Coppell Trade-LR060222CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94051190.0194
Service Date: January 24, 2006
'] reffi!lcon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client:
Coppell Trade Center LP
Attn: Bennet Ratliff
5055 Keller Springs Rd Ste 300
Addison TX 75001
Report Date:
Project: ~ppell I raae center
Ooppell, TX
Project No.: 94051190
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 6:49am
Supplier: TXI
Truck No: 101
Mix I.D. No.: B6276
Plant: 141
Ticket No: 192899
Field Test Data
Test
Result
Slump, inches: 5.00
Air Content, %: 5.0
Concrete Temperature, o F: 54
Ambient Temperature, o F: 32
Plastic Unit Weight, pcf: 143.0
Laboratory Test Data
set Specimen Diameter Area
No. ID (inches) (sq. inches)
1 1 6.00 28.27
Sample Information
Date Cast: January 24, 2006
Technician: Polikarp J. Labecki
Weather Conditions~lear sky
Accumulative Yards: 8/16
Placement Method: Direct Discharge
Sample Locations: SW corner
Placement Location: Pavement, W Exit Approach Drive
Specification
3-5
3-7
Time:7:30am
Date
Tested
01/27/2006
Test Method
ASTM C143
ASTM C231
ASTM C1064
ASTM C1064
ASTM C138
Age at Maximum Compressive
Test Load Strength
(days) (lbs) (psi)
3 101,620 3,590
1 2 6.00 28.27 01/31/2006 7 98,740 3,490
1 3 6.00 28.27 01/31/2006 7 101,440 3,590
Average 3,540
1 4 6.00 28.27 02/21/2006 28 128,680 4,550
1 5 6.00 28.27 02/21/2006 28 123,530 4,370
Average 4,460
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Polikarp J. Labecki
Report Distribution:
(1) Coppell Trade Cenler LP
(1) TechniSlructures
(1) City of Coppell TX
(1) City of Coppell TX
(1) Merriman Assoc Inc
(1) McFadden & Miller
(1) Macatee Engineerir~g fnc
Reviewed by: ~
Senior Project ~
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.