Freeport NIP(6)-LR060323CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94061061.0005
Service Date: March 9, 2006
'lrerracon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client:
Pacific Builders
Attn: Brendan Mullen
3360 East Wiley Post Rd Ste 100
Carrollton TX 75006
Report Date: March 23, 2006
Project: Citigroup Add~
R e a~.F./F~s.tatcS e r vi c e s Center
--,---f'T11 Northpoint Drive
Coppell, TX
Project No.: 94061061
Material Information
Specified Strength: 3000 psi @ 28 Days
Batch Time:
Supplier:
Truck No:
Mix I.D. No.:
Contractor Made
Ticket No:
Field Test Data
Test
Result
Slump, inches:
Air Content, %:
Concrete Temperature,o F:
Ambient Temperature,o F:
Plastic Unit Weight, pcf:
Laboratory Test Data
Set Specimen Diameter Area
No. ID (inches) (sq. inches)
1 1 6.00 28.27
1 2 6.00 28.27
1 3 6.00 28.27
Sample Information
Date Cast: February 16, 2006 Time:
Technician: Sampled by contractor
Weather Conditions:
Placement Method:
Sample Locations:
Placement Location: Kitchen plumbing trenches
Specification
Age at Maximum Compressive
Date Test Load Strength
Tested (days) (lbs) (psi)
03~09~2006 21 84,320 2,980
03/16/2006 28 104,410 3,690
03/16/2006 28 106,880 3,780
Average (28 Days) 3,740
Comments: Not tested for plastic unit weight.
Services - Pick up test cylinders cast by others and return them to the laboratory for curing and testing.
Technician: Craig Blackwell
Report Distribution:
(1) Pacific Builders
(1) City of Coppell TX
(1) City of Coppell TX
Reviewed by:
Eric J. Cleveland, ~P.E
Senior Project Engineer
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials