Coppell Trade-LR050812CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94051190.0093 Service Date: August 4, 2005 Client: Coppell Trade Center LP Attn: Bennet Ratiiff 5055 Keller Springs Rd Ste 300 Addison TX 75001 'lrerracon 8~O1 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Report Date: August 12, 2005 Project: Coppell Trade Center - Bldg C NWC Sandy Lake/Freeport Pkwy Coppell, TX Project Number: 94051190 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 6:06am Plant: 141 Supplier: TXI Track No: 68 Ticket No: 94705 Mix I.D. No.: 2806 Water Added Onsite Before Test: 0 Gallons Water Added Onsite After Test: 0 Gallons Sample Information Sample Time: 6:33am Date Cast:August 4, 2005 Technician: Bradley W. Hatch Weather Conditions: Clear Accumulative Yards: 10 Placement Method: Direct Discharge Sample Locations: See attached sketch Placement Location: Footings @ B, B.5, C, C.5, D, D.5, D.8, E.2/1; F/1.2; Pavement, see attached sketch Field Test Data Test Result Specification Test Method 5.25 3-5 ASTM C143 8.2 3-7 ASTM C231 93 ASTM C1064 79 ASTM C1064 ASTM C138 Slump, inches: Air Content, %: Concrete Temperature, O F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 1 1 6.00 28.27 08/11/2005 7 91,260 3,230 I 2 6.00 28.27 08/11/2005 7 92,600 3,270 Average 3,250 1 3 09/01/2005 28 1 4 09/01/2005 28 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the crient indicated above and shall not be reproduced except in full without the written ccnsent of our ccmpany. Test results transmitted herein are only applicable to the actual samples tested at the Iccation(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CONCRETE COMPRESSIVE STRENGTH TEST Client: Coppell Trade Center LP Comments (cont'd): 'lrerracan ProJect Number:94051190 Report Number: 94051190.0093 Comments: Not tested for plastic unit weight. NOTE: Superintendent was notified of air contetn. Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94051190.0093 Service Date: August 4, 2005 Client: Coppell Trade Center LP Attn: Bennet Ratliff 5055 Keller Springs Rd Ste 300 Addison TX 75001 rEffar'on 8901 Carpenter Fro/y, Sts #100 Dallas, Texas 75247 (214) 630-1010 Report Date: August 12, 2005 Project: Coppell Trade Center- Bldg C NWC Sandy Lake/Freeport Pkwy Coppell, TX Project Number: 94051190 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 7:30am Plant: 141 Supplier: TXI Truck No: 837 Ticket No: 94817 Mix I.D. No.: 2806 Water Added Onsite Before Test: 0 Gallons Water Added Onsite After Test: 0 Gallons Field Test Data Test Result Slump, inches: 5.00 Air Content, %: 6.2 Concrete Temperature, o F: 94 Ambient Temperature, o F: 81 Plastic Unit Weight, pcf: Sample Information Sample Time: 8:02am Date Cast:August 4, 2005 Technician: Bradley W. Hatch Weather Conditions: Clear Accumulative Yards: 120 Placement Method: Direct Discharge Sample Locations: See attached sketch Placement Location: Footings @ B, B.5, C, C.5, D, D.5, D.8, E.2/1; F/1.2; Pavement, see attached sketch Specification Test Method 3-5 ASTM C143 3-7 ASTM C231 ASTM C1064 ASTM C1064 ASTM Cl 38 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 2 1 6.00 28.27 08/11/2005 7 103,310 3,650 2 2 6.00 28.27 08/11/2005 7 103,660 3,670 Average 3,660 2 3 09/01/2005 28 2 4 09/01/2005 28 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the usa of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the pmpetties of other apparently similar or Identical materials. Page 3 of 4 o~.~u~-~,, , CONCRETE COMPRESSIVE STRENGTH TEST Client: Coppell Trade Center LP ' rerracorl Project Number:94051190 Report Number: 94051190,0093 Comments (cont'd): Comments: Not tested for plastic unit weight. Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Bradley W, Hatch Report Distribution: (1) Coppell Trade Center LP (1) TechniStruct ures (1) Cily of Coppell TX (1) City of Coppell TX (1) Merriman ASSO¢ Inc (1) McFadden & Miller (1) Macatee Engineering Inc Rober~ D. Ray, S.E.T./' Senior Project Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of uther apparently similar or identical materials. Page 4 of 4 STREET HEADER SPECIFICATIONS R2g.50'- R1. 24' 20.00' 118.00'