Coppell Trade-LR050726CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94051190.0080
Service Date: July 18, 2005
Client: Coppell Trade Center LP
Attn: Bennet Ratliff
5055 Keller Springs Rd Ste 300
Addison TX 75001
'lrerracon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: July 26, 2005
Project: Coppell Trade Center - Bldg C
NWC Sandy Lake/Freeport Pkwy
Coppell, TX
Project Number: 94051190
Material Information
Specified Strength: 3000 psi ~ 28 Days
Batch Time: 12:47pm Plant: 141
Supplier: TXI
Truck No: 803 Ticket No: 83549
Mix I.D. No.: 9506
Water Added Onsite Before Test: 15 Gallons
Field Test Data
Test
Sample Information
Sample Time: 1:30pm Date Cast: July 18, 2005
Technician: CharlesA. Patterson
Weather Conditions: Mostly sunny
Accumulative Yards: 10
Placement Method: Direct Discharge
Sample Locations: Footings A.3/2
Placement Location: Retaining Wall Beam W of building &
footings
Slump, inches:
Air Content, %:
Concrete Temperature,° F:
Ambient Temperature, o F:
Plastic Unit Weight, pcf:
Result Specification Test Method
4.75 3-5 ASTM C143
3.3 3-7 ASTM C231
94 ASTM Cl 064
90 ASTM C1064
ASTM C138
Laboratory Test Data Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
1 1 6.00 28.27 07/25/2005 7 94,510
1 2 08/15/2005 28
1 3 08/15/2005 28
1 4 09/12/2005 56
3,340
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
. CONCRETE COMPRESSIVE STRENGTH TEST
Client: Coppell Trade Center LP
Project Number:94051190
Report Number: 94051190.0080
Comments (cont'd):
Comments: Not tested for plastic unit weight.
Services - Obtain samples of fresh concrete at the placement locations, pen~orm required field tests and cast compressive
strength samples.
Technician: Chades A. Patterson
Report Distribution:
(1) Coppell Trade Center LP (1) Merriman Assoc Inc
(1) TechniStructures (1) McFadden & Miller Reviewed by:
The tests were ,performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the ~ocation(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 2 of 2