Loading...
ST9703-LR050901 one Engineering 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6500 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630-9745 CONCRETE COMPRESSIVE STRENGTH TEST Client: City' of Coppell Ms. Suzan Taylor PO Box 9478 Coppell TX 75019 Report No.: 238841 Project No.: 0510377 Date of Service: 08/02/2005 Report Date: 09/01/2005 Project: MacArthur Boulevard Widening ST 97-03 Seth, ices: Obtain samples of flesh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. CONTRACTOR: JRJ Paving CONCRETE SUPPLIER: LMC pi~¥r: 7 SPECIFICATION REQUIREMENTS STRENGTm 3600 psi ~ 28 Days SLUMP (in): 3" - 5" AVa (%): 3% - 6% TEST METHOD: ASTM C- 172 ASTM C-31 ,.~ 1 ~ ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-1231 ASTM C-39 PROJECT DATA MEASURED M1XDESIGN I.D.: 1701 SLUMP PLACEMENT DATE: 08/02/2005 (inches) WEATHER CONDITIONS: Clear 4.0 TIME SAMPLED: 9110am BATCH TIME: 8:37am TEMPERATURE (F) - Am 88 E CONCRETE: 87 F XaVC~ZNO: 947 TICKZTNO: 7155007 AIR CONTENT (%): 4.4 UNIT WE1GHT (pcf): NA OVERALL PLACEMENT LOCATION: Paving, leave-out areas, MacArthur Boulevard center median areas, Stations 27+34, 26+34, and 31+60; center median area, Station 23--23 to 23+10 SAMPLE LOCATION: REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" MacArthur Boulevard, center median area, Station 27+34 CYLINDER MARKED DATE AGE DIAMETER SET NO. TESTED (days) (inches) 1 1 08/09/2005 7 6.00 1 2 08/30/2005 28 6.00 I 3 08/30/2005 28 6.00 MAXIMUM COMPRESSIVE AREA LOAD STRENGTH FRACTURE (sq.in.) (lbs. force) (psi) TYPE 28.26 90980 3220 Unbonded Cap 28.26 123540 4370 Unbonded Cap 28.26 124600 4410 Unb0nded Cap Average 4390 1 4 Hold Technician: Pat Parks Report Distribution: (1) Cit3, of Coppell (1) City of Coppel] Started: 8:30am Finished: l 0:45m'n K. Scott Watson, AET CMT Operations Manager LIMITATIONS; Thc test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality '' otc oran otherfeamreofsmilarsubjectmagtcrpr°vidcdbypers°ns°rc°ndt°ns°verwhichwehaven°e°ntr°hOurlettersandrep°rtsarc (compos~non..appearance, .) Y .... rl ti ehall nm be re.roa--~a except in f~ll without the written approval of ROBe Engineering Services, Ltd. Pa~e 1 of 1 one Engineering 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630-9745 CONCRETE COMPRESSIVE STRENGTH TEST Client: City of Coppell Report No.: 238772 Ms. Suzan Taylor Project No.: 0510377 PO Box 9478 Date of Service: 08/01/2005 Coppell TX 75019 Report Date: 09/01/2005 Project: MacArthur Boulevard Widening ST 97-03 Obtain samples of fresh concrete at the placement locations, perfonm required field testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA STRENGTH: SLUM~ (in): AIR (%): TEST METHOD: COhq'RACTOR: JRJ Paving CONCRETE SUPPLIER: TXI PLANT: 141 SPECIFICATION REQUIREMENTS 3600 psi ~ 28 Days i" - 4" 3% - 6% ASTM C- 172 ASTM C-31 ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-1231 ASTM C-39 MEASURED MIX DESIGN I.D.: 8274 SLUMP PLACEMENT DATE: 08/01/2005 (inches) WEATHER CONDITIONS: SutTny 6.0 TIME SAMPLED: 9:19am BATCHTIME: 8:46am TEMPERATURE (F)-AIR 81 F CONCRETE: 93 ~ TRUCKNO: 37 TICKET NO: 92306 AIR CONTENT (%): 5.4 UNITWEIGHT(pclD: NA OVEIIALL PLACEMENT LOCATION: Paving, South MacAa~hur Boulevard east mm lane, Station 28+50 to 31+50 SAMPLE LOCATION: Station 39+36 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" CYLENDER MAXIMUM COMPRESSIVE MARKED DATE AGE DIAMETER AREA LOAD STRENGTH FRACTURE SET NO. TESTED (days) (inches) (sq.in.) (lbs. force) (psi) TYPE 1 1 08/08/2005 7 6.00 28.26 103120 3650 Unbonded Cap 1 2 08/29/2005 28 6.00 28.26 134520 4760 Unbonded Cap 1 3 08/29/2005 28 6.00 28.26 138740 4910 Unbonded Cap Average 4840 1 4 Hold Water added at site: 15 gallons Technician: Osvaldo Flores Report Distribution: (1) City of CoppeII (1) City of Coppell Started: 8:15am Finished: 10:00am CMT Operations Manager LEM~TAT1ONS: The test results presented herein were prepared based upon the specific samples provided for testing. We ~ssume no responsibility for variation in quality (composition, appearance, etc) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall nm be reproduced except in f~ll without the written approval of Rone Engineering Services, Ltd 01SS Page 1 ofl i one Eng,neenng 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. IS0, Houston, TX 77040 Corporate Phone: (214) 630-9745 CONCRETE COMPRESSIVE STRENGTH TEST Client: Project: City of Coppell Ms. Sttzan Taylor PO Box 9478 Coppell TX 75019 MacArthur Boulevard Widening ST 97-03 Report No.: 238565 Project No.: 0510377 Date of Service: 07/29/2005 Report Date: 09/01/2005 Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring samples back to the laboratory for curing and tesfing in accordance with applicable standards. PROJECT DATA STRENGTH: SLUMP (in): TEST METHOD: CONTRACTOR: JRJ Paving CONCRETE SUPPLIER: TX~[ P LA N~I': 15 1 SPECIFICATION REQUIREMENTS 3600 psi ~ 28 Days 3" - 5" 3% - 6% ASTM C-172 ASTM C-31 ASTM C-143 ASTM C-231 ASTM C- 1064 ASTM C-1231 ASTM C-39 MIX DESIGN I.D.: 8274 MEASURED SLUMP PLACEMENT DATE: 07/29/2005 (inches) WEATHER CONDITIONS: Partly cloudy 4.5 TIME SAMPLED: 7:20air BATCH TIME: 6:33am TEMPERATURE (F)- AIR 74 F CONCRETE: 80 F mUCK NO: 826 T~Cm~T NO: 30767 AIR CONTENT (%): 4.5 UNITWEIGHT(pcf~: NA OVERALL PLACEMENT LOCATION: Paving, MacArthur Boulevard, south side of street, inside lane next to median, Station 20+88 to 27+20 SAMPLE LOCATION: Station 20+93 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" CYLINDER MAXIMUM COMPRESSIVE MARKED DATE AGE DIAMETER AREA LOAD STRENGTH FRACTURE SET NO. TESTED (days) (inches) (sq.in.) (lbs. force) (psi) TYPE 1 1 08/05/2005 7 6.00 28.26 100770 3560 Unbonded Cap 1 2 08/26/2005 28 6.00 28.26 134590 4760 Unbonded Cap 1 3 08/26/2005 28 6.00 28.26 128670 4550 Unbonded Cap Average 4660 1 4 Hold L[iv[FfATIONS: The test results presented herein were prepared based upon the specific samples provided for testing We assume no responsibility for variation in quality (composition, appearance, etc) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. 01SS Page I of 2 - one Engineenng 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630-9745 CONCRETE COMPRESSIVE STRENGTH TEST Client: Project: City of Coppell Ms. Suzan Taylor PO Box 9478 Coppell TX 75019 MacArthur Boulevard Widening ST 97-03 Report No.: 238565 Project No.: 0510377 Date of Service: 07/29/2005 Report Date: 09/01/2005 Services: Obtain samples of fresh concrete at the placement locations, perform requ red field testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA CONTRACTOR: JRJ Paving CONCRETE SUPPLIER: T]XI PLANT: 151 SPECIFICATION REQUIREMENTS STRENGTH: 3600 psi ~ 28 Days SLUMP (in): 3" - 5" AIR (%): 3% - 6% TEST METHOD: ASTM C- 172 ASTM C-31 ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-1231 ASTM C-39 MEASURED MIX DESIGN I.D.: 8274 SLUMP PLACEMENT DATE: 07/29/2005 (inches) WEATHER CONDITIONS: Partly cloudy 4.5 TIME SAMPLED: 10:40am BATCHTIME: 9:54am TEMPERATURE (F) - AIR 89 F CONCRETE: 86 F TRUCK NO: 101 TICKET NO: 91117 AIR CONTENT (%): 4.6 UNITWEIGHT (pc0: NA OVEIL4.LL PLACEMENT LOCATION: Paving MacArthur Boulevard, south side of streeg inside lane next to median, Station 20+88 to 27+20 SAMPLE LOCATION: Station 25+53 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" CYLINDER NL~DI2IMUM COMPRESSWE MARKED DATE AGE DIAMETER AREA LOAD SII~3ENGTH FRACTURE SET NO. TESTED (days) (inches) (sq.in.) (lbs. force) (psi) TYPE 2 1 08/05/2005 7 6.00 28.26 99530 3520 Unbonded Cap 2 2 08/26/2005 28 6.00 28.26 125450 4440 Unbonded Cap 2 3 08/26/2005 28 6.00 28.26 131370 4650 Unbonded Cap Average 4550 2 4 Hold Technician: Pat Parks Report Distribution: (1) City of Coppell (1) City of Coppell Started: 6:30am Finished: 12:15pm (/~ngin~ring ~'J~n Cr~'sy, ~ET / LIMITATIONS: The test results presented herein were prepared b~sed upon the specific samples provided for tosting We assume no responsibiliW fur variation in quality (composition, appearance, etc) or any other feature of similar subJeCT matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd Page 2 of 2