ST9302-LR 990204ALPHA TESTING, INC.
2209 Wisconsin St., Suite 100
Dallas, Texas 75229
972/620-8911 - 972/263-4937 (Metro)
FAX: 972/406-8023
TESTED FOR
CITY OF COPPELL
COPPELL, TEXAS
REPORT OF FIELD
COMPACTION TESTS
DATE 2/4/99
PROJECT
SANDY LAKE ROAD
PROJECT NO. ST 93-02
COPPELL, TEXAS
OUR REPORT NO,
98881-14
TEST DATA:
TEST '""~ ELEV. SOIL ID OPnMUM MAXIMUM LAB IN PLACE IN PLACE PERCENT
NO, DATE~ NUMBER MOISTURE DRY DENSITY MOISTURE DRY DENSITY COMPACTION COMMENT'*
% PCF % PCF
38 2~4~99 FG-3.0 3 13.3 117.6 13.6 117 100 I-A
39 2~4~99 FG-2.0 3 13,3 117.6 13.2 112 95 1-A
40 2/4/99 FG-1.0 3 13.3 117.6 14.2 113 96 1-A
:ATION: UTILITIES
38 16" WATER LINE AT STATION //102+14
39 16" WATER LINE AT STATION //102+04
40 16" WATER LINE AT STATION //101 +94
1. FILL
2. NATURAL SUBGRADE
3. LIME SI*ABILIZED
4, CEMENT rflEATED
A. IN PLACE PERCENT MOISTURE AND PERCENT COMPACTION COMPLY WITH SPECIFICATIONS
8. PERCENT COMPACTION DOES NOT COMPLY WITH SPECIFICATIONS
C. PERCENT IN PLACE MOISTURE DO~S NOT COMPLY WITH SPECIFICATIONS
D. RETEST
Geo~E~ · ~/Vk3tetials Tes'//ng · ~ta/~ · ~