Coppell Trade-LR050712CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94051190.0043
Service Date: June 16, 2005
Client: Coppell Trade Center LP
Attn: Bennet Ratliff
5055 Keller Springs Rd Ste 300
Addison TX 75001
'lrerracon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: July 12, 2005
Project: Coppell Trade Center- Bldg C
NWC Sandy Lake/Freeport Pkwy
Coppell, TX
Project Number: 94051190
Material Information
Specified Strength: 4000 psi <~ 28 Days
Batch Time:
Supplier:
Truck No:
Mix I.D. No.: 9506
Ticket No:
Sam_~_~.~nformation
Sample Time: Date Cast: June 13, 2005
Technician: Contractor Made
Weather Conditions:
Placement Method:
Sample Locations:
Placement Location: Spread Footings: B, C, D, E/14, 15
Field Test Data
Test
Result
Slump, inches:
Air Content, %:
Concrete Temperature, O F:
Ambient Temperature, o F:
Plastic Unit Weight, pcf:
Laboratory Test Data
Set Specimen Diameter Area
No. ID (inches) (sq. inches)
1 1 6.00 28.27
1 2 6.00 28.27
1 3 6.00 28.27
1 4 6.00 28.27
Specification Test Method
ASTM C143
ASTM C231
ASTM C1064
ASTM C1064
ASTM C138
Age at Maximum Compressive
Date Test Load Strength
Tested (days) (lbs) (psi)
06/20/2005 7 92,360 3,270
06/20/2005 7 94,770 3,350
Average 3,310
07/11/2005 28 121,380 4,290
07/11/2005 28 121,080 4,280
Average 4,290
Comments: Not tested for plastic unit weight.
Services - Pick up test cylinders cast by others and return them to the laboratory for curing and testing.
Technician: Eric G. Jemigan
Report Distribution:
(1) Coppell Trade Center LP
(1) TechniStructures
(1) Cily of Coppell TX
(1) City of Coppell TX
(1) Merriman Assoc Inc
(1) McFadden & Miller
(1) Macatee Engineering Inc
Reviewed by:
Robert D. Ray,~.
Senior Proje~vlglanager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the Iccation(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials. Page 1 of 1
CONCRETE COMPRESSIVE STRENGTH TEST
· Report Number: 94051190.0061
Service Date: June 30, 2005
Client: Coppell Trade Center LP
Attn: Bennet Ratliff
5055 Keller Springs Rd Ste 300
Addison TX 75001
' rl!!ff con
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: July 12, 2005
Project: Coppell Trade Center- Bldg C
NWC Sandy Lake/Freeport Pkwy
Coppell, TX
Project Number: 94051190
Material Information
Specified Strength: 4000 psi ~ 28 Days
Batch Time: 6:54am
Supplier: TXI
Truck No: 111
Mix I.D. No·: 8206
Water Added Onsite Before Test:
Water Added Onsite After Test:
Field Test Data
Test
Plant: 141
Ticket No: 73152
0 Gallons
0 Gallons
Result
Slump, inches: 4.50
Air Content, %: 6.2
Concrete Temperature, o F: 90
Ambient Temperature, o F: 83
Plastic Unit Weight, pcf: 144.3
Laboratory Test Data
Sample Information
sample Time: 8:10am
Technician: Kudret Aksu
Weather Conditions: Clear
Accumulative Yards: 10
Placement Method: Direct Discharge
Sample Locations: See attached sketch
Placement Location: Paving
Date Cast: June 30, 2005
Specification Test Method
3-5
3-6
ASTM C143
ASTM C231
ASTM C1064
ASTM C1064
ASTM Cl 38
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
I 1 6.00 28.27 07/07/2005 7 85,360 3,020
I 2 6.00 28.27 07/07/2005 7 87,010 3,080
Average 3,050
1 3 07/28/2005 28
1 4 07/28/2005 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials, o~.E~,
Page 1 of 3
CONCRETE COMPRESSIVE STRENGTH TEST
· Report Number: 94051190.0061
Service Date: June 30, 2005
Client: Coppell Trade Center LP
Attn: Bennet Ratliff
5055 Keller Springs Rd Ste 300
Addison TX 75001
" rerracon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: July 12, 2005
Project: Coppell Trade Center - Bldg C
NWC Sandy Lake/Freeport Pkwy
Coppell, TX
Project Number: 94051190
Material Information
Specified Strength: 4000 psi ~ 28 Days
Batch Time: 7:57am Plant: 141
Supplier: TXI
Truck No: 70 Ticket No: 73265
Mix I.D. No.: 8206
Water Added Onsite Before Test: 15 Gallons
Water Added Onsite After Test: 0 Gallons
Field Test Data
Test
Slump, inches:
Air Content, %:
Concrete Temperature, o F:
Ambient Temperature, o F:
Plastic Unit Weight, pcf:
Laboratory Test Data
Sample Information
Sample Time: 9:00am
Technician: Kudret Aksu
Weather Conditions: Clear
Accumulative Yards: 60
Placement Method: Direct Discharge
Sample Locations: See attached sketch
Placement Location: Paving
Result Specification Test Method
4.75 3-5 ASTM C143
6.1 3-6 ASTM C231
91 ASTM C1064
87 ASTM Cl 064
ASTM C138
Date Cast: June 30, 2005
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
2 1 6.00 28.27 07/07/2005 7 98,970 /
3,500
2 2 6.00 28.27 07~07/2005 7 97,640 ~r 3,45~
Average
2 3 07/28/2005 28
2 4 07/28/2005 28
Comments: Not tested for plastic unit weight.
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the uss of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
Page 2 of 3
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94051190.0061
Service Date: June 30, 2005
Client: Coppell Trade Center LP
Attn: Bennet Rafiiff
5055 Keller Springs Rd Ste 300
Addison TX 75001
lrerracon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: July 12, 2005
Project: Coppell Trade Center - Bldg C
NWC Sandy Lake/Freeport Pkwy
Coppell, TX
Project Number: 940511g0
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 10:19am
Supplier: TXI
Track No: 507
Mix I.D. No.: 8206
Water Added Onsite Before Test:
Water Added Onsite After Test:
Field Test Data
Test
Slump, inches:
Air Content, %:
Concrete Temperature,° F:
Ambient Temperature, o F:
Plastic Unit Weight, pcf:
Laboratory Test Data
Plant: 141
Ticket No: 73510
0 Gallons
0 Gallons
Result
4.50
6.1
93
98
Sample Information
Sample Time: 11:05am
Technician: Kudret Aksu
Weather Conditions: Clear
Accumulative Yards: 150
Placement Method: Direct Discharge
Sample Locations: See attached sketech
Placement Location: Paving
Specification
3-5
3-6
Date Cast:June 30, 2005
Set Specimen Diameter Area Date
No. ID (inches) (sq. inches) Tested
3 I 6.00 28.27
3 2 6.00 28.27
3 3
3 4
Test Method
ASTM C143
ASTM C231
ASTM Cl 064
ASTM Cl 064
ASTM C138
Age at Maximum Compressive
Test Load Strength
(days) (lbs) ( ~9~0~
07/07/2005 7 111,200 3,
07/07/2005 7 110,030 . 3,890~
Average
07/28/2005 28
07/28/2005 28
Comments: Not tested for plastic unit weight.
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Kudret Aksu
(1) Coppe~l Trade Center LP (1) Merriman Assoc Inc .... ~JJ Jf~-~ V~
(1) Technt~tructures (1) McFadden & Miller i-(evlewea Dy: ~' ~/'J /'-~"
(1) City of Coppelt TX (1) Macatee Engineering Inc ~' Robe~ D. Ray, S.E.T~v~J
(1) city o~ Coppell TX Senior Project Man..~,.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use o-f the client
indicated above and shall not he reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials. Page 3 of 3 0~.F~o ~,~
CONCRETE COMPRESSIVE STRENGTH TEST
' Report Number: 94051190.0029
Service Date: June 9, 2005
Client: Coppell Trade Center LP
Attn: Bennet Ratliff
5055 Keller Springs Rd Ste 300
Addison TX 75001
' rl ff con
8901 Carpenter Fn*/y, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: July 12, 2005
Project: Coppell Trade Center- Bldg C
NWC Sandy Lake/Freeport Pkwy
Coppell, TX
Project Number: 94051190
Material Information
Specified Strength: 3000 psi @ 28 Days
Batch Time: 6:25am Plant: 141
Supplier: TXI
Truck No: 37 Ticket No: 59569
Mix I.D. No.: 8206
Water Added Onsite Before Test: 10 Gallons
Sample Information
Sample Time: 7:20am Date Cast: June 9, 2005
Technician: Burl E. Thomas
Weather Conditions: Clear
Accumulative Yards: 60
Placement Method:
Sample Locations: 60' N & 20' W of property comer
Placement Location: Paving
Field Test Data
Test
Result
Slump, inches: 5.00
Air Content, %: 4.0
Concrete Temperature,° F: 92
Ambient Temperature, o F: 75
Plastic Unit Weight, pcf: 144.8
Specification
Test Method
3-5 ASTM C143
4-6 ASTM C231
ASTM C1064
ASTM C1064
ASTM C138
Laboratory Test Data Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
1 1 6.00 28.27
06/16/2005 7 111,070 3,930
Services -
2 6.00 28.27 07/07/2005 28 146,120 5,170
3 6.00 28.27 07/07/2005 28 145,770 5,160
Average 5,170
Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the Icoation(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials, o~.~a~-F~.. ~.~
Page 1 of 4
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94051190.0029
Service Date: June 9, 2005
Client: Coppell Trade Center LP
Attn: Bennet Ratliff
5055 Keller Springs Rd Ste 300
Addison TX 75001
'1 rerracon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: July 12, 2005
Project: Coppell Trade Center - Bldg C
NWC Sandy Lake/Freeport Pkwy
Coppell, TX
Project Number: 94051190
Material Information
Specified Strength: 3000 psi (~ 28 Days
Batch Time: 7:32am Plant: 141
Supplier: TXI
Truck No: 66
Mix I.D. No.: 8206
Water Added Onsite Before Test: 10 Gallons
Water Added Onsite After Test: 0 Gallons
Field Test Data
Test
Ticket No: 59454
Slump, inches:
Air Content, %:
Concrete Temperature, o F:
Ambient Temperature, o F:
Plastic Unit Weight, pcf:
Sample Information
Sample Time: 8:12am Date Cast: June 9, 2005
Technician: Burl E. Thomas
Weather Conditions: Clear
Accumulative Yards: 140
Placement Method: Direct Discharge
Sample Locations: 58' N & 108' W of SE corner
Placement Location: Paving
Result Specification Test Method
6.0 3-5 ASTM C143
4.2 4-6 ASTM C231
93 ASTM C1064
80 ASTM C1064
ASTM C138
Laboratory Test Data Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
2 1 6.00 28.27 06/16/2005 7 110,400 3,900
2 2 6.00 28.27 07/07/2005 28 141,240 4,990
2 3 6.00 28.27 07/07/2005 28 143,580 5,080
Average 5,040
Comments: Not tested for plastic unit weight,
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT teat methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Tset results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 2 of 4 =~.£,,~
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94051190.0029
Service Date: June 9, 2005
Client: Coppell Trade Center LP
Attn: Bennet Ratliff
5055 Keller Spdngs Rd Ste 300
Addison TX 75001
'lrefracon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: July 12, 2005
Project: Coppell Trade Center - Bldg C
NWC Sandy Lake/Freeport Pkwy
Coppell, TX
Project Number: 94051190
Material Information
Specified Strength: 3000 psi (~ 28 Days
Batch Time: 8:44am Plant: 141
Supplier: TXI
Truck No: 110
Mix I.D. No.: 8206
Water Added Onsite Before Test: 10 Gallons
Field Test Date
Test
Result
Slump, inches: 6.25
Air Content, %: 4.6
Concrete Temperature,° F: 93
Ambient Temperature, o F: 81
Plastic Unit Weight, pcf: 144.0
Ticket No: 59694
Sample Information
Sample Time: 9:44am Date Cast: June 9, 2005
Technician: Burl E. Thomas
Weather Conditions: Clear
Accumulative Yards: 230
Placement Method: Direct Discharge
Sample Locations: 33' N & 320' W of SE property comer
Placement Location: Paving
Specification
3-5
4-6
Test Method
ASTM C143
ASTM C231
ASTM C1064
ASTM C1064
ASTM C138
Laboratory Test Data Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
3 1 6.00 28.27 06/16/2005 7 113,730 4,020
3 2 6.00 28.27 07/07/2005 28 141,410 5,000
3 3 6.00 28.27 07/07/2005 28 139,840 4,950
Average 4,980
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusrvely for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 3 of 4
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94051190.0029
Service Date: June 9, 2005
Client: Coppell Trade Center LP
Attn: Bennet Ratliff
5055 Keller Springs Rd Ste 300
Addison TX 75001
'lrerracon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 830-1010
Report Date: July 12, 2005
Project: Coppell Trade Center - Bldg C
NWC Sandy Lake/Freeport Pkwy
Coppell, TX
Project Number: 94051190
Material Information
Specified Strength: 3000 psi ~ 28 Days
Batch Time: 10:25am Plant: 141
Supplier: TXI
Truck No: 111
Mix I.D. No.: 8206
Water Added Onsite Before Test: 10 Gallons
Water Added Onsite After Test: 0 Gallons
Ticket No: 59876
Sample Information
Sample Time: 11:35am Date Cast: June 9, 2005
Technician: Burl E. Thomas
Weather Conditions: Clear
Accumulative Yards: 340
Placement Method: Direct Discharge
Sample Locations: 35' N & 280' E of SE property comer
Placement Location: Paving
Field Test Data
Test Result Specification Test Method
Slump, inches: 4.50 3-5 ASTM C143
Air Content, %: 4.0 4-6 ASTM C231
Concrete Temperature, o F: 95 ASTM C1064
Ambient Temperature, o F: 87 ASTM C1064
Plastic Unit Weight, pcf: ASTM C138
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
4 1 6.00 28.27 06/16/2005 7 112,320 3,970
4 2 6.00 28.27 07/07/2005 28 145,830 5,160
4 3 6.00 28.27 07/07/2005 28 149,850 5,300
Average 5,230
Comments: Not tested for plastic unit weight.
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Burl E. Thomas
Report Distribution:
(1) Coppell Trade Center LP
(1) TechniSlructures
(1) City of Coppell TX
(1) City of Coppell TX
(1) Men'iman Assoc Inc
(1) McFadden & Miller
(1) Macatee Engineering Ir~c
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusiveJy for the use of the client
indicated above and shall not be reproduced except in full without the wriQen consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
reatedals.