Follow-up Walk-thru Coppeli Crossing Lot 4 6/25/01
2.
3.
4.
Need 1" meter loop to set 1" meter for domestic.
Need 5/8" meter loop to set 5/8" meter for irrigation.
Need to test DC for irrigation and have paperwork.
Manhole chimney seal on 18" sewer line bottom ring loose.
Note: Call 972-304-3545, Danny Hightower, when ready.
CITY OF COPPELL PUBLIC WORKS DEPARTMENT
MESSAGE CONFIRMATION
06/2G/0i 08:11
IDzCITY OF COPPELL
DATE
S,R-TIME DISTANT STATION ID MODE PAGES
00'21" CITY OF COPPELL CALLING O1
RESULT
OK 0000
Issued: inished:
Name:
Phone Number: (HM)
WATER
Employee: ]~k/~ Grid ~p:
(WK):
Check for: Accuracy test: Meter Leak:
Initial meter relocation inspections
Check water pressure:
Re-read
1. Backflow insn. 2. Reoair
4. Other
Backflow Insp.
Bldlow Cert. Date
Re-Cert. Date
A. Main Line A. Pump A. Line Locate
B. Valves B. Water Tower B. Line Locate
C. Sereice Line C. Samples C. Tap
D. Hydrants D. Equ~ment D Excavation
E. Safety
5. Reason for failure: A. Electxolysis B. New Construction C Poor Installation D. Other
6. List of safety equipment at site if applicable:
A. Barricades B. Cones C. Tape D. Lights E. Other
Request for Servic.e~s:
7. If Meter/Service Leak: Classify: - City:. Customer
A. Water Loss (estimate): GPM
B. Was Water Metered: Yes
C. Was Customer Notified: Verbally
Fire plug flushing
No
Total Gallons
Doorknocker -
8. If Meter Change Out:
Vehicle/Equipment Used
Unit # Miles Ihs Equipment
A. Old Meter # Reading
B. New Meter # Reading
C. Old Meter Size~ype:
E. Type of work performed or findings:
D New Meter Size/Type
9. If mainline or deep service repair, descn'be type of pipe or service line and condition:
I0. Man-hours:
11. List Materials Used:
Crew Members.
12. If you had an accident"Incident while performing this request. Did you report it? Yes or no
13. Water Utilities meter inspection: pass or fail
14. How many trips to do task?
· ~6/19/01 19:01
CITY ' COPPELL ENGINEERING ~ CITY OF Cw, PELL
N0.194
P,O. BOX d78
255 PARKWAY BLVD.
COPPF.,LL, TX 75019
PAX NO. (972) 304-3570
ENGINEERING DEPARTMENT
TO: r; .~,,~_~
FAX NO.:
TRANSMIT'rED BY:
FROM:
PHONE NO.:~
DATE:
TIME: ....
NLrMBER OF PAGES (INCLUDING COVERSHEET):
IF YOU DO NOT KECEIVE ALL OF THE PAGES, PLEASE CALL (972) 304-3679.
£ng~neeriag. ~.x~ellence l~y Design
MEMORANDUM
FROM THE
DEPARTMF NT OF PUBLIC WORKS
Garreth Campbell, Construction Inspector g~n~neering
Danny Hightower, Utilities Division Public Works
April 19, 2001
Walk-thru Coppeil Crossing Block 1, Lot 4
Reset meter can on blow off; place dirt around can at ground level.
.~ 2. Plan~ call for 2' water meter service, l' moter was installed; no 2" bypass in
place
on
~ ~f~l" meter loop. In order to have !' meter, it must be approved by City on
[' ~.~ $~ (~ plan~ and service must be chan.~ed to 1".
~. Mark in red FHV on curb.
Place blue marker in street to mark FH.
Mark on curb MH in red at ail manholes.
2~d manhole from bark of building must be sealed.
2~d manhole needs to be grouted at pipe into manhole to stop inflow from ground
wa~r.
9. Locate covered manhole on 30" sewer line and call 972-304-3545 to check for work
needed after locate.
10. Place chimney seal on sewer manhole running 18" sewer line.
Note: Call 972-304-3~45, Danny Hightower, when ready for follow-up walk-thru.