Loading...
Park Place-CS 910404April 4, 1991 Mr. Larry Davis Development Construction Inspector City of Coppell 732 Deforest Rd. P.O. Box 478 Coppell, Tx 75019 Re;' ~ace~ Ai~lts Dear Larry, C.W. Young Construction Co. retained us Thursday, April 8th 1991, to perform line acceptance testing in the Park Place Addition. The line segment tested was in Woodcrest Lane, (an 8" sanitary sewer) line "C" from station #8 + 31 to 13 + 06. The criteria used for acceptance testing on SDR35 was the current North Texas Council of Governments set of standard specifications, located in division 6 on pages 332 and 333. The line segment was approximately 475' in length with service lines capped at the property line. Our test procedure was to pump the line to 4 psig and allow the air to stabilize. The line was bled back to 3.5 psig and the time noted to begin the test. The C.O.G. standard for 475' of 8" SDR 35 is 4:26 minutes allowed time for a drop in pressure from 3.5 to 2.5. If a pressure drop of 1 psig occurs in less than 4:26 minutes, the line would not meet the standard, if a pressure drop is less than 1 psig in 4:26 minutes the line meet the test criteria established by C.O.G. and meets the standard. continued 515 N, Kealy Street 19350 FM 1093 (214) 436-4568 Lewisville,Texas 75057 · Richmond,Texas 77469 (713) 579-0074 Municipal and Utility Contractor's Services page 2 In testing this line segment, we noted a pressure drop of 1/4 pound during the 4:26 period of allowable loss. This amount of loss falls we]] within the C.O.G. guidelines. It is clear that the line has met the standards required and will perform as designed. If I can be of any further assistance, don't hesitate to call. c.c.C.W. Young c.c. Howard Pafford, City of Coppell GTS/nl 515 N. Kealy Street 19350 FM 1093 (214) 436-4568 tewisville,Texas 75057 · Richmond,Texas 77469 (7t3) 579-0074 equilibr/um with the temperature of the pipe walls. The pressure w/ii normaily drop slightly until equilibrium is obtained. During this period all assessable plugs should be checked with soap solution to detect any plug leakage. 5) Determine the rate of ulr loss by either the constant pressure method or the time pressure drop method. For the constant pressure method, air is supplied to the pipe test section at a rate suffi- cient to maintain a gauge pressure of 3.0 psi. The rate of air flow in cubic feet per minute is read directly by means ufa retometer. The rate of air flow must be corrected for pressure and temperature under standard conditions. 6) Upon completion of the test, the bleeder valve is opened and ail air is allowed to escape. Plugs should not be removed until afl air pressure in the test section has been released. Also no one should be allowed in the trench or manhole while the test is being conducted. (C) Constant Pressure Method: 1) Air is supplied to the pipe test section at a rate sufficient to mainta/n a gauge pressure of 3.0 psi. The rate of air flow ' - m cubic feet per minute is read directly by the means ufa retometer. The rate of air flow shall be corrected for pressure and tern- under standard conditions. 2) The requirements for air loss under the "Constant Pressure" method shaft be considered satisfied if the air loss does not exceed a rate of 0.003 cfm per square foot of internal pipe surface area with a total rate of air loss not greater than 2.0 cubic feet per minute, based on a wetted pipe. (D) Time Pressure Drop Method: 1) Air is slowly introduced into the section of plpPsi~O e air pressure is raised to ap- ' owed to stabilize for a period of two minutes. The air supply is disconnected and the test pressure allowed to decrease to 3.5 psig. The time required for the test pressure to drop from 3.5 psig to 2.5 psig is determined, and this time interval is then compared · · to the required time to determine ff the rate of ah' Ions is within the allowable. 2) Minimum holding times required per pipe diame- ter · re shown in the table "Duration Requirements for Air Testing.' (Note: Test times are independent of the line length once the minimum holding time has been reeched.) (4) Individuai Joint Test Method. Afl concrete sewer main 36* ~ ~ larger in dhuneter shall be 100% air tested at each The method of testing shaft be described in Item 6.7.2.(/). j ~ u,mu oe au' tested until the p~pe has been b~kffi{~l..{ shah be performed ss pipe inst~l!ption progresses. At no ~ installation exceed 100 feet fi'om the lnst joint tested. Iftbe pass the joint air test, necessary ropaire as recommended I manufacturer may be made ff approved by the ow~z~ m~l tim tested. Failure to pass the air test after r for rejection. At'DST t987 TABLE -- DURAT1ON REQUIREMENTS FOR AIR TESTING SPECIIqCAT1ON TIME REQUIRED FOR LOSS OF PRESSURE FROM 3.5 PSIG TO ?-5 PSIG FOR SIZE AND LENGTH OF FqPE INDICATION FOR Q=0.{X)3 4 1:53 597 1:53 1:53 1:53 1:53 1:53 1:53 1:53 - 1:53 6 2:50 398 2:50 2:50 2:50 2:50 2:50 2:50 2:50-- 2:50 8 3:47 298 3:47 3:37 3:47 3:47 3:48 4:26 4:26 10 4:43 239 4:43 4:43 4:43 4:57 5:56. 5:56 12 5:40 199 5:40 5:40 5:42 7:08 7:08 15 7:05 159 7:05 7:05 8:54 8:54 18 8:30 133 8:30 9:37 9:37 21 9:95 114 9:55 13:05 13:05 24 11:20 99 11:24 11:24 27 12:45 88 14:25 14:25 30 14:10 80 17:48 17:48 33 15:35 72 21:33 .21:33 36 17.'00 66 25:39 25:39 "This tatYm is based on T = 0.0850 DK/Q D = p~pe diameter, in. L = ~ of pipe be~rtcj tested, ff. ~ '"Te~ New Sewer Pipe Installation' by Roy E. Ramseier. This document is part of the ASTM Standards process and is for ASTM committee use only. It shall not be reproduced, in whole or in part, outside of the ASTM committee activities except with the approval of the chairman of the committee having jurisdiction or the President of the Society. Proposed Draft: A Date: 06-01-90 SUBCOMMITTEE: F17.62 PROJECT NO: 62-90-03 Subcommittee Letter Ballot Standard Test Method for Low-Pressure Air Test of Plastic Pipe Sewer Line 1. Scope 1.1 This test method defines procedures for testing plastic pipe sewer lines, using low-pressure air to demonstrate the structural integrity of the installed line. 1.2 This test method shall be performed on lines after connection laterals, if any, have been plugged and braced adequately to withstand the test pressure, and after the trenches have been backfilled for a sufficient time, not less than 30 days, to generate a significant portion of the ultimate trench load on the pipe line. The time between completion of the backfill operation and low-pressure air testing shall be determined by the approving authority. 1.3 This test method may also be used as a preliminary test, which enables the installer to demonstrate the condition of the line prior to backfill and further construction activities. 1.4 This test method is suitable for testing gravity-flow sewer pipe constructed of plastic pipe and fittings. 1.5 Thermoplastic pipe, pipe and reinforced plastic test method. reinforced thermosetting resin (RTRP) mortar (RTMP) pipe are covered by the 1.6 This and equipment. safety problems standard may involve hazardous materials, operations, This standard does not purport to address all of the associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. 2. Referenced Documents 2.1 ASTM Standards: D618 Methods of Conditioning Plastics and Electrical Insulating 2 Materials for Testing 2 D695 Test Method of Compressive Properties of Rigid Plastics 2,3 D833 Definitions of Terms Relating to Plastics 2,3 D1600 Abbreviations of Terms Relating to Plastics D2122 Method of Determining Dimensions of Thermoplastic Pipe and 3 Fittings F405 Specification for Corrugated Polyethylene (PE) Tubing and 3 Fittings 3 F412 Definitions of Terms Relating to Plastic Piping Systems 2 3. Significance and Use 3.1 The low-pressure air test provides for the detection of damaged installed pipe or improper jointing and is a test which determines the rate at which air under pressure escapes from an isolated section of sewer. 3.2 The rate of air loss is intended to indicate the presence or absence of installed pipe damage. 3.3 Whether or not the joints have been properly installed. 3.4 The test is not intended to indicate water leakage limits and cannot be used as a measure of leakage under service conditions for infiltration or exfiltrations. 4. S~mmary of Test Method 4.1 pressure, test if The section of the line to be tested is plu§ged. Air, at low is introduced into the plugged line. The line passes the the rate of air loss, as measured by pressure drop, does not exceed a specified amount in a specified time. This may be determined by the use of Table I, or calculated by use of the formulas in Section 9.1. 5. Hazards 5.1 through lack overpressuri zed important that The low pressure air test may be dangerous to personnel if, of understanding or carelessness, a line is or plugs are installed improperly. It is extremely the various plugs be installed so as to prevent the sudden expulsion of a poorly installed or partially inflated plug. As an example of the hazard, a force of 250 lbf (1112 N) is exerted on an 8-in. (200-mm) plug by an internal pressure of 5 psi (34 kPa). Observe the following safety precautions: 5.1.1 No one shall be allowed in the manholes during testing because of the hazards. 5.1.2 Install all plugs securely. 5.1.3 When lines are to be tested, it will be necessary that the plugs be braced as an added safety factor. 5.1.4 Do not overpressurize the lines. 5.1.5 Do not exceed 9 psig internal pressure at any time. 6. Preparation of the Line 6.1 The section of sewer line to be tested shall be flushed and cleaned prior to conducting the low pressure air test. This serves to eliminate debris, as well as, wet the pipe and produce the most consistent results. ?. Procedures 7.1 inflatable branches, laterals, will be plugged to Isolate the section of sewer line to be tested by means of stoppers or other suitable test plugs. The ends of all tees, wyes and stubs to be included in the test prevent air leakage. All plugs will be securely braced O~e of the plugs connecting a hose hose to the inlet to prevent possible blow-out due to the internal air pressure. should have an inlet tap, or other provision for to a portable air control source. Connect the air tap and portable air control source. The air equipment will consist of necessary valves and pressure gauges to control air source. The air equipment will consist of necessary valves and pressure gauges to control the rate at which air flows into the test section and to enable monitoring of the air pressure within the test section. Add air slowly to the test section until the pressure inside the pipe is raised to 4.0 psig. After the pressure of 4.0 psig is obtained, regulate the air supply so that the pressure is maintained between 3.5 to 4.0 psig for a period of two minutes. This allows the air temperature to stabilize in equilibrium with the temperature of the pipe walls. The pressure will normally drop slightly until equilibri~m is obtained. During this period all assessable plugs should be checked with soap solution to detect any plug leakage. 7.2 Determine the rate of air loss by either the constant pressure method or the time pressure drop method. 5 7.2.1 Constant Pressure Method: Air is supplied to the pipe test section at a rate sufficient to maintain a gauge pressure of 3.0 psi. The rate of air flow in cubic feet per minute is read directly by the means of a rotometer. The rate of air flow shall be Corrected for pressure and temperature under standard conditions. The requirements for air loss under the "Constant Pressure" method shall be considered satisfied if the air loss does not exceed a rate of 0.0015 cfm per square foot of internal pipe surface area. Air is supplied to the pipe test section at a rate sufficient to maintain a gauge pressure of 3.00 psig. The rate of air flow in cubic feet per minute is read directly by means of a rotometer. 7.2.2 Time Pressure Drop Method: 1) Air is slowly introduced into the section of pipe to be tested, until the air pressure is raised to approximately 4.0 psig. The air shall be allowed to stabilize for a period of two minutes. The air supply is disconnected and the test pressure allowed to decrease to 3.5 psig. The time required for the test pressure to drop from 3.5 psig to 2.5 psig is determined, end this time interval is then compared to the required time to determine if the rate of air loss is within the allowable. 2) Minimum holding times required per pipe diameter are shown in the Table 1. all air should be conducted. 7.3 Upon completion of the test, the bleeder valve is opened and air is allowed to escape. Plugs should not be removed until all pressure in the test section has been released. Also, no one allowed in the trench or manhole while the test is being 6 8. Apparatus 8.1 Pings mechanical or pneumatic type designed to resist internal test pressure without bracing or blocking. 8.2 with a pressure pressure pressure psi. Air Compressor - a properly calibrated pOrtable air source singular control panel containing a main shut off valve, re~ulatinq valve, a 9 psig pressure relief valve input gauge, and a continuous monitoring pressure gauge having range from 0 to at least 10 psi and an accuracy of + 0.04 9. ?e~t Time 9.1 Test time criteria - No test section shall be accepted if air loss is more than 0.0015 cubic feet per minute per square foot. Calculate all test time by the following formula. ? ~ 0.085 PK / (; T= 8hottest time in seconds allowed for air pressure to drop 1.0 psig. K = 0.000419 DL but not less than 1.0 Q = 0.0015 cubic feet/minute/square feet of internal surface D = Normal pipe diameter in inches. L = Length of pipe being tested in feet. Table I contains the specified minimum times required for 1.00 psig pressure drop from a starting pressure of 3.5 psig to 2.5 psig. 7 9.2 in Table excessive falls the determine If pressure drops 1.0 psig before the appropriate time shown I has elapsed, the air loss rate shall be considered ~nd the section of pipe has failed the test. If the line test then segmented testing may be utilized solely to the location of leaks. Once leaks are located and repaired, the completed pipe installation meet the requirements of this test. 9.3 diameter of 1.0 shall be retested and required to Efficient testing of long sections and or sections of larger pipes, a time pressure drop of 0.5 psig may be used in lieu psig timed pressure drop. If a 0.5 psig pressure drop is used the appropriate required test time shall be exactly half as long as shown on Table I. Table II is provided for convience. 9.4 It is not necessary to hold the test for the entire period of time in Table I or Table II when it is clearly evident that the rate of air loss is less than the allowable, and is authorized by the approving authority. APPENDIX (NON X.i.1 In order to demonstrate the technique of applying this test method the following examples have been prepared. The examples have been designed to illustrate the use of Tables and the formula. X.l.l.2 A manhole to manhole reach of nominal 12 inch pipe is 350 feet long. No lateral connections exist in the reach. What is the required test time for a 0.5 psig pressure drop? Solution: The required test time can be read directly form Table II. For 350 feet of 12 inch pipe, the required test time is 9:58 (9 minutes and 58 seconds). X.l.l.3 A 350 foot section of nominal 12 inch pipe is ready for testing. A total of 128 feet of 4 inch lateral sewer pipe is connected to the 350 foot section and will be included in the test. What will be their required test time for a 0.5 psig pressure drop? Solution: Lateral sewers may be disregarded when selecting test times Ieee Section 9.4). Therefore, the required test time will be the same as for Example A, i.e., 9 minutes and 58 seconds. **NOTE: If the lateral sewers had not been disregarded, the required test time would be 10 minutes and 22 seconds, i.e., only 24 seconds longer. X.l.l.4 Wh~t should the required test time be for a 1.0 psig pressure drop in 327 feet of nominal 8 inch diameter pipe between two manholes? Solution: The exact test time is easily calculated by using Table I. Table ! is used because a 1.0 psig pressure drop is specified. Since 327 feet exceeds the 298 foot length associated with the minimum test time for an 8 inch pipeline, the forth column in Table I shall be used to quickly calculate the required test time as follows: T = 1.520 L = 1.52 x 327 = 497 seconds Therefore, the required test time for a 1.0 psig pressure drop is 497 seconds or 8 minutes and 17 seconds. X.l.l.5 A manhole feet long. What is drop? to manhole reach of nominal 24 inch pipe is 82 the required test time for a 0.5 psig pressure Solution: Table II must be used because a 0.5 peig pressure drop is specified. Since 82 feet is less than the 99 foot length associated with the minimum test time for a 24 inch Pipeline, the minimum test time shall apply. Thus, the required test time for a 0.5 psig pressure drop must be 11:20 (11 minutes and 20 seconds). X.l.l.6 readied lateral the 15 and A 412 foot section of nominal 15 inch sewer pipe has been for air testing. A total of 374 feet of nominal 6 inch piping and 148 feet of nominal 4 inch later piping branch off inch sewer line. All laterals have been capped and/or plugged will be tested together with the 15 inch main line. The specified pressure drop which will be timed in 0.5 peig. What is the appropriate test time for this piDe network? Solution: All.lateral sewer sizes and lengths may be disregarded since their influence is generally not significant enough to warrant computation. Table II must be used for a 0.5 psig pressure drop. The fourth column in the table provides the appropriate formula for calculating the required test time because 412 feet is longer than the third column value of 159 feet. T = 2.671L = 2.671 x 412 = 1,100 seconds The required test time is 1,100 seconds or 18 minutes and 20 seconds. Xl.l.7 A manhole to manhole reach of nominal 8 inch pipe is only 100 feet long. A total of 300 feet of nominal 4 inch lateral piping is connected to the 100 foot section end will be included in air testing the section and will be included in air testing the section. What will be the required test time for a 1.0 psig pressure drop? Solution: The required test time can be read directly from Table l, since lateral sewers need not be considered. Thus, for 100 feet of 8 inch pipe, the required holding time is 7:34 (7 minutes and 34 seconds). However, should the section fail to meet this test, the required holding time must be recalculated taking into account the connected laterals. This recalculation is required because the total internal pipe surface area is less than 625 square feet. Total Area : 12 : 3.14 ~8 x 100) : (4 x 300~ 12 : 524 square feet Thus using the equation provided in Section 9.4, the required test ti~e should be recomputed as follows: K = 0.000419 (8 x 100) + (4 x 300) --> K 1.0 K will always be 1.0 when the total area is less than = 0.838 0.838 < 1.0 ** NOTE: 625 square feet. T= 0.085 ~.~8A x 100)+ (4~4 x 300)9 L (8 loo) _- 300)_j 1.O 0.0015 T = 317 seconds The required test time is actually only 317 seconds or 5 minutes and 17 seconds for a 1.0 psig pressure drop. Therefore, if the section is able to meet this test time, it shall be passed. ** NOTE: - For a holding time would seconds. specified 0.5 psig pressure drop, the test be only half as long, i.e., 2 minutes and 38