Loading...
SS9901-CS040614 (2)Turner Collie .. Braden Inc. T ,A SMITTAL To: From: Date: Job No.: Subject: See Distribution George Cisneros, P.E. - TCB June 14, 2004 052 131124.0001 04000.A123 (2.1) Deforest and Sandy Lake Wastewater Lift Stations and Force Main Improvements Force Main Line D Shop Drawing Review Comments Submittal No. 1 TCB has the following comments on this submittal: Description Status Comment HDPE Pipe & Fittings No Exceptions Taken 4" Gate Valve No Exceptions Taken Combination Sewage No Exceptions Taken Air Release Valve Precast Manhole Rejected Per plans, 5-foot manholes are to be used for the air valves; MH Pipe to Manhole Rejected Per City's Sheet SD 21, Contractor to install Connector Kor-n-seal boot assembly; MH Rubber Gasket for Rejected Per City's Sheet SD 21, manhole section Section Joints joints to be sealed with Ramnek strips; Lifting Bodies with No Exceptions Taken Eyelinks or Chains 4500 psi Concrete Mix No Exceptions Taken Design Manhole Ring & Cover No Exceptions Taken Flange Bolt & Gasket No Exceptions Taken Set Megalug Retainer No Exceptions Taken Gland Trench Excavation & Submit Specified Item Shoring Safety Plan Training Certification Submit Specified Item in HDPE Fusion Joining 30" Gate Valve Submit Specified Item 4000 psi Concrete Make Corrections Noted State use; Batch Design When you m-submit the shop drawings, please address all comments and submit seven (7) copies to this office. Distribution: [X] 2 copies of submittal to the City IX] 4 copies of submittal to Mastec [X] I copy of submittal to TCB file [ ] Other