ST9302-LR 990617ALPHA TESTING, INC.
2209 Wisconsin St., Suite 100
Dallas, Texas 75229
972/620-8911 - 972/263-4937 (Metro)
FAX: 972/406-8023
REPORT OF FIELD
COMPACTION TESTS
TESTED FOR
CITY OF COPPELL
COPPELL, TEXAS
DATE 6/17/99
PROJECT
SANDY LAKE ROAD
PROJECT NO. ST 93-02
COPPELL, TEXAS
OUR REPORT NO.
98881-38
TEST DATA:
TEST ~ ELEV. SOIL ID OPTIMUM MAXIMUM LAB IN PLACE IN PLACE PERCENT
NO. DATEDEPTH~ NUMBER MOISTURE DRY DENSITY MOISTURE DRY DENSITY COMPACTION COMMENT'
% PCF % PCF
98 6/17/99 FG-5.0 7 21.5 99.6 22.2 96 96 2-A
99 6/17/99 FG-4.0 7 21.5 99.6 24.7 95. 95 2-A
100 6/17/99 FG-3.0 7 21.5 99.6 21.5 98 98 2-A
101 6/17/99 FG-2.0 5 13.5 111.9 14.4 106 95 2-A
102 6/17/99 FG-1.0 5 13.5 111.9 17.0 109 98 2-A
103 6/17/99 FG-3.0 3 13.3 117.6 15.1 116 99 2-A
104 6/17/99 FG-2.0 5 13.5 111.9 17.5 112 100 2-A
TEST LOCATION:
98 30" WATER LINE AT STATION #47 + 40
99 30" WATER LINE AT STATION //47 + 35
100 30" WATER LINE AT STATION //47+30
101 30" WATER LINE AT STATION //47+25
102 SANDY LAKE ROAD AT STATION //38+50
103 SANDY LAKE ROAD AT STATION //38 +00
104 SANDY LAKE ROAD AT STATION //37 +50
1. FILL
2. NATURAL SUBGRADE
3. LIME STABILIZED
4. CEMENT TREATED
e A. IN PLACE PERCENT MOISTURE AND PERCENT COMPACTION COMPLY WITH SPECIFICATIONS
B. PERCENT COMPACTION DOES NOT COMPLY WITH SPECIFICATIONS
C, PERCENT IN PLACE MOISTURE DOES NOT COMPLY WITH SPECIFICATIONS
D. RETEST