Loading...
Vista Ridge 1R-8 D-LR051014 SAM ENGiNEERiNG & TESTING, L.P. ~ Serving The Geo-lndustry Since 1974 ,~ ~ 1115 Luke Street, Suite 100 '~_~' Irving, Texa/ 75061 ~ Phone: (972) 790-1910 FAX: (972) 790-0967 CONCRETE CO, RE REPORT REPORT DATE: 10/17/05 ~ ! SAMPLE DATE: CLIENT: JBP, LP ~/~PROJECT NO.: 5301 Village Creek Drive, Suite A [ Piano, TX 75093 REPORT NO.: 10/14/05 308TXlK5 35 PROJECT: ~9nway 'lZ1 & K~dg~mo"~nt 4 Lewisville & Coppell, TX METHOD OF TEST: ASTMC42 & Visual SE&T TECHNICIAN: Mike Saint & Jeremy Speak Attn: NealHeckel PAGE I OF '! On the above date, representatives of SAM Engineering & Testing, LP. performed the following testing and inspection services: 1. Two 1.75" diameter concrete cores (CC) were taken by SE&T from the existing pavement and were tested for their Length (L)with the following results: ~, ~1~ ,~~ .CC #1 Deceleration Ln. - 121 & Plaza Blvd. AT 227'E. x 6'S. L = 11" .CC #2 Deceleration Ln. - 121 & Plaza Blvd. AT 69'E. x 4'S. L = 11.25" 2. Based on the above data and our experience, the L of the tested CC ranged from 11" to 11.25" with an average of 11.25". This range and average meet/exceed the minimum required 10" pavement thickness. 3. The location and number of CC were selected by SE&T and were backfilled with high-early-strength grout by SE&T after codng. ~/ery Truly Yours, ~' ..... PhD PE Sadik (SAM) AI-Musawe, M.Sc ....... Civil & Environmental Engineer Texas Registration Number: 61893 This report is for the sole use of the client addressed. The use of our company name must receive pdor wdtten consent. This report applies only to the sump e tested and does not necessarily represent identical or similar samples.