Coppell Trade-LR050816CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94051190.0080
Service Date: July 18, 2005
Client: Coppell Trade Center LP
Attn: Bennet Ratliff
5055 Keller Spdngs Rd Ste 300
Addison TX 75001 ~'~1, TX
94051190
Material Information
Specified Strength: 3000 psi @ 2
Batch Time: 12:47pm
Supplier: TXI
Truck No: 803 Ticket No: 83549
Mix I.D. No.: 9506
Water Added Onsite Before Test: 15 Gallons
'1 rerracon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: August 16, 2005
Project: Coppell Trade Center- Bldg C
NWC Sandy ~ ....
Project Number:
~rmation
Sample Time: 1:30pm Date Cast: July 18, 2005
Technician: Charles A. Patterson
Plant: 141 Weather Conditions: Mostly sunny
Accumulative Yards: 10
Placement Method: Direct Discha~le
Sample Locations: FootingsA.3/2
Placement Location: Retaining Wall Beam W of building &
footings
Field Test Data
Test
Slump, inches:
Air Content, %:
Concrete Temperature,O F:
Ambient Temperature, o F:
Plastic Unit Weight, pcf:
Laboratory Test Data
Result Specification Test Method
4.75 3-5 ASTM C143
3.3 3-7 ASTM C231
94 ASTM C1064
90 ASTM C1064
ASTM C138
Set Specimen Diameter Area
No. ID (inches) (sq. inches)
1 1 6.00 28.27
Age at Maximum Compressive
Date Test Load Strength
Tested (days) (lbs) (psi)
07/25~2005 7 94,510 3,340
1 2 6.00 28.27 08/15/2005
28 122,570 4,330
28 121,530 4,300
Average 4,320
56
The tests were performed in general accordance with applicable ASTM, AASHTO, ar DOT test methods. This report is exclusively for the use of the client
indicated above and shall nut be reproduced except in full without the written consent of our company. Test resuEs transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 2
· CONCRETE COMPRESSIVE STRENGTH TEST
Client: coppell Trade Center LP
Comments (cont'd):
lr rr can
Project Number:94051190
Report NumbeF. 94051190.0080
Comments: Not tested for plastic unit weight.
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Chades A. Patterson
Report Distribution:
(1) Coppell Trade Center LP
(1) TechniStructures
(1) city of Coppell TX
(1) City of Coppell TX
(t) Merriman Asset Inc
(1) McFadden & M;ller
(1) Macatee Engineering Inc
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and ara not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 2 of 2