Coppell Trade-LR051103CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94051190.0126 Service Date: October 5, 2005 Client: Coppell Trade Center LP Attn: Bennet Ratliff 5055 Keller Springs Rd Ste 300 Addison TX 75001 '1 rerracon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Report Date: November 03, 2005 Project: Coppell Trade Center - Bldg C NWC Sandy Lake/Freeport Pkwy Coppell, TX Project No.: 94051190 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 10:35am Supplier: TXI Truck No: 69 Mix I.D. No.: 8206 Water Added Onsite Before Test: Water Added Onsite After Test: Field Test Data Test Plant: 141 Ticket No: 131463 0 Gallons 0 Gallons Result Slump, inches: 5.00 Air Content, %: 5.0 Concrete Temperature, o F: 93 Ambient Temperature, o F: 83 Plastic Unit Weight, pcf: 144 Laboratory Test Data Set specimen Diameter Area No. ID (inches) (sq. inches) 1 I 6.00 28.27 Sa_~_.ple Information Sample Time: 11:02am Date Cast: October 5, 2005 Technician: Burl E. Thomas Weather Conditions: Hazy Accumulative Yards: 20 Placement Method: Direct Discharge Sample Locations: 3' W & 150' S of Building, NW corner Placement Location: Pavement, W of Building Specification Test Method 3-5 ASTM C143 4-6 ASTM C231 ASTM C1064 ASTM Cl 064 ASTM Cl 38 Age at Maximum Compressive Date Test Load Strength Tested (days) (lbs) (psi) 10/12/2005 7 89,710 3,170 1 2 6.00 28.27 11/02/2005 28 119,390 4,220 1 3 6.00 28.27 11/02/2005 28 122,130 4,320 Average 4,270 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Burl E. Thomas Report Distribution: (1) Coppell Trade Center LP (1) MelTiman Assoc Inc (1) TechnIStructures (1)McFadden&Mille~ ~eweweo Dy. ~ V ~ __~_ (1) city of Coppeit TX (1) Macatee Engineering Inc Robert D. Ray,~.E.T. (1) City of Coppell TX Senior Projec~anager The tests were pedormed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94051190.0147 Service Date: October 25, 2005 Client: Coppell Trade Center LP Attn: Bennet Ratliff 5055 Keller Springs Rd Ste 300 Addison TX 75001 ']rerracon 8901 Carpenter Frwy, Ste #100 Dal[as, Texas 75247 (214) 630-1010 Report Date: November 03, 2005 Project: Coppell Trade Center - Bldg C NWC Sandy Lake/Freeport Pkwy Coppell, TX Project No.: 94051190 Material Information Specified Strength: 4000 psi ~ 28 Days Batch Time: 6:50am Supplier: TXI Truck No: 803 Mix I.D. No.: 8206 Water Added Onsite Before Test: Water Added Onsite After Test: Plant: 41 Ticket No: 143515 0Gallons 0 Gallons Sample Information Sample Time: 7:21am Date Cast: October 25, 2005 Technician: Barry Cuble Weather Conditions: Clear, cold Accumulative Yards: 30 Placement Method: Direct Discharge Sample Locations: 20' N of S, 25' E of Curb Placement Location: Pavement: W Parking; 345' & 45' Building Porches at E.8-F/1-1.2, 6.5-7.5, 12.5-13.5, 18.5-19.5, 24.8-25 Field Test Data Test Result Slump, inches: 4.50 Air Content, %: Concrete Temperature,O F: 62 Ambient Temperature, o F: 40 Plastic Unit Weight, pcf: N/A Laboratory Test Data Set Specimen Diameter Area No. ID (inches) (sq. inches) 1 1 6.00 28.27 1 2 6.00 28.27 1 3 1 4 Specification Test Method 3-5 ASTM C143 3-6 ASTM C231 ASTM C1064 ASTM Cl 064 ASTM C138 Age at Maximum Compressive Date Test Load Strength Tested (days) (lbs) (psi) 11/01/2005 7 134,020 4,740 11/01/2005 7 130,050 4,600 Average 4,670 11/22/2005 28 11/22/2005 28 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the wriffen consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the Iccation(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. ,CONCRETE COMPRESSIVE STRENGTH TEST 'lrerracon Client: Coppell Trade Center LP Project Number:94051190 Report Number: 94051190.0147 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the wrk'ten consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identicat materials. Page 2 of 6 0~-~.~.o CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94051190.0147 Service Date: October 25, 2005 Client: Coppell Trade Center LP Attn: Bennet Ratliff 5055 Keller Springs Rd Ste 300 Addison TX 75001 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Report Date: November 03, 2005 Project: Coppell Trade Center- Bldg C NWC Sandy Lake/Freeport Pkwy Coppell, TX Project No.: 94051190 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 7:58am Plant: 41 Supplier: TXI Truck No: 716 Ticket No: 143616 Mix I.D. No.: 8206 Water Added Onsite Before Test: 10Gallons Water Added Onsite After Test: 0 Gallons Sample Information Sample Time: 8:47am Date Cast: October 25, 2005 Technician: Barry Cuble Weather Conditions: Sunny, cool Accumulative Yards: 130 Placement Method: Direct Discharge Sample Locations: 180' N of S, 35' E of Curb Placement Location: Pavement: W Parking; 345'& 45' Building Porches at E.8-F/1-1.2, 6.5-7.5, 12.5-13.5, 18.5-19.5, 24.8-2 Field Test Data Test Result Slump, inches: 5.25 Air Content, %: 3.8 Concrete Temperature,O F: 66 Ambient Temperature, o F: 42 Plastic Unit Weight, pcf: N/A Laboratory Test Data set specimen Diameter Area No. ID (inches) (sq. inches) 2 1 6.00 28.27 2 2 6.00 28.27 2 3 2 4 Specification Test Method 3-5 ASTM C143 3-6 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Age at Maximum Compressive Date Test Load Strength Tested (days) (lbs) (psi) 11/01/2005 7 103,020 3,640 11/01/2005 7 113,350 4,010 Average 3,830 11/22/2005 28 11/22/2005 28 The tests were pedormed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusivery for the use of the client indicated above and shall not bo reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. . CONCRETE COMPRESSIVE STRENGTH TEST 'lrerracon Client: Coppell Trade Center LP Project Number:94051190 Report Number: 94051190.0147 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shatl not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples*tested at the location(s) referenced and are not necessariJy indicative of the properties of other apparently similar or identical materials. Page 4 of 6 ~.,~.~, ~,~ CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94051190.0147 Service Date: October 25, 2005 Client: Coppell Trade Center LP Attn: Bennet Ratliff 5055 Keller Springs Rd Ste 300 Addison TX 75001 'l rracon 8901 Carpenter Fn/e/, Ste #100 Dallas, Texas 75247 (214) 630-1010 Report Date: November 03, 2005 Project: Coppell Trade Center- Bldg C NWC Sandy Lake/Freeport Pkwy Coppell, TX Project No.: 94051190 Material Information Specified Strength: 4000 psi (~ 28 Days Batch Time: 9:17am Plant: 41 Supplier: TXI Truck No: 716 Mix I.D. No.: 8206 WaterAdded Onsite Before Test: 10Gallons Water Added Onsite After Test: 0 Gallons Field Test Data Test Result Slump, inches: 5.00 Air Content, %: 3.8 Concrete Temperature, O F: 69 Ambient Temperature, o F: 56 Plastic Unit Weight, pcf: N/A Laboratorl~ Test Data Set Specimen Diameter Area No. ID (inches) (sq. inches) 3 1 6.00 28.27 3 2 6.00 28.27 3 3 3 4 Ticket No: 143735 Sample Information Sample Time: 10:35am Date Cast: October 25, 2005 Technician: Barry Cuble Weather Conditions:Bunny, cool Accumulative Yards: 220 Placement Method: Pump Sample Locations: Building Porch at E.8-F/6.5-7.5 Placement Location: Pavement: W Parking; 345' & 45' Building Porches at E.8-F/1-1.2, 6.5-7.5, 12.5-13.5, 18.5-19.5, 24.8-2 Specification 3-5 3-6 Test Method ASTM C143 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Age at Maximum Compressive Date Test Load Strength Tested (days) (lbs) (psi) 11/01/2005 7 100,610 3,560 11/01/2005 7 113,520 4,010 Average 3,790 11/22/2005 28 11/22/2005 28 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test msuits transmitted herein are only appliceble to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CONCRETE COMPRESSIVE STRENGTH TEST ll'erracon Client: Coppell Trade Center LP Project Number:94051190 Report Number: 94051190.0147 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Bamj Cuble Report Distribution: (1) Coppell Trade Center LP (1) Merdman Assoc (1) TechniStruotures (1) McFadden & Miller Reviewed by: (1) City of Coppell TX (1) Macatee Engineering Inc (1) City of Coppell TX se~b~or~P rD(~j (~c~Y 'E~a g ~ r The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This repod is exclusively for the use of the client indicated abo~ and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the Iocstion(s) referenced and are not necessarily indicative of the propedies of other apparently similar or identical materials. Page 6 of 6