Coppell Trade-LR051028CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94051190.0142
Service Date: October 20, 2005
Client:
Coppell Trade Center LP
Attn: Bennet Ratliff
5055 Keller Springs Rd Ste 300
Addison TX 75001
Report Date: October 28, 2005
Project:
rf fflilcon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Coppell Trade Center - BIdg C
NWC Sandy Lake/Freeport Pkwy
Coppell, TX
Project No.: 94051190
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 6:54am Plant: 41
Supplier: TXI
Truck No: 58
Mix I.D. No.: 8206
WaterAdded Onsite Before Test: 10Gallons
Water Added Onsite After Test: 0 Gallons
Field Test Data
Test Result
Slump, inches: 4.50
Air Content, %: 4.0
Concrete Temperature,° F: 83
Ambient Temperature, o F: 67
Plastic Unit Weight, pcf:
Laboratory Test Data
set Specimen Diameter Area
No. ID (inches) (sq. inches)
1 1 6.00 28.27
1 2 6.00 28.27
1 3
1 4
Ticket No: 140862
Sample Information
Sample Time: 7:41am Date Cast: October 20, 2005
Technician: Barry Cuble
Weather Conditions: Sunny, mild, light winds
Accumulative Yards: 20
Placement Method: Direct Discharge
Sample Locations: 10' N of Curb, 25' W of E curb
Placement Location: Pavement, NW Parking
Specification
3-5
Test Method
ASTM C143
ASTM C231
ASTM C1064
ASTM C1064
ASTM C138
Age at Maximum Compressive
Date Test Load Strength
Tested (days) (lbs) (psi)
10/27/2005 7 117,190 4,140
10/27/2005 7 110,500 3,910
Average 4,030
11/17/2005 28
11/17/2005 28
Comments: Not tested for plastic unit weight.
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Barry Cuble
Report Distribution:
(1) Coppell Trade Center LP
(1) TechniStructures
(1) Cily of Coppell TX
(1) City of Coppell TX
(1) Merriman Assoc ~nc
(1) McFadden & Miller
(1) Macetee Engineering Inc
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusivery for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials, o~.^c~o~.F~,.
Page 1 of 1