Amberpoint BP 2R-LR060119CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94051418.0061 Service Date: January 11,2006 Client: mranswestem Commercial Services Attn: Jim Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 'lreffacon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Report Date: January 19, 2006 Project: AmberPoint Business Park Buildings 4, 5 and 6 505 South Royal Lane Coppell, TX Project No.: 94051418 Material Information Specified Strength: 4200 psi @ 28 Days Batch Time: 1:34pm Plant: 6 Supplier: Lattimore Materials Co. Truck No: 1109 Mix i.D. No.: 1851 Ticket No: 626867 Sample Information Sample Time: 2:35pm Cate Cast: January 11,2006 Technician: Daniel J. Crogos Weather Conditions: Sunny, windy Accumulative Yards: 10 Placement Method: Bucket Sample Locations: Inlet Walls Placement Location: Water Drain Inlet at the comer of Northpoint and Sandy Lake Field Test Data Test Result Slump, inches: 5.25 Air Content, %: 4.7 Concrete Temperature,° F: 71 Ambient Temperature, o F: 73 Plastic Unit Weight, pcf: 140.4 Laboratory Test Data Age at Set Specimen Diameter Area Cate Test No. ID (inches) (sq. inches) Tested (days) 1 1 6.0028.27 01/18/2006 7 1 2 02/08/2006 28 1 3 02/08/2006 28 Specification 1 4 03/08/2006 56 Test Method ASTM C143 ASTM C231 ASTM C1064 ASTM Cl 064 ASTM C138 Maximum Compressive Load Strength (lbs) (psi) 106,420 3,760 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Daniel J. Drogos Report Distribution: (1) Transwestern Commercial Se~ces (1) O'Brien & Assoc (1) City of Coppell TX (1) TechniStmctures Reviewed by: (1) City of Coppell TX Hus d, P.E. (1) Rogers O'Brien Construction Co Senior Project Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This repoil is exclusively for the use of the client indicated above and shall not be raproducad except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 1 FIELD DENSITY TESTING Report Number: 94051419.0005 Service Date: January 6, 2006 Client: Big Sky Construction Attn: John Clark 2611 North Beltline Ste 105 Sunnyvale TX 75182 'lrerracon 8901 Carpenter Frwy, Ste #100 Dal[as, Texas 75247 (214) 630-1010 Report Date: January 19, 2006 Project: N. Texas P&DC West Dock Expansion Bethel & Royal Coppell, TX Project No.: 94051419 Material Information Lab Test Data Proiect Requirements Optimum Max. Lab Water Dry Unit Water Minimum Dry Material Laboratory Content Weight Content Unit Weight No. Test Method Description and Classification (%) (pct~ (%) (% compaction) 1. 514190001 ASTM D 698 Medium brown sandy clay 22.5 95.9 +2/+6 95 Field Test Data Probe Water Dry Unit Dry Unit Test Lift/ Mat. Depth Content Weight Weight No. Test Location Elevation No. (inches) (%) (pc0 (%compaction) Spread Fotting 15 5' W & 10' S of SW corner of building Final 1 6 19.9 * 95.4 99 16 5' W & 20' S of SW corner of building Final 1 6 20.6 * 96.9 100+ 17 5' W & 60' S of SW corner of building Final 1 6 18.8 * 96.4 100+ Comments: An asterisk (*) appears next to test results which do NOT meet the project specifications, Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture condition. Field Test Method~,STM D2922, ASTM D3017 Technician: Armando Rendon Field Results Reported To: Contractor Report Distribution: (1) Big Sky Construction (1) City of Coppell TX (1) City of Coppell TX Reviewed by: s~ o~~ The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples teated at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. FIELD DENSITY TESTING Report Number: 94051190.0184 Service Date: January 11, 2006 Client: Coppell Trade Center LP Attn: Bennet Ratliff 5055 Keller Springs Rd Ste 300 Addison TX 75001 Report Date: January 19, 2006 Project: ' rEff lcon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Coppell Trade Center - Bldg C NWC Sandy Lake/Freeport Pkwy Coppell, TX Project No.: 94051190 Material Information Lab Test Data Prelect Requirements Optimum Max. Lab Water D~J Unit Water Minimum Dry Material Laboratory Content Weight Content Unit Weight No. Test Method Description and Classification (%) (pcf) (%) (% compaction) 1. 510810065 ASTM D 698 Crashed limestone flexible base 8.4 124.8 >/-- Opt 95 Field Test Data Probe Water Dry Unit Dry Unit Test LiftJ Mat. Depth Content Weight Weight No. Test Location Elevation No. (inches) (%) (pot) (% compaction) Loading Dock Ramp 450 Grid Line #2 BG 1 6 11.1 120.4 96 451 Grid Line #3 BG 1 6 12,0 119.0 95 Datum: BG = below grade Comments: Test results on this report meet project specification. Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture condition, Field Test Method:ASTM D2922, ASTM D3017 Technician: Francisco Morillo Field Results Reported To: Bob L, Superintendent Re port Dist ri bution: (1) Coppell Trade Center LP (1) IVlerriman Assoc (1) TechniStr~ctures (1) McFadden & Miller Reviewed by: (1) City of Coppell TX (1) Macatee Engineering Inc Robert D. Ray, ,~. (1) City of Coppe~l TX Senior Proje~vlanager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not bo reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparentiy similar or identical materials. Page 1 of 1 REPORT OF LIME DEPTH CHECKS ]rerfacon Date of Service: Client No.: Client: Contractor: General Location: Test Method: Comments: None 01/19/06 50854 Transwestem Commercial Services 5001 Spring Valley Rd Ste 600 W Dallas, TX 75244 Rogers-O'Brien Construction Co. Building Pad//4 NTCOG Report No.: Project No.: Project: 94051418.0102 94051418 AmberPoint Business Park Buildings 4, 5 and 6 505 South Royal Lane Coppell, TX REQUIRED DEPTH ACTUAL DEPTH TEST LOCATION OF LIME OF LIME NO. (in.) (in.) 1 20'N&20'WofSEcomer 8 9 1/2 2 100' N & 100' WofSE comer 8 9 3/4 3 200' N & 200' W of SE comer 8 10 4 200'N & 300' W of SE comer 8 9 3/4 5 20' N &100' W of SE comer 8 9 1/2 6 100'N&300'WofSEcomer 8 9 3/8 7 20'N&300'WofSEcomer 8 9 1/2 Technician: A. Rendon Report Distribution: (1) Transwestern Commercial Services (1) City of Coppell TX (1) City of Coppell TX 309as (1) Rogers O'Brien Construction Co (1) O'Brien & Assoc (1) TechniStructures Hussein H. Abusaad, P.E. Senior Project Manager This repor~ is exclusively for the use of the client indicated above and shall not be reproduced in full without written approval of Terracon.