Amberpoint BP 2R-LR060103FIELD DENSITY TESTING
Report Number: 94051418.0033
Service Date: December 3(~ 2005
Client:
Transwestern Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd Ste 600 W
Dallas TX 75244
'lrerracon
8901 Carpenter Fwvy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: January 03, 2006
Project: AmberPoint Business Park
Buildings 4, 5 and 6
505 South Royal Lane
Coppell, TX
Project No.: 94051418
Material Information Lab Test Data Proiect Requirements
Optimum Max. Lab
Water Dry Unit Water Minimum Dry
Material Laboratory Content Weight Content Unit Weight
No. Test Method Description and Classification (%) (pcf) (%) (% compaction)
1. 514180001 ASTM D 698 Brown clay w/sand 19.0 101.2 >/= +3 93
2. 514180003 ASTM D 698 Reddish brown sandy clay 14.8 112.3 >/= +3 93
Field Test Data Probe Water Dry Unit Dry Unit
Test Lift/ Mat. Depth Content Weight Weight
No. Test Location Elevation No. (inches) (%) (pct') (% compaction)
Building #4, Building Pad Moisture
Conditioned
219 60' N & 25' W of SE corner 1' BFG 1 6 23.9 97.9 97
220 100' N & 45' W of SE corner 1' BFG 1 6 24.4 96.3 95
221 175' N & 90' W of SE corner 1' BFG 1 6 23.2 98.4 97
222 250' N & 60' W of SE corner 1' BFG 2 6 19.6 106.6 95
223 325' N & 75' W of SE corner 1' BFG 1 6 24.2 96.8 96
224 400' N & 35' W of SE corner 1' BFG 1 6 23.7 98.0 97
225 475' N & 50' W of SE corner 1' BFG 2 6 20.4 105.8 94
226 550' N & 80' W of SE corner 1' BFG 2 6 20.9 105.0 93
227 70' N & 110' W of SE comer SG 2 6 19.1 107.8 96
228 150' N & 150' W of SE corner SG 2 6 19.9 107.0 95
229 225' N & 180' W of SE corner SG 2 6 21.0 105.6 94
230 300' N & 140' W of SE corner SG 2 6 20.7 106.1 94
231 375' N & 125' W of SE corner SG 2 6 21.6 105.0 93
Datum: BFG = below final grade SG = subgrade
Comments:
Test results on this report meet project specification.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclush/ely for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
,FIELD DENSITY TESTING 'lrerracon
Client:Transwestern Commercial Services
Project Number:94051418
Report Number: 94051418.0033
Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture
condition.
Field Test Method:ASTM D2922, ASTM D3017
Technician: Carlos D. Dotson
Field Results Reported To: Superintendent
Report Distribution: ~
(1) Transweslem Commercial Services (1) O'Brien & Assoc
(1) Cityof Cop~ell TX (1) TechniStructures Reviewed by: __
(1) City of Coppell TX Hussein H. Abusaad, P.E.
(1) Rogers O'Brien Construction Co Senior Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
FIELD DENSITY TESTING
Report Number: 94051418.0029
Service Date: December 28, 2005
Client:
Transwestern Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd Ste 600 W
Dallas TX 75244
Report Date: January 03, 2006
Project:
Project No.:
'lrerracon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
AmberPoint Business Park
Buildings 4, 5 and 6
505 South Royal Lane
Coppell, TX
94051418
Material Information
Material Laboratory
No. Test Method
Description and Classification
Lab Test Data Pmiect Requirements
Optimum Max. Lab
Water Dry Unit Water Minimum Dry
Content Weight Content Unit Weight
(%) (pcf) (%) (% compaction)
1. 514180003 ASTM D 698 Reddish brown sandy clay
Field Test Data Probe
Test Lift/ Mat. Depth
No. Test Location Elevation No. (inches)
195
196
197
198
199
2OO
201
202
203
204
205
206
Datum:
Building #4, Building Pad Moisture
Conditioned
60' N & 20' W of SE corner 3' BFG 1 6
100' N & 40' W of SE corner 3' BFG 1 6
175' N & 80' W of SE corner 3'BFG 1 6
250' N & 30' W of SE corner 3' BFG 1 6
325' N & 60' W of SE corner 3' BFG 1 6
400' N & 90' W of SE comer 3' BFG 1 6
475' N & 50' W of SE corner 3' BFG 1 6
550' N & 75' W of SE corner 3' BFG 1 6
Retest of Test #196, dated 12/28/05 3' BFG 1 6
Retest of Test # 197, dated 12/28/05 3' BFG 1 6
Retest of Test # 198, dated 12/28/05 3' BFG 1 6
Retest of Test #202, dated 12/28/05 3' BFG 1 6
BFG = below final grade
14.8 112.3 >/= +3 93
Water Dry Unit Dry Unit
Content Weight Weight
(%) (pc0 (% compaction)
21.6 104.0 93
24.3 97.9 87
23.9 99.6 89 *
25.1 93.3 83 *
20.6 105.4 94
21.6 104.7 93
20.4 106.3 95
25.4 93.0 83 *
22.0 104.4 93
21.4 105.6 94
21.9 105.0 93
22.4 104,0 93
Comments:
An asterisk {*) appears next to test results which do NOT meet the project specifications,
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
rnateriais.
,FIELD DENSITY TESTING 'lrerracon
Client:Transwestem Commercial Services Project Number:94051418
Report Number: 9405'i418.0029
Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture
condition.
Field Test Method:ASTM D2922, ASTM D3017
Gauge ID: 35367
Technician: Carlos D. Dotson
Field Results Reported To: Superintendent
Report Distribution:
(1) Tra~swestern Commercial Services
(1) City of Coppe~l TX
(1) City of Coppell TX
(1) Rogers O'Brien Construction Co
(1) O'Brlen & Assoc
(1) TechniStructures
Reviewed by:
Hussein H. Abusaad, P.E.
Senior Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94051418.0025
Service Date: December 23, 2005
Client:
Transwestern Commercial Services
Attn: Jim Gaspard
5001 Spdng Valley Rd Ste 600 W
Dallas TX 75244
rerracon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: January 03, 2006
Project: AmberPoint Business Park
Buildings 4, 5 and 6
505 South Royal Lane
Coppell, TX
Project No.: 94051418
Material Information
Specified Strength: 4200 psi (~ 28 Days
Batch Time: Plant: 1
Supplier: Redi-Mix Concrete
Truck No: 136
Mix i.D. No.: 604
Water Added Onsite Before Test: 10Gallons
Water Added Onsite After Test:
Field Test Data Test
Ticket No: 159614
0 Gallons
Result
Slump, inches: 1.00
Air Content, %: 3.8
Concrete Temperature,° F: 73
Ambient Temperature, o F: 63
Plastic Unit Weight, pcf: 148.8
Laboratory Test Data
set Specimen Diameter Area
No. ID (inches) (sq. inches)
1 1 6.00 28.27
Sample Information
sample Time: 2:43 Date Cast: December 23, 2005
Technician: Burl E. Thomas
Weather Conditions:Clear
Accumulative Yards: 8
Placement Method: Bucket
Sample Locations: Line SR/1, Sta. 2+83
Placement Location: Manhole
Specification
Test Method
ASTM C143
ASTM C231
ASTM C1064
ASTM C1064
ASTM c138
Age at Maximum Compressive
Date Test Load Strength
Tested (days) (lbs) (psi)
12/30/2005 7 163,960 5,800
1 2 01/20/2006 28
1 3 01/20/2006 28
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Burl E. Thomas
Repeal Distribution: ~
(1) Transwestern Commercial Services (1) O'Brien & Assoc
(1) City of Ceppell TX (1) TechniStructures Reviewed by:
(1) City of Coppell TX Husse~n H Abusaad, P E
(1) Rogers O'Brien Construction Co Senior Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein ere only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials. Page 1 of 1 °~ PDR/R01F~t~re~e¥
FIELD DENSITY TESTING
Report Number: 94051418.0030
Service Date: December 29, 2005
']rerracon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client:
Transwestern Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd Ste 600 W
Dallas TX 75244
Report Date: January 03, 2006
Project: AmberPoint Business Park
Buildings 4, 5 and 6
505 South Royal Lane
Coppell, TX
Project No.: 94051418
Material Information Lab Test Data Project Requirements
Optimum Max. Lab
Water Dry Unit Water Minimum Dry
Material Laboratory Content Weight Content Unit Weight
No. Test Method Description and Classification (%) (pcO (%) (% compaction)
1. 514180001 ASTM D 698 Brown clay w/sand 19.0 101.2 >/= +4 92
2. 514180003 ASTM D 696 Reddish brown sandy clay 14.8 112.3 >/= +4 92
Field Test Data Probe Water Dry Unit Dry Unit
Test Lift/ Mat. Depth Content Weight Weight
No. Test Location Elevation No. (inches) (%) (pcO (% compaction)
Building Pad
207 60' N & 25' W of SE corner 2' BFG 1 6 23.8 96~1 95
208 100' N & 45' W of SE corner 2' BFG 1 6 23.3 98.2 97
209 175' N & 90' W of SE corner 2' BFG 1 6 24.1 95.4 94
210 250' N & 60' W of SE corner 2'BFG 2 6 19.9 107.3 96
211 325' N & 75' W of SE corner 2' BFG 1 6 23.6 97.0 96
212 400' N & 35' W of SE corner 2' BFG 1 6 24.5 94.4 93
213 475' N & 50' W of SE corner 2'BFG 2 6 21.7 104.9 93
214 550' N & 80' W of SE corner 2'BFG 2 6 20.9 106.0 94
Datum: BFG = below final grade
Comments:
Test results on this report meet project specification.
Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture
condition.
Field Test Method~,STM D2922, ASTM D3017
Technician: Carlos D. Dotson
Field Results Reported To: Superintendent
Report Distribution: ~
(1) Transwestern Commercial Sel~ices (1) O*Brien & Assoc
(1) City of Coppel[ TX (1) TechniStructures Reviewed by:
(1) City of Co@pel[ TX Hussein H. Abusaad, P E.
(1) Rogers O'Brien Construclion Co Senior Project Manager
The tests were performed in genera[ accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
FIELD DENSITY TESTING
Report Number: 94051418.0031
Service Date: December 29, 2005
Client:
Transwestern Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd Ste 600 W
Dallas TX 75244
Report Date: January 03, 2006
Project:
Project No.:
'1 rerracon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
AmberPoint Business Park
Buildings 4, 5 and 6
505 South Royal Lane
Coppell, TX
94051418
Material Information Lab Test Data Project Requirements
Optimum Max. Lab
Water Dry Unit Water Minimum Dry
Material Laboratory Content Weight Content Unit Weight
No. Test Method Description and Classification (%) (pct~ (%) (% compaction)
1. 514180002 ASTM D 698 Tan clayey sand
12.4 118.0 -1/+3 95
Field Test Data Probe Water Dry Unit Dry Unit
Test Lift/ Mat. Depth Content Weight Weight
No. Test Location Elevation No. (inches) (%) (pcf) (% compaction)
8" Sanitary Sewer, Line S
215 Sta. 2+20 3' BFG 1 6 13.0 117.0 99
216 sra. 2+20 2' BFG 1 6 13.4 116.4 99
217 Sta. 2+20 1' BFG 1 6 12.9 117.7 100
218 Sta. 2+20 Final 1 6 13.6 116.0 98
Datum: BFG = below final grade
Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture
condition.
Field Test Method:ASTM D2922, ASTM D3017
Technician: Carlos D. Dotson
Field Results Reported To: Superintendent
Report Distribution: ~
(1) Transwestem Commercial Se~ices (1) O'Brien & Assoc
(1) City of Coppeil TX (1) TechniStructures Reviewed by: _
(1) city of Coppell TX Husaein H. Abusaad, P.E,
(1) Rogers O'Brien Construction Co Senior Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods, This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
FIELD DENSITY TESTING
Report Number: 94051418.0032
Service Date: December 27, 2005
Client:
Transwestern Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd Ste 600 W
Dallas TX 75244
'lrerracon
8901 Carpenter Frvvy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: January 03, 2006
Project: AmberPoint Business Park
Buildings 4, 5 and 6
505 South Royal Lane
Coppell, TX
Project No.: 94051418
Material Information Lab Test Data Proiect Requirements
Optimum Max. Lab
Water Dry Unit Water Minimum Dry
Material Laboratory Content Weight Content Unit Weight
No. Test Method Description and Classification (%) (pc0 (%) (% compaction)
1. 514180002 ASTM D 698 Tan clayey sand
12.4 118.0 -2/+2 95
Field Test Data Probe Water Dry Unit Dry Unit
Test Lift/ Mat. Depth Content Weight Weight
No. Test Location Elevation No. (inches) (%) (pct~ (% compaction)
8" Sanitary Sewer Line, SR1
192 Sta. 1+80 2' BFG 1 6 13.9 115.8 98
193 Sta. 1+80 1' BFG 1 6 14.1 115.0 97
194 Sta. 1+80 Final 1 6 12.8 117.0 99
Datum: BFG = below final grade
Comments:
Test results on this report meet project specification.
Services - Pedorm in-place density and moisture content tests to determine degree of compaction and material moisture
condition.
Field Test Method:ASTM D2922, ASTM D3017
Gauge ID: 35367
Technician: Carlos D. Dotson
Field Results Reported To: Superintendent
Report Distribution:
(1) Transwestem Commercial Services
(1) City of Coppell TX
(1) City of Coppel~ TX
(1) Rogers O'Brien Construction Co
(1) O'Brien & Assoc
(1) TechniStructures
Reviewed by:
Hussein H. Abusaad, P.E
Senior Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.