Loading...
Coppell CC 1B1-CS010914 (3) MEMORANDUM FROM THE DEPARTMENT OF PUBLIC WORKS To: From: RE: Larry Davis, Construction ln~eetor Engineering Danny Hightower, Utilities Division Public Works September 14, 2001 Walk-thru Koll Center 800 Freeport 9/12/01 e '-[4. 16. 18. S.E. need pad around valve stack to vault. Irrigation ne~lsn~t-~m~ DC on all. ~L~& D~ Need caps on curb top stacks. ~l~aintmet. er can lid bl-~and vault lids blue and valve stacks blue on MLV valves. Paint on curb in blue IRR & DOM. Test DC in vaults and domestic and irrigation. MLV to vault needs valve extension. Mark on curb MLV in blue. Need plugs in all ball valves DC and vaults. Need lock latch on all vault lids. Uncover valves to FH and stub out onHammo~.~' Uncover FH or raise FH so Fire D~partment can open. Block under wheel valve in vaults. Seal vaults at pipe and seam. Clean meter cam below lower fittings. ~I-~ata-and.lli~ove~ Cit~sewer clcanout for inspection. Back fill around FH 2'~ from SE corner. Need letter from landscaper stating that he will not cover valves or manholes. Raise meter can to curb high to Building 2. Reset Ftt markers in street (loose). Need valve extemion on FII valve SW side of Building 2 - 1' FH. ~× CITY OF COPPELL Pf]BLlC WORg$ DEPA~~ 22.~eed valve extension on FH valve SW side of building 2 - 2" FFI. 23] '~Need valve extension on MLV at NE side of Building 3. 24. ~Need valve extension on FH east of Building 3 - 2'~ FH. ~. Oil name FH east of Bui]dln_~ 3 - 2'~ FH. 26. ~- Need valve extemion at NE of Buildin~ 1 FH. 2~ ~4'ain lille water valve stack l~pair at ]~l~i]tlln~ 1 llext to FLV to Buildin~ 1. /Need to repair City main line sewer DO at Buildings 1 &2. Need extension on north FH at Buildln~ 1 & 2 in MID. 304/'~ Clean 2'a manhole of dirt from south CO. ~l'nnhole north of buildin~ 3 needs chimney seal and rain pan and concrete around top outside of manhole. Note: When ready for follow-up or if you have any questiom vail (972) 30~-3.~4~ - Danny Hightower. CITY OF COPPEt t P~BLIC F~'ORI~ DEPARTMENT