (psi) 06/23/2005 7 95,120 3,360 06/23/2005 7 91,700 3,240 Average 3,300 07/14/2005 28 07/14/2005 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were pert'ormod in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report Is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test resuEs transmitted herein ara only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 3 CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94051190.0041 Service Date: June 16, 2005 Client: Coppell Trade Center LP Attn: Al Sorrels 5055 Keller Springs Rd Ste 300 Addison TX 75001 ll'erracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (2t 4) e3o-t 0t o Report Date: June 27, 2005 Project: Coppell Trade Center - Bldg C NWC Sandy Lake/Freeport Pkwy Coppell, TX Project Number: 94051190 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 10:20am Supplier: TXI Truck No: 112 Mix I.D. No.: 8206 Water Added Onsite Before Test: Water Added Onsite After Test: Field Test Data Test Plant: 141 Ticket No: 64593 0 Gallons 0 Gallons Result Slump, inches: 5.50 Air Content, %: 6.0 Concrete Temperature,o F: 96 Ambient Temperature, o F: 94 Plastic Unit Weight, pcf: N/A Laboratory Test Data Sample Information Sample Time: 10:50am Date Cast: June 16, 2005 Technician: Eric G. Jemigan Weather Conditions: Sunny, clear & warm Accumulative Yards: 270 Placement Method: Direct Discharge Sample Locations: 400' S of N end of Bldg C Placement Location: See page 1 Specification Test Method 3-5 ASTM C143 3-7 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 3 1 6.00 28.27 06/23/2005 7 82,800 2,930 3 2 6.00 28.27 06/23/2005 7 88,840 3,140 Average 3,040 3 3 07/14/2005 28 3 4 07/14/2005 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Eric G. Jemigan Report Distribution: (1) Coppell Trade Center LP (1) TechniStructures (1) City of Coppell TX (1) City of Coppell TX (1) Merriman Assoc lAC (1) McFadden & Miller (1) Macatee Engineering Inc Reviewed by: ~~ The tests were p~formed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are oniy applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 3 of 3 o~,~...~