Coppell Trade-LR060227CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94051190.0200 Service Date: January 27, 2006 'lrerracon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Coppell Trade Center LP Attn: Bennet Ratliff 5055 Keller Springs Rd Ste 300 Addison TX 75001 Material Information Specified Strength: 4000 psi ~ 28 Days Batch Time: 6:48am Plant: 141 Supplier: TXI Truck No: 102 Ticket No: 196067 Mix I.D. No.: 8206 Water Added Onsite Before Test: 0Gallons Water Added Onsite After Test: 0 Gallons Report Date: Februa~,Q~27, 2006 Project: ~jT,~e~Sell Trade Center- B[d~,,~J~ f Nwc sanuy Lake/ j -% rPk - Coppell, TX ~J Project No.: 94051190 ~,/' "~J Sample Information Date Cast: January 27, 2006 Time: 7:30am Technician: Kudret Aksu ~'~ Weather Conditions: Clear ~ o ~ · ~ Accumulative Yards: 20/90 Placement Method: Pump Sample Locations: SW corner of Placement Are, Placement Location: Pavement, SW corner of Building, next to Ramp Retaining Wall Field Test Data Test Specification 3-5 3-6 Result Slump, inches: 5.00 Air Content, %: 4.8 Concrete Temperaturep F: 59 Ambient Temperature,o F: 46 Plastic Unit Weight, pcf: 144.2 Laboratory Test Data Set Specimen Diameter Area No. ID (inches) (sq. inches) 1 1 6.00 28.27 02/03/2006 1 2 6.00 28.27 02/03/2006 1 3 6.00 28.27 02/24/2006 1 4 6.00 28.27 02/24/2006 Date Tested Test Method ASTM C143 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Age at Maximum Compressive Test Load Strength (days) (lbs) (psi) 7 122,170 4,320 7 125,150 4,430 Average (7 Days) 4,380 28 160,930 5,690 28 161,240 5,700 Average (28 Days) 5,700 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. (1) Coppell Trade Center LP (1) Merriman Assoc [nc (1) TechniStructures (1) McFadden & Miller Reviewed by: (1) City of Coppell TX (1) Macatee Engineering Inc ~' -- Robert D. Ray, S.E.T~~ (1) City of Coppell TX Senior Project Ma~er~' The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use df the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.