Amberpoint BP 2R-LR060330CONCRETE COMPRESSIVE STRENGTH TEST Report Number 94051418 0204 Service Date February 15, 2006 l~err~con 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Report Date March 30, 2006 Transwestern Commercial Services Project• AmberPoint Business Park Attn David Gunderson Buildings 4, 5 and 6 5001 Spring Valley Rd Ste 600 W 505 South Royal Lane Dallas TX 75244 Coppell, TX Project No 94051418 Material Information Specified Strength 3600 psi @ 28 Days Batch Time 10 29am Plant. On-site Supplier Potter Concrete Truck No 118 Ticket No 103008 Mix I D No 7752 Field Test Data Test Result Slump, inches 5 50 Air Content, % 5 0 Concrete Temperature,o F 70 Ambient Temperature,o F 65 Plastic Unit Weight, pcf• Laboratory Test Data Set Specimen Diameter Area No ID (inches) (sq. inches) 1 1 6 00 28.27 1 2 6 00 28.27 1 3 6 00 28.27 1 4 6 00 28.27 Sample Information Date Cast. February 15, 2006 Time 10 35am Technician AI Rodriguez Weather Conditions Mild Accumulative Yards 40 Placement Method Direct Discharge Sample Locations 100' S of Building along Building Line 2 9 Placement Location Pavement, S of Building #4 Specification Test Method 3-5 ASTM C143 3-6 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Age at Maximum Compressive Date Test Load Strength Tested (days) (ibs) {psi) 02/22/2006 7 113,860 4,030 02/22/2006 7 112,000 3,960 Average (7 Days) 4,000 03/15/2006 28 146,260 5,170 03/15/2006 28 141,170 4,990 Average (28 Days) 5,080 Comments'Not tested for plastic unit weight. Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT fest methods, This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 6 0, PoR~RO,-F~~ekey CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94051418 0204 Service Date• February 15, 2006 l~~rracon 8901 Carpenter Frvvy, Ste #100 Dalias, Texas 75247 {214) 630-1010 Client: Report Date March 30, 2006 Transwestern Commercial Services Project Amberl'oint Business Park Attn David Gunderson Buildings 4, 5 and 6 5001 Spring Valley Rd Ste 600 W 505 South Royal Lane Dallas TX 75244 Coppell, TX Project No 94051418 Material Information Specified Strength 3600 psi @ 28 Days Batch Time 11 56am Plant. On-site Supplier Potter Concrete Truck No 108 Ticket No 103023 Mix I D No 7752 Sample Information Date Cast: February 15, 2006 Time 12 10pm Technician AI Rodriguez Weather Conditions Mild Accumulative Yards 180 Placement Method Direct Discharge Sample Locations 50' S of Building along Building Line 4 0 Placement Location Pavement, S of Building #4 Field Test Data Test Result Specification Test Method Slump, inches 4 50 3-5 ASTM C143 Air Content, % 5 5 3-6 ASTM C231 Concrete Temperatureo F 72 ASTM C1064 Ambient Temperatureo F 68 ASTM C1064 Plastic Unit Weight, pcf~ ASTM C138 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq inches) Tested (days) (Ibs) (psij 2 1 6 00 28 27 02/22/2006 7 114,650 4,050 2 2 6 00 28 27 02/22/2006 7 139,980 4,950 Average (7 Days) 4,500 2 3 6 00 28.27 03/15/2006 28 125,450 4,440 2 4 6 00 28.27 03/15/2006 28 127,730 4,520 Average (28 Daysj 4,480 Comments Not tested for plastic unit weight. Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples The tests were pertormed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shad not be reproduced except in full without the written consent of our company Test results transmitted herein are only applicable to the actual samples tested at the location{s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 6 01-PDRIR01-Future key CONCRETE COMPRESSIVE STRENGTH TEST b 94051418 0204 l~~rr~con Report Num er Service Date Februa 15, 2006 8901 Carpenter Fnnry, ste#1oo rY Dallas, Texas 75247 (214) 630-1010 Client: Report Date March 30, 2006 Transwestern Commercial Services Project: AmberPoint Business Park Attn David Gunderson Buildings 4, 5 and 6 5001 Spring Valley Rd Ste 600 W 505 South Royal Lane Dallas TX 75244 Coppell, TX Project No • 94051418 Maferial Information Specified Strength 3600 psi @ 28 Days Batch Time 12 18pm Plant. On-site Supplier Potter Concrete Truck No 118 Ticket No 103028 Mix I D No 7752 Field Test Data Test Result Slump, inches 4 00 Air Content, % 5 0 Concrete Temperature,o F 76 Ambient Temperature,o F 69 Plastic Unit Weight, pcf~ Laboratory Tesf Data Set Specimen Diameter Area No. ID (inches) (sq inches) 3 1 6 00 28.27 3 2 6 00 28.27 3 3 6 00 28.27 3 4 6 00 28.27 Sample Information Date Cast. February 15, 2006 Time 1 OOpm Technician AI Rodriguez Weather Conditions Warm Placement Method Direct Discharge Sample Locations 40' S of Building along Building Line 6 0 Placement Location Pavement, S of Building #4 Specification Test Method 3-5 ASTM C143 3-6 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Age at Maximum Compressive Date Test Load Strength Tested (days) {Ibs) (psi) 02/22/2006 7 94,470 3,340 02/22/2006 7 113,530 4,010 Average (7 Days) 3,680 03/15/2006 28 154,220 5,450 03/15/2006 28 144,340 5,100 Average (28 Days) 5,280 Comments• Not tested for plastic unit weight. Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 3 of 6 °"oR~°,.F"°'a"aY CONCRETE COMPRESSIVE STRENGTH TEST Report Number 94051418 0204 1(~rracon 8901 Carpenter Frwy, Ste #100 Service Date February 15, 2006 Dallas, Texas 75247 (214) 630-1010 Client: Report Date March 30, 2006 Transwestern Commercial Services Project: AmberPoint Business Park Attn David Gunderson Buildings 4, 5 and 6 5001 Spring Valley Rd Ste 600 W 505 South Royal Lane Dallas TX 75244 Coppell, TX Project No • 94051418 Material Information Specified Strength 3600 psi @ 28 Days Batch Time 1 56pm Plant. On-site Supplier Potter Concrete Truck No 118 Ticket No 103044 Mix I D No 7752 Sample Information Date Cast. February 15, 2006 Time 2 10pm Technician AI Rodriguez Weather Conditions Accumulative Yards 390 Placement Method Direct Discharge Sample Locations 108' S of Building along Building Line 8 0 Placement Location Pavement, S of Building #4 Field Test Data Test Result Specification Test Method Slump, inches 5 50 3-5 ASTM C143 Air Content, % 5 0 3-6 ASTM C231 Concrete Temperature,o F 76 ASTM C1064 Ambient Temperature,o F 70 ASTM C1064 Plastic Unit Weight, pcf• ASTM C138 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days} (Ibs) (psi) 4 1 6 00 28 27 02/22/2006 7 92,790 3,280 4 2 6 00 28.27 02/22/2006 7 98,030 3,470 Average (7 Days) 3,380 4 3 6 00 28.27 03/15/2006 28 123,430 4,360 4 4 6 00 28.27 03/15/2006 28 124,700 4,410 Average (28 Days) 4,390 Comments Not tested for plastic unit weight. Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company Test results transmitted herein are only applicable Po the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 4 of 6 o,-POR~o,-FN~,akaY CONCRETE COMPRESSIVE STRENGTH TEST Report Number 94051418 0204 Service Date. February 15, 2006 l~~rr~con 8901 Carpenter Fnnry, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Report Date March 30, 2006 Transwestern Commercial Services Project: AmberPoint Business Park Attn David Gunderson Buildings 4, 5 and 6 5001 Spring Valley Rd Ste 600 W 505 South Royal Lane Dallas TX 75244 Coppell, TX Project No :94051418 Material lnformafion Specified Strength 3600 psi @ 28 Days Batch Time 2.22pm Plant. On-site Supplier Potter Concrete Truck No 127 Ticket No 103049 Mix I D No 7752 Sample Information Date Cast. February 15, 2006 Time 2 55pm Technician AI Rodriguez Weather Conditions: Accumulative Yards 440 Placement Method Direct Discharge Sample Locations 95' S of Building along Building Line 10 0 Placement Location Pavement, S of Building f#4 Field Test Data Test Result Specification Test Method Slump, inches 4 00 3-5 ASTM C143 Air Content, % 5 0 3-6 ASTM C231 Concrete Temperature,o F 78 ASTM C1064 Ambient Temperature,o F 73 ASTM C1064 Plastic Unit Weight, pcf~ ASTM C138 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (Ibs) (psi) 5 1 6 00 28.27 02/22/2006 7 116,200 4,110 5 2 6 00 28 27 02/22/2006 7 118,860 4,200 Average (7 Days) 4,160 5 3 6 00 28.27 03/15/2006 28 160,780 5,690 5 4 6 00 28.27 03/15/2006 28 125,700 4,450 Average (28 Days) 5,070 Comments. Not tested for plastic unit weight. Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 5 of 6 0'-PDWROLFuIUre Kay CONCRETE COMPRESSIVE STRENGTH TEST R rt N ber• 94051418 0204 l~~rr~con epo um Service Date Februa 15, 2006 8901 Carpenter Frwy, ste#1oo ry Dallas, Texas 75247 (214) 630-1010 Client: Report Date• March 30, 2006 Transwestern Commercial Services Project: AmberPoint Business Park Attn David Gunderson Buildings 4, 5 and 6 5001 Spring Valley Rd Ste 600 W 505 South Royal Lane Dallas TX 75244 Coppell, TX Project No • 94051418 Material Information Specified Strength 3600 psi @ 28 Days Batch Time 3 18pm Plant. On-site Supplier Potter Concrete Truck No 118 Ticket No 103058 Mix I D No 7752 Field Test Data Test Slump, inches. Air Content, Concrete Temperature o F Ambient Temperature,o F Plastic Unit Weight, pcf• Laboratory Test Data Result 5 50 50 80 74 Set Specimen Diameter Area No. ID (inches) (sq. inches) 6 1 6 00 28.27 Sample Information Date Cast. February 15, 2006 Time 4 15pm Technician AI Rodriguez Weather Conditions. Warm Accumulative Yards. 530 Placement Method Direct Discharge Sample Locations 85' S of Building along Building Line 12 5 Placement Location Pavement, S of Building #4 Specification 3-5 3-6 Test Method ASTM C143 ASTM C231 ASTM C1064 ASTM C1064 ASTM C138 Age at Maximum Compressive Date Test Load Strength Tested (days) (Ibs) (psi) 02/22/2006 7 93,190 3,300 6 2 6 00 28.27 02/22/2006 7 90,930 3,220 Average (7 Days) 3,260 6 3 6 00 28.27 03/15/2006 28 127,040 4,490 6 4 6 00 28.27 03/15/2006 28 122,400 4,330 Average (28 Days) 4,410 Comments Not tested for plastic unit weight. Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples Technician AI Rodriguez Report Distribution (1) Transwestern Commercial Services (1) TechniStructures ~/ / /X Y (1) City of Coppell TX (1) Rogers O'Brien Construction Co Reviewed by• / (1) City otCoppell TX n H. Abusaad, P.E. (1) O'Brien 8 Assoc Senior Project Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 6 of 6 Ot-PDRIROt-FN:re Key