Northlake 635(2)-CS000823 MEMORANDUM
FROM THE
DEPARTMENT OF PUBLIC WORKS
To:
From:
Date:
RE:
Lanny Allison, Construction Inspector Engineering
Danny Hightower, Utilities Division Public Works
August 23, 2000
Walk-thru PSINet
e
11.
12.
13.
Need 2 domestic meters (2").
One (1) DC 2" needs cut off handles.
Seal inside vault on north side of building.
Clean out CO sewer on north side of building 20' from vault.
Need F.H. markers in street by all F.H. blue markers.
Manhole N.E. of building need rain pan out of bottom of manhole & clean bottom of
manhole.
F.H. valve at Lakeshore & Crestside dig up stack and reset with new pad cannot get
on valve.
Raise sewer manhole on Lakeshore middle of building to ground high & need chimney
seal.
Vault on east side of building needs new link seal on street side of pipe inside vault.
Drainage cleanout needs caps & pad on southeast corner of building.
Repair F.H. at back of building-will not cut off.
Valve stack on F.H. southwest of building cannot get on valve-repair with new pad.
**Cut & plug grease trap tied in to drainage.**
CITY OF COPPELL PUBLIC WORKS DEPARTMENT
MESSAGE
CONF I RMAT I ON
08/2~/00 08:10
IDzCITY OP COPPELL
DATE
08/23
S~R-TIME DISTANT STATION ID
00~22" CITY OF COPPELL
MODE PAGES RESULT
CALLING 01 OK 0000
214 584 5570
08/21×00 09:26 CITY OD COPPELL ENGINEERING ~ CITY OF COPPELL N0.5~2
DOl
MEMORANDUM
FROM THE
DEPARTMENT OF ENGINEERING
To:
Date:
RE:
Mike Martin, P.E., Azst. City Engineer
Glenn D. Hollowell, P.E., Asst. Public Works Director
Lanny ~ui~_on, Construction Inspector ~/~,~
Aukq~st 21, 2000
Walk-Thru for PSINet
A walk-~a'u for s~reets, u~ilities ~d drainage on the referenced project h~ been
scheduled for Tuesday, August 22. 2000 at 9:00 a,m.
If I can be of further assistance please let me know.
cc: James Cofer, TriDal Ltd. FAX 817/481-8195
Rle/sulxl/psi.wt