CONCRETE CO, RE REPORT
REPORT DATE: 10/17/05 ~ ! SAMPLE DATE:
CLIENT: JBP, LP ~/~PROJECT
NO.:
5301 Village Creek Drive, Suite A
[
Piano, TX 75093 REPORT NO.:
10/14/05
308TXlK5
35
PROJECT:
~9nway 'lZ1 & K~dg~mo"~nt 4
Lewisville & Coppell, TX
METHOD OF TEST: ASTMC42 & Visual
SE&T TECHNICIAN: Mike Saint & Jeremy Speak
Attn: NealHeckel PAGE I OF '!
On the above date, representatives of SAM Engineering & Testing, LP. performed the following testing and inspection
services:
1. Two 1.75" diameter concrete cores (CC) were taken by SE&T from the existing pavement and were tested for
their Length (L)with the following results: ~, ~1~ ,~~
.CC #1 Deceleration Ln. - 121 & Plaza Blvd. AT 227'E. x 6'S. L = 11"
.CC #2 Deceleration Ln. - 121 & Plaza Blvd. AT 69'E. x 4'S. L = 11.25"
2. Based on the above data and our experience, the L of the tested CC ranged from 11" to 11.25" with an average
of 11.25". This range and average meet/exceed the minimum required 10" pavement thickness.
3. The location and number of CC were selected by SE&T and were backfilled with high-early-strength grout
by SE&T after codng.
~/ery Truly Yours,
~' ..... PhD PE
Sadik (SAM) AI-Musawe, M.Sc .......
Civil & Environmental Engineer
Texas Registration Number: 61893