Belt Line Trade-CS051027DEVELOPMENT REVIEW COMMITTEE
ENGINEERING COMMENTS
(TEM:
Beltline Trade Center~ Lot 1~ Block 2~ Site Plan, to allow the development of
an approximate 23,336-square-foot office/warehouse building on approximately
three acres of property located along the north side of Beltline Road,
approximately 3,000 feet east of North Lake Drive, at the request of Edward
Eckart, Goodwin and Marshall, Inc.
STAFF REP.: Gary Sieb PROJECT ID# SPA-05-0054
DRC DA TE: October 2 7, 2005 and November 3, 2005
CONTACT: Kenneth M. Griffin, P.E., Dir. of Engineering/Public Works 972/304-3686
COMMENT STATUS: ~"PRELIMINARY F!NAL ~c~r~
AFTER P&Z
Site Plan:
1. The orientation of the drawings should be consistent throughout the entire drawing
set.
2. Show the location of the FDC on this sheet.
3. Be advised that the portion of Belt Line Road adjacent to the site lies within the Dallas
City limits. The proposed modifications to the medians should be approved and
permitted by the City of Dallas. Light standards in the medians may need to be
relocated.
DEVELOPMENT REVIEW COMMITTEE
ENGINEERING COMMENTS
ITEM:
Beltline Trade Center~ Lot IT Block 2~ Minor Plat~ to allow the development
of an approximate 23,336-square-foot office/warehouse building on
approximately three acres of property located along the north side of Beltline
Road, approximately 3,000 feet east of North Lake Drive, at the request of
Edward Eckart, Goodwin and Marshall, Inc.
STAFF REP.: Gary Sieb PROJECT ID# MP-05-0055
DRC DA TE: October 27, 2005 and November 3, 2005
CONTACT: Kenneth M. Gri~qn, P.E., Dir. o~ En~ineering/Public Works 972/304-3686
COMMENT STATUS: ,~PRELIMINARY ,~tAT ,,,,~,~ A · ~ ~,7·C~n · ~
A ~vo P&Z
Minor Plat:
1. Additional easements will be required based on changes made to the proposed water
design.
2. Should the "Proposed Sanitary Sewer Easement (By Separate Instrument)" be
dedicated by this plat?
Preliminary Utility Layout:
1. The overall design of water and sewer for this site is based on the proposed utility
design for Building "A," Lot 1, Block 1. Be advised that the following utility
comments assume that Building "A" improvements are constructed prior to the
approval of the project under review.
2. The 8" water line is considered a private fire line. An 8" DDC should be placed in a
25'X25' easement near the Belt Line Road property line at both locations where the 8"
line tees off the 10" line. The proposed 6" DDC is not necessary.
3. Place an $" main-line valve mid-way along the fire line. (Minimum valve spacing is
500'.)
4. Show the fire lane on this sheet. Fire hydrants should be located 3'-6' from the fire
lane.
5. Show the location of the FDC on this sheet. The FDC should be located within 50' of a
fire hydrant and on the same side of the fire lane as the fire hydrant.
6. Provide a blow-off valve at the end of the 10" water line.
Preliminary Storm Drain Layout:
1. Provide documentation indicating that the existing channel has the capacity to accept
the flow from this site.